Bryant 588A, 589A user manual Install Electrical Connections, High-Voltage Connections

Page 18

Fig. 20 Ð Vertical Discharge Cover Removed

Adhere to the following criteria when selecting, sizing, and installing the duct system:

1.Units are shipped with all 4 duct openings covered. Re- move appropriate panels for intended installation.

2.Select and size ductwork, supply-air registers, and return-air grilles according to American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) recommendations.

3.Use ¯exible transition between rigid ductwork and unit to prevent transmission of vibration. The transition may be screwed or bolted to duct ¯anges. Use suitable gas- kets to ensure weathertight and airtight seal.

4.All units must have ®eld-supplied ®lters or accessory ®l- ter rack installed in the return-air side of the unit. Rec- ommended sizes for ®lters are shown in Tables 1 and 2.

5.Size all ductwork for maximum required air¯ow (either heating or cooling) for unit being installed. Avoid abrupt duct size increases or decreases or performance may be affected.

6.Adequately insulate and weatherproof all ductwork located outdoors. Insulate ducts passing through uncon- ditioned space, and use vapor barrier in accordance with latest issue of Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air Con- ditioning Contractors of America (ACCA) minimum in- stallation standards for heating and air conditioning systems. Secure all ducts to building structure.

7.Flash, weatherproof, and vibration-isolate all openings in building structure in accordance with local codes and good building practices.

X. STEP 10 Ð INSTALL ELECTRICAL CONNECTIONS

WARNING: The unit cabinet must have an uninter- rupted, unbroken electrical ground to minimize the pos- sibility of personal injury if an electrical fault should occur. This ground may consist of an electrical wire con- nected to the unit ground lug in the control compart- ment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code) ANSI/NFPA (latest edition) (in Canada, Cana- dian Electrical Code CSA [Canadian Standards Asso- ciation] C22.1) and local electrical codes. Do not use gas piping as an electrical ground. Failure to adhere to this warning could result in personal injury or death.

CAUTION: Failure to follow these precautions could result in damage to the unit being installed:

1.Make all electrical connections in accordance with NEC ANSI/NFPA (latest edition) and local electrical codes gov- erning such wiring. In Canada, all electrical connec- tions must be in accordance with CSA standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.

2.Use only copper conductor for connections between ®eld- supplied electrical disconnect switch and unit. DO NOT USE ALUMINUM WIRE.

3.Be sure that high-voltage power to unit is within oper- ating voltage range indicated on unit rating plate.

4.Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc. On 3-phase units, ensure phases are balanced within 2%. Consult local power company for correction of improper voltage and/or phase imbalance.

A.High-Voltage Connections

The unit must have a separate electrical service with a ®eld- supplied, waterproof, disconnect switch mounted at, or within sight from, the unit. Refer to the unit rating plate for maxi- mum fuse/circuit breaker size and minimum circuit amps (am- pacity) for wire sizing. See Tables 4A and 4B for electrical data.

The ®eld-supplied disconnect switch box may be mounted on the unit over the high-voltage inlet hole when the standard power and low-voltage entry points are used. See Fig. 2-9 for acceptable location.

Standard Power Entry

Proceed as follows to complete the high-voltage connections to the unit:

1.Connect ground lead to chassis ground connection when using separate ground wire.

2.Run high-voltage leads into unit control box.

3.Locate black and yellow wires connected to line side of contactor.

4.Cut wires at partition where they exit control box.

5.Strip back leads and connect to high voltage leads. On 3-phase units, blue wire is provided stripped back and ready to connect to high voltage lead. See unit wiring label and Fig. 21.

Ð18Ð

Image 18
Contents Contents Safety ConsiderationsGeneral 588A018-042 Without Base Rail, Unit Dimensions Ð2Ð588A018-042 With Optional Base Rail, Unit Dimensions Ð3Ð588A048,060 Without Base Rail, Unit Dimensions Ð4Ð588A048,060 With Optional Base Rail, Unit Dimensions Ð5Ð589A024-036 Without Base Rail, Unit Dimensions Ð6Ð589A024-036 With Optional Base Rail, Unit Dimensions Ð7Ð589A042-060 Without Base Rail, Unit Dimensions Ð8Ð589A042-060 With Optional Base Rail, Unit Dimensions Ð9ÐIII. Ð Field Fabricate Ductwork Receiving and Installation Check EquipmentII. Ð Provide Unit Support IV. Ð Provide ClearancesÐ11Ð Part NumberCurb Weight Unit MAXUnit Units With Optional Base Rail VII. Ð Install Flue HoodVIII. Ð Install GAS Piping VI. Ð Connect Condensate DrainPhysical Data Ð Unit 588A Ð14ÐPhysical Data Ð Unit 589A Ð15ÐIX. Ð Install Duct Connections Conguring Units for Down¯ow Vertical DischargeMaximum Gas Flow Capacity Ð17ÐInternal Length of PIPE, FT² Iron Pipe Diameter Size Install Electrical Connections High-Voltage ConnectionsÐ Electrical Data Ð Unit 588A Ð19ÐÐ Electrical Data Ð Unit 589A Ð20ÐRLA LRA FLA Special Procedures for 208-V Operation High- and Control-Voltage ConnectionsTransformer Protection PRE-START-UPSTART-UP Check for Refrigerant Leaks II. Start UP Heating Section and Make AdjustmentsAdjust Gas Input Check Heating ControlPressure Rated Gas Inputs at Indicated Manifold PressuresGAS Supply Pressure Manifold Natural GAS Propane Number OrificesHeating Temperature Rise F Input Check Burner FlameÐ25Ð III. Start UP Cooling Section and Make Adjustments 208/230-1-60 Wiring Diagram, Units 588A018-060 Ð27Ð208/230-3-60 Wiring Diagram, Units 588A030-060 Ð28Ð460-3-60 Wiring Diagram, Units 588A036-060 Ð29Ð208/230-1-60 Wiring Diagram, Units 589A024-042 Ð30Ð208/230-1-60 Wiring Diagram, Units 589A048,060 Ð31Ð208/230-3-60 Wiring Diagram, Units 589A036-042 Ð32Ð208/230-3-60 Wiring Diagram, Units 589A048,060 Ð33Ð460-3-60 Wiring Diagram, Units 589A036-048 Ð34ÐChecking and Adjusting Refrigerant Charge Indoor Air¯ow and Air¯ow AdjustmentsSpeed Ð Superheat Charging Table, 588A018 Ð Superheat Charging Table, 588A024Ð36Ð Ð Superheat Charging Table, 588A042 Ð Superheat Charging Table, 588A030Ð Superheat Charging Table, 588A036 Ð37ÐÐ Superheat Charging Table, 588A060 Ð38ÐÐ Superheat Charging Table, 589A036 Ð Superheat Charging Table, 589A024Ð Superheat Charging Table, 589A030 Ð39ÐÐ Superheat Charging Table, 589A060 Ð Superheat Charging Table, 589A042Ð Superheat Charging Table, 589A048 Ð40ÐRequired Suction-Tube Temperature F Ð41ÐÐ42Ð Ð43Ð Unit 589ACooling Sequence of Operation MaintenanceWet Coil Pressure Drop Unit Size Airflow Pressure DropIII. Evaporator Blower and Motor AIR FilterII. Unit TOP Removal IV. Flue GAS PassagewaysVII. Burner Ignition VI. Limit SwitchCOMBUSTION-AIR Blower VIII. Main BurnersXII. Refrigerant Circuit XI. Electrical Controls and WiringCondenser FAN XIII. GAS InputTroubleshooting Symptom Cause RemedyIntegrated control IFM runs when itPoor ¯ame characteristics MotorService Training LED OFFPage Preliminary Information START-UP ChecklistTemperatures III. START-UP Electrical
Related manuals
Manual 27 pages 52.72 Kb

589A, 588A specifications

The Bryant 588A is a high-efficiency gas furnace celebrated for its advanced technology and superior performance in residential heating. Known for its reliability and durable construction, this model is ideal for homeowners looking for warmth and comfort during colder months.

One of the standout features of the Bryant 588A is its remarkable AFUE (Annual Fuel Utilization Efficiency) rating, which can reach up to 96.5%. This high efficiency means that a significant portion of the fuel consumed is converted into usable heat, leading to lower energy bills and a reduced carbon footprint. The furnace utilizes a two-stage heating system, which improves comfort levels by providing more consistent temperatures and reducing the frequency of temperature swings in the home.

Another notable characteristic is the incorporation of a multi-speed blower motor. This innovation enhances airflow and optimizes energy use by adjusting the fan speed according to the heating needs of the home. The variable speed operation also helps to minimize noise levels, creating a quieter environment compared to traditional single-speed furnaces.

The Bryant 588A features an advanced control system that allows for better system management and can be integrated with smart home technologies. This allows homeowners to monitor and adjust their heating settings remotely, offering convenience and efficiency. Additionally, the furnace is compatible with Bryant’s Evolution System, which provides advanced diagnostic features and improved energy performance.

Durability is a key characteristic of the Bryant 588A, as it is constructed with a heavy-duty cabinet designed to withstand the rigors of daily use and harsh weather conditions. The unit also includes a corrosion-resistant heat exchanger, ensuring longevity and reliability.

Furthermore, the Bryant 588A operates quietly, thanks to its insulated cabinet and advanced design. This feature is especially appreciated by homeowners seeking a peaceful living environment free from disruptive noises typically associated with heating systems.

In summary, the Bryant 588A gas furnace combines high efficiency, innovative technology, and durable construction. Its effective heating capabilities paired with user-friendly features make it a smart investment for anyone looking to enhance their home heating system while enjoying lower energy costs and increased comfort.