Bryant 588A, 589A user manual Troubleshooting, Symptom Cause Remedy

Page 48

TROUBLESHOOTING

Cooling

SYMPTOM

CAUSE

REMEDY

 

 

 

Compressor and

Power failure

Call power company.

condenser fan will

 

 

Fuse blown or circuit breaker tripped

Replace fuse or reset circuit breaker.

not start.

Defective thermostat, contactor, transformer,

Replace component.

 

 

or control relay

 

 

 

 

 

Insufficient line voltage

Determine cause and correct.

 

Incorrect or faulty wiring

Check wiring diagram and rewire correctly.

 

Thermostat setting too high

Lower thermostat setting below room temperature.

Compressor will not

Faulty wiring or loose connections in

Check wiring and repair or replace.

start but condenser

compressor circuit

 

fan runs.

 

 

Compressor motor burned out, seized, or

Determine cause. Replace compressor.

 

internal overload open

 

 

Defective run/start capacitor, overload,

Determine cause and replace.

 

start relay

 

 

One leg of 3-phase power dead

Replace fuse or reset circuit breaker.

 

 

Determine cause.

Three-phase scroll

Scroll compressor is rotating in the

Correct the direction of rotation by reversing the

compressor (Units

wrong direction

3-phase power leads to the unit. Shut down unit to

588A048,060 and

 

allow pressures to equalize.

589A036-060 only)

 

 

makes excessive

 

 

noise, and there

 

 

may be a low pres-

 

 

sure differential.

 

 

Compressor cycles

Refrigerant overcharge or undercharge

Recover refrigerant, evacuate system, and

(other than normally

 

recharge to capacities shown on nameplate.

satisfying

 

 

Defective compressor

Replace and determine cause.

thermostat).

Insufficient line voltage

Determine cause and correct.

 

 

Blocked condenser

Determine cause and correct.

 

Defective run/start capacitor, overload

Determine cause and replace.

 

or start relay

 

 

Defective thermostat

Replace thermostat.

 

Faulty condenser-fan motor or capacitor

Replace.

 

Restriction in refrigerant system

Locate restriction and remove.

Compressor

Dirty air ®lter

Replace ®lter.

operates

 

 

Unit undersized for load

Decrease load or increase unit size.

continuously.

Thermostat set too low

Reset thermostat.

 

 

Low refrigerant charge

Locate leak, repair, and recharge.

 

Leaking valves in compressor

Replace compressor.

 

Air in system

Recover refrigerant, evacuate system, and recharge.

 

Condenser coil dirty or restricted

Clean coil or remove restriction.

Excessive head

Dirty air ®lter

Replace ®lter.

pressure.

 

 

Dirty condenser coil

Clean coil.

 

 

Refrigerant overcharged

Recover excess refrigerant.

 

Air in system

Recover refrigerant, evacuate system, and recharge.

 

Condenser air restricted or air short-cycling

Determine cause and correct.

Head pressure too

Low refrigerant charge

Check for leaks, repair and recharge.

low.

 

 

Compressor valves leaking

Replace compressor.

 

 

Restriction in liquid tube

Remove restriction.

Excessive suction

High heat load

Check for source and eliminate.

pressure.

 

 

Compressor valves leaking

Replace compressor.

 

 

Refrigerant overcharged

Recover excess refrigerant.

Suction pressure

Dirty air ®lter

Replace ®lter.

too low.

 

 

Low refrigerant charge

Check for leaks, repair and recharge.

 

 

Metering device or low side restricted

Remove source of restriction.

 

Insufficient evaporator air¯ow

Increase air quantity. Check ®lter Ð replace if

 

 

necessary.

 

Temperature too low in conditioned area

Reset thermostat.

 

Outdoor ambient below 40 F

Install low-ambient kit.

 

Field-installed ®lter-drier restricted

Replace.

Ð48Ð

Image 48
Contents Contents Safety ConsiderationsGeneral 588A018-042 Without Base Rail, Unit Dimensions Ð2Ð588A018-042 With Optional Base Rail, Unit Dimensions Ð3Ð588A048,060 Without Base Rail, Unit Dimensions Ð4Ð588A048,060 With Optional Base Rail, Unit Dimensions Ð5Ð589A024-036 Without Base Rail, Unit Dimensions Ð6Ð589A024-036 With Optional Base Rail, Unit Dimensions Ð7Ð589A042-060 Without Base Rail, Unit Dimensions Ð8Ð589A042-060 With Optional Base Rail, Unit Dimensions Ð9ÐReceiving and Installation Check Equipment II. Ð Provide Unit SupportIII. Ð Field Fabricate Ductwork IV. Ð Provide ClearancesÐ11Ð Part NumberCurb Weight Unit MAXUnit VII. Ð Install Flue Hood VIII. Ð Install GAS PipingUnits With Optional Base Rail VI. Ð Connect Condensate DrainPhysical Data Ð Unit 588A Ð14ÐPhysical Data Ð Unit 589A Ð15ÐIX. Ð Install Duct Connections Conguring Units for Down¯ow Vertical DischargeMaximum Gas Flow Capacity Ð17ÐInternal Length of PIPE, FT² Iron Pipe Diameter Size Install Electrical Connections High-Voltage ConnectionsÐ Electrical Data Ð Unit 588A Ð19ÐÐ Electrical Data Ð Unit 589A Ð20ÐRLA LRA FLA Special Procedures for 208-V Operation High- and Control-Voltage ConnectionsTransformer Protection PRE-START-UPII. Start UP Heating Section and Make Adjustments Adjust Gas InputSTART-UP Check for Refrigerant Leaks Check Heating ControlRated Gas Inputs at Indicated Manifold Pressures GAS Supply Pressure Manifold Natural GAS Propane NumberPressure OrificesHeating Temperature Rise F Input Check Burner FlameÐ25Ð III. Start UP Cooling Section and Make Adjustments 208/230-1-60 Wiring Diagram, Units 588A018-060 Ð27Ð208/230-3-60 Wiring Diagram, Units 588A030-060 Ð28Ð460-3-60 Wiring Diagram, Units 588A036-060 Ð29Ð208/230-1-60 Wiring Diagram, Units 589A024-042 Ð30Ð208/230-1-60 Wiring Diagram, Units 589A048,060 Ð31Ð208/230-3-60 Wiring Diagram, Units 589A036-042 Ð32Ð208/230-3-60 Wiring Diagram, Units 589A048,060 Ð33Ð460-3-60 Wiring Diagram, Units 589A036-048 Ð34ÐChecking and Adjusting Refrigerant Charge Indoor Air¯ow and Air¯ow AdjustmentsSpeed Ð Superheat Charging Table, 588A018 Ð Superheat Charging Table, 588A024Ð36Ð Ð Superheat Charging Table, 588A030 Ð Superheat Charging Table, 588A036Ð Superheat Charging Table, 588A042 Ð37ÐÐ Superheat Charging Table, 588A060 Ð38ÐÐ Superheat Charging Table, 589A024 Ð Superheat Charging Table, 589A030Ð Superheat Charging Table, 589A036 Ð39ÐÐ Superheat Charging Table, 589A042 Ð Superheat Charging Table, 589A048Ð Superheat Charging Table, 589A060 Ð40ÐRequired Suction-Tube Temperature F Ð41ÐÐ42Ð Ð43Ð Unit 589AMaintenance Wet Coil Pressure DropCooling Sequence of Operation Unit Size Airflow Pressure DropAIR Filter II. Unit TOP RemovalIII. Evaporator Blower and Motor IV. Flue GAS PassagewaysVI. Limit Switch COMBUSTION-AIR BlowerVII. Burner Ignition VIII. Main BurnersXI. Electrical Controls and Wiring Condenser FANXII. Refrigerant Circuit XIII. GAS InputTroubleshooting Symptom Cause RemedyIFM runs when it Poor ¯ame characteristicsIntegrated control MotorService Training LED OFFPage START-UP Checklist TemperaturesPreliminary Information III. START-UP Electrical
Related manuals
Manual 27 pages 52.72 Kb

589A, 588A specifications

The Bryant 588A is a high-efficiency gas furnace celebrated for its advanced technology and superior performance in residential heating. Known for its reliability and durable construction, this model is ideal for homeowners looking for warmth and comfort during colder months.

One of the standout features of the Bryant 588A is its remarkable AFUE (Annual Fuel Utilization Efficiency) rating, which can reach up to 96.5%. This high efficiency means that a significant portion of the fuel consumed is converted into usable heat, leading to lower energy bills and a reduced carbon footprint. The furnace utilizes a two-stage heating system, which improves comfort levels by providing more consistent temperatures and reducing the frequency of temperature swings in the home.

Another notable characteristic is the incorporation of a multi-speed blower motor. This innovation enhances airflow and optimizes energy use by adjusting the fan speed according to the heating needs of the home. The variable speed operation also helps to minimize noise levels, creating a quieter environment compared to traditional single-speed furnaces.

The Bryant 588A features an advanced control system that allows for better system management and can be integrated with smart home technologies. This allows homeowners to monitor and adjust their heating settings remotely, offering convenience and efficiency. Additionally, the furnace is compatible with Bryant’s Evolution System, which provides advanced diagnostic features and improved energy performance.

Durability is a key characteristic of the Bryant 588A, as it is constructed with a heavy-duty cabinet designed to withstand the rigors of daily use and harsh weather conditions. The unit also includes a corrosion-resistant heat exchanger, ensuring longevity and reliability.

Furthermore, the Bryant 588A operates quietly, thanks to its insulated cabinet and advanced design. This feature is especially appreciated by homeowners seeking a peaceful living environment free from disruptive noises typically associated with heating systems.

In summary, the Bryant 588A gas furnace combines high efficiency, innovative technology, and durable construction. Its effective heating capabilities paired with user-friendly features make it a smart investment for anyone looking to enhance their home heating system while enjoying lower energy costs and increased comfort.