Bryant 589A, 588A START-UP Check for Refrigerant Leaks, Check Heating Control, Check Gas Input

Page 23

a.Before lighting the unit for the ®rst time, perform the following: If the gas supply pipe was not purged before connecting the unit, it will be full of air. It is recommended that the ground joint union be loos- ened, and the supply line be allowed to purge until the odor of gas is detected. Never purge gas lines into a combustion chamber. Immediately upon detection of gas odor, retighten the union. Allow 5 minutes to elapse, then light unit.

b.Make sure that condenser-fan blade is correctly po- sitioned in fan ori®ce. Leading edge of condenser-fan blade should be 1¤2 in. maximum from plastic fan ori- ®ce (see Fig. 23).

c.Make sure that air ®lter(s) is in place.

d.Make sure that condensate drain trap is ®lled with water to ensure proper drainage.

e.Make sure that all tools and miscellaneous loose parts have been removed.

Fig. 23 Ð Fan Blade Clearance

START-UP

I. CHECK FOR REFRIGERANT LEAKS

Proceed as follows to locate and repair a refrigerant leak and to charge the unit:

1.Locate leak and make sure that refrigerant system pres- sure has been relieved and reclaimed from both high- and low-pressure ports.

2.Repair leak following accepted practices.

NOTE: Install a ®lter drier whenever the system has been opened for repair.

3.Add a small charge of R-22 refrigerant vapor to system and leak-test unit.

4.Evacuate and reclaim refrigerant from refrigerant sys- tem if additional leaks are not found.

5.Charge unit with R-22 refrigerant, using a volumetric- charging cylinder or accurate scale. Refer to unit rating plate for required charge. Be sure to add extra refriger- ant to compensate for internal volume of ®lter drier.

II.START UP HEATING SECTION AND MAKE ADJUSTMENTS

CAUTION: Complete the required procedures given in Pre-Start-Up section on page 22 before starting the unit.

Do not jumper any safety devices when operating the unit.

Make sure that burner ori®ces are properly aligned. Un- stable operation may occur when the burner ori®ces in the manifold are misaligned.

Follow the lighting instructions on the heating section operation label (located inside the burner or blower access door) to start the heating section.

NOTE: Make sure that gas supply has been purged, and that all gas piping has been checked for leaks.

A. Check Heating Control

Start and check the unit for proper heating control operation as follows. (See furnace lighting instructions located inside burner or blower access panel.)

1.Place the room thermostat SYSTEM switch in the HEAT position and the fan switch in the AUTO. position.

2.Set the heating temperature control of the thermostat above room temperature.

3.The induced-draft motor will start.

4.After a call for heating, the main burner should light within 5 seconds. If the burners do not light, there is a 22-second delay before another 5-second try. If the burn- ers still do not light, this sequence is repeated. If the burners do not light within 15 minutes from the initial call for heat, there is a lockout. To reset the control, break the 24-v power to W.

5.The evaporator fan will turn on 45 seconds after the flame has been established. The evaporator fan will turn off 45 seconds after the thermostat has been satis®ed.

B.Check Gas Input

Check gas input and manifold pressure after unit start-up. (See Table 5.) If adjustment is required proceed as follows.

The rated gas inputs shown in Table 5 are for altitudes from sea level to 2000 ft above sea level. These inputs are based on natural gas with a heating value of 1050 Btu/ft3 at 0.65 speci®c gravity, or propane gas with a heating value of 2500 Btu/ft3 at 1.5 speci®c gravity. For elevations above 2000 ft, reduce input 4% for each 1000 ft above sea level. When the gas supply being used has a different heating value or spe- ci®c gravity, refer to national and local codes, or contact your distributor to determine the required ori®ce size.

CAUTION: These units are designed to consume the rated gas inputs using the ®xed ori®ces at speci®ed mani- fold pressures as shown in Table 5. DO NOT REDRILL THE ORIFICES UNDER ANY CIRCUMSTANCES.

C. Adjust Gas Input

The gas input to the unit is determined by measuring the gas ¯ow at the meter or by measuring the manifold pressure. Measuring the gas ¯ow at the meter is recommended for natu- ral gas units. The manifold pressure must be measured to determine the input of propane gas units.

Ð23Ð

Image 23
Contents General ContentsSafety Considerations Ð2Ð 588A018-042 Without Base Rail, Unit DimensionsÐ3Ð 588A018-042 With Optional Base Rail, Unit DimensionsÐ4Ð 588A048,060 Without Base Rail, Unit DimensionsÐ5Ð 588A048,060 With Optional Base Rail, Unit DimensionsÐ6Ð 589A024-036 Without Base Rail, Unit DimensionsÐ7Ð 589A024-036 With Optional Base Rail, Unit DimensionsÐ8Ð 589A042-060 Without Base Rail, Unit DimensionsÐ9Ð 589A042-060 With Optional Base Rail, Unit DimensionsIV. Ð Provide Clearances Receiving and Installation Check EquipmentII. Ð Provide Unit Support III. Ð Field Fabricate DuctworkCurb Ð11ÐPart Number Unit WeightUnit MAX VI. Ð Connect Condensate Drain VII. Ð Install Flue HoodVIII. Ð Install GAS Piping Units With Optional Base RailÐ14Ð Physical Data Ð Unit 588AÐ15Ð Physical Data Ð Unit 589AConguring Units for Down¯ow Vertical Discharge IX. Ð Install Duct ConnectionsInternal Length of PIPE, FT² Iron Pipe Diameter Size Maximum Gas Flow CapacityÐ17Ð High-Voltage Connections Install Electrical ConnectionsÐ19Ð Ð Electrical Data Ð Unit 588ARLA LRA FLA Ð Electrical Data Ð Unit 589AÐ20Ð High- and Control-Voltage Connections Special Procedures for 208-V OperationPRE-START-UP Transformer ProtectionCheck Heating Control II. Start UP Heating Section and Make AdjustmentsAdjust Gas Input START-UP Check for Refrigerant LeaksOrifices Rated Gas Inputs at Indicated Manifold PressuresGAS Supply Pressure Manifold Natural GAS Propane Number PressureÐ25Ð Heating Temperature Rise F InputCheck Burner Flame III. Start UP Cooling Section and Make Adjustments Ð27Ð 208/230-1-60 Wiring Diagram, Units 588A018-060Ð28Ð 208/230-3-60 Wiring Diagram, Units 588A030-060Ð29Ð 460-3-60 Wiring Diagram, Units 588A036-060Ð30Ð 208/230-1-60 Wiring Diagram, Units 589A024-042Ð31Ð 208/230-1-60 Wiring Diagram, Units 589A048,060Ð32Ð 208/230-3-60 Wiring Diagram, Units 589A036-042Ð33Ð 208/230-3-60 Wiring Diagram, Units 589A048,060Ð34Ð 460-3-60 Wiring Diagram, Units 589A036-048Speed Checking and Adjusting Refrigerant ChargeIndoor Air¯ow and Air¯ow Adjustments Ð36Ð Ð Superheat Charging Table, 588A018Ð Superheat Charging Table, 588A024 Ð37Ð Ð Superheat Charging Table, 588A030Ð Superheat Charging Table, 588A036 Ð Superheat Charging Table, 588A042Ð38Ð Ð Superheat Charging Table, 588A060Ð39Ð Ð Superheat Charging Table, 589A024Ð Superheat Charging Table, 589A030 Ð Superheat Charging Table, 589A036Ð40Ð Ð Superheat Charging Table, 589A042Ð Superheat Charging Table, 589A048 Ð Superheat Charging Table, 589A060Ð41Ð Required Suction-Tube Temperature FÐ42Ð Unit 589A Ð43ÐUnit Size Airflow Pressure Drop MaintenanceWet Coil Pressure Drop Cooling Sequence of OperationIV. Flue GAS Passageways AIR FilterII. Unit TOP Removal III. Evaporator Blower and MotorVIII. Main Burners VI. Limit SwitchCOMBUSTION-AIR Blower VII. Burner IgnitionXIII. GAS Input XI. Electrical Controls and WiringCondenser FAN XII. Refrigerant CircuitSymptom Cause Remedy TroubleshootingMotor IFM runs when itPoor ¯ame characteristics Integrated controlLED OFF Service TrainingPage III. START-UP Electrical START-UP ChecklistTemperatures Preliminary Information
Related manuals
Manual 27 pages 52.72 Kb

589A, 588A specifications

The Bryant 588A is a high-efficiency gas furnace celebrated for its advanced technology and superior performance in residential heating. Known for its reliability and durable construction, this model is ideal for homeowners looking for warmth and comfort during colder months.

One of the standout features of the Bryant 588A is its remarkable AFUE (Annual Fuel Utilization Efficiency) rating, which can reach up to 96.5%. This high efficiency means that a significant portion of the fuel consumed is converted into usable heat, leading to lower energy bills and a reduced carbon footprint. The furnace utilizes a two-stage heating system, which improves comfort levels by providing more consistent temperatures and reducing the frequency of temperature swings in the home.

Another notable characteristic is the incorporation of a multi-speed blower motor. This innovation enhances airflow and optimizes energy use by adjusting the fan speed according to the heating needs of the home. The variable speed operation also helps to minimize noise levels, creating a quieter environment compared to traditional single-speed furnaces.

The Bryant 588A features an advanced control system that allows for better system management and can be integrated with smart home technologies. This allows homeowners to monitor and adjust their heating settings remotely, offering convenience and efficiency. Additionally, the furnace is compatible with Bryant’s Evolution System, which provides advanced diagnostic features and improved energy performance.

Durability is a key characteristic of the Bryant 588A, as it is constructed with a heavy-duty cabinet designed to withstand the rigors of daily use and harsh weather conditions. The unit also includes a corrosion-resistant heat exchanger, ensuring longevity and reliability.

Furthermore, the Bryant 588A operates quietly, thanks to its insulated cabinet and advanced design. This feature is especially appreciated by homeowners seeking a peaceful living environment free from disruptive noises typically associated with heating systems.

In summary, the Bryant 588A gas furnace combines high efficiency, innovative technology, and durable construction. Its effective heating capabilities paired with user-friendly features make it a smart investment for anyone looking to enhance their home heating system while enjoying lower energy costs and increased comfort.