(5.) Reverse Phase 3 fault code indication

(6.) Welded Contactor fault code indication

(7.) Low Voltage fault code indication

(8.) Anti-short cycle protection

(9.) Phase reversal protection

2.Minimum safety devices which are equipped with automatic reset (after resetting first at thermostat), shall in- clude:

a.High discharge pressure cutout.

b.Low pressure cutout. H. Operating Characteristics:

1.The capacity of the condensing unit shall meet or exceed _____ Btuh at a suction temperature of ______F. The power consumption at full load shall not exceed _____ kW.

2.The combination of the condensing unit and the evaporator or fan coil unit shall have a total net cooling capacity of _____ Btuh or greater at conditions of _____ cfm entering-air temperature at the evaporator at ______F wet bulb and ______F dry bulb, and air entering the condensing unit at ______F.

3.The system shall have an EER of _____ Btuh/Watt or greater at standard AHRI conditions.

4.Standard unit shall be capable to operate up to 125_F (52_C) and down to 40_F (4_C)

I.Electrical Requirements:

1.Nominal unit electrical characteristics shall be _____ v, 3-ph, 60 Hz. The unit shall be capable of satisfactory operation within voltage limits of ____ v to _____ v.

2.Unit electrical power shall be single-point connection.

3.Unit control circuit shall contain a 24-v transformer for unit control.

J.Special Features:

1.Low-Ambient Temperature Control:

A low-ambient temperature control shall be available as a factory-installed option or as a field-installed accessory. This low-ambient control shall regulate speed of the condenser-fan motors in response to the saturated condensing temperature of the unit. The control shall maintain correct condensing pressure at outdoor temperatures down to –20_F (-29_C).

2.Unit-Mounted, Non-Fused Disconnect Switch:

Switch shall be factory-installed and internally mounted. NEC and UL-approved non-fused switch shall provide unit power shutoff. Switch shall be accessible from outside the unit and shall provide power off lockout capability. Non-fused disconnect switch cannot be used when unit MOCP electrical rating exceeds 80 amps.

3.Convenience Outlet:

Outlet shall be factory-installed and internally mounted with easily accessible 115-v female receptacle. Outlet shall include 15 amp GFI (ground fault interrupter) receptacle with independent fuse protection. Voltage required to operate convenience outlet shall be provided by a factory-installed step-down transformer. Outlet shall be ac- cessible from outside the unit.

4.Thermostat Controls:

a.Programmable multi-stage thermostat shall have 7-day clock, holiday scheduling, large backlit display, remote sensor capability, and Title 24 compliance.

b.Commercial Electronic Thermostat shall have 7-day time clock, auto-changeover, multi-stage capability, and large LCD (liquid crystal display) temperature display.

5.Louvered hail Guard Package:

Louvered hail guard package shall protect coils against damage from hail and other flying debris.

6.Condenser Coil Grille (Novation coil models 07-14):

Grille shall add decorative appearance to unit and protect condenser coil from large objects and vandalism.

569J

59

Image 59
Contents Product Data Features / BenefitsControls for performance dependability Factory-installed options FIOPsIndoor-air quality IAQ features Efficient operationTable of Contents Model Number Nomenclature Cooling NOM NET Cooling Sound Power LEVELS, dBUnit Compressors Capacity Power EER Ieer Circuits Tons MBH AHRI* Capacity Ratings569J*12A 569J*14A 569J*16A Physical Data569J*07A 569J*08A 569J*12A 569J*14A 569J*16A 569J*07A569J*25D Dimensions Dimensions C101214 Condenser Coil Options Options and Accessories569J* factory-installed options 569J* Options and Accessories524J Options and Accessories 569J* field-installed accessories524J factory-installed options 524J field-installed accessoriesOptions and Accessories 524J with Economizer UV-C Germicidal Lamps Operating sequences Selection ProcedureControls Typical Wiring Schematic Typical Wiring Schematic 569J*08A AIR Temperature Entering Condenser FPerformance Data 569J*07A100 105 115 120 569J*12A569J*12D Dual Circuit AIR Temp ENT Condenser F569J*14D Dual Circuit 569J*14A105 115 125 569J*16A569J*16D Dual Circuit 569J*25D Dual Circuit 569J*25ACombination Ratings 569J*07A 524J*072600 Cfm 569J*07A 524J*082250 Cfm 3750 Cfm 569J*08A 524J*082625 Cfm 3375 Cfm4000 Cfm 569J*08A 524J*12Cfm 35005000 Cfm 569J*12A 524J*123500 Cfm 5700 Cfm 569J*12 A- 524J*144300 Cfm 569J*12D 524J*12 569J*12D 524J*14 6250 Cfm 569J*14A 524J*144375 Cfm 5625 Cfm6800 Cfm 569J*14A 524J*165300 Cfm EA wb 6000 Cfm569J*14D 524J*14 5300 Cfm 569J*14D 524J*16569J*16A 524J*16 9000 Cfm 569J*16A 524J*257000 Cfm 8000 Cfm569J*16D- 524J*16 8000 Cfm EA wb 569J*16D 524J*259000 Cfm EA wb 569J*25A 524J*257000 Cfm EA wb 8750 Cfm 569J*25A- 524J*287500 Cfm 569J*25D- 524J*25 8750 Cfm EA wb 569J*25D- 524J*28569J*08A Cooling Without Powered Convenience Outlet 569J*07A Cooling Without Powered Convenience Outlet569J*07A Cooling with Powered Convenience Outlet 569J*08A Cooling with Powered Convenience Outlet569J*12D Cooling with Powered Convenience Outlet 569J*12A Cooling Without Powered Convenience Outlet569J*12A Cooling with Powered Convenience Outlet 569J*12D Cooling Without Powered Convenience Outlet569J*14D Cooling with Powered Convenience Outlet 569J*14A Cooling Without Powered Convenience Outlet569J*14A Cooling with Powered Convenience Outlet 569J*14D Cooling Without Powered Convenience Outlet569J*16D Cooling with Powered Convenience Outlet 569J*16A Cooling Without Powered Convenience Outlet569J*16D Cooling Without Powered Convenience Outlet 569J*16A Cooling with Powered Convenience Outlet569J*25D Cooling with Powered Convenience Outlet 569J*25A Cooling Without Powered Convenience Outlet569J*25D Cooling Without Powered Convenience Outlet 569J*25A Cooling with Powered Convenience OutletRefrigerant piping Minimum OUTDOOR-AIR Operating TemperatureApplication Data Operating limits569J* 07-14 Piping Recommendations SINGLE-CIRCUIT Unit 569J*25 569J 16-25 Piping Recommendations SINGLE-CIRCUIT UnitModel 569J*16Model 569J*12 569J 12-14 Piping Recommendations TWO-CIRCUIT Unit569J 16-25 Piping Recommendations TWO-CIRCUIT Unit Roof Installation and a Ceiling-Mounted Fan Coil Typical Piping and WiringRoof Installation and a Vertical Discharge Fan Coil Ground Level Installation and Vertical Discharge Fan Coil Dual Condensing Units and a Dual Circuit Fan System Description Guide Specifications569J 569J Catalog No. PDS569J---03