PHYSICAL DATA (CONT.)
Dual Circuit Models with NOVATION |
| |||
|
| 569J*12D | 569J*14D | 569J*16D |
Refrigeration System |
| 2 / 2 /Scroll | 2 / 2 /Scroll | 2 / 2 /Scroll |
# Circuits / # Comp. / Type |
| |||
R |
| 3.0 /3.1 | 3.7/3.9 | 6.1/6.1 |
System charge w/ fan coil |
| 7.4 / 7.4 | 10.8 / 10.8 | 12.0/12.0 |
Metering device |
| TXV | TXV | TXV |
| 630 / 505 | 630 / 505 | 630 / 505 | |
| 54 / 117 | 54 / 117 | 54 / 117 | |
|
|
|
|
|
Cond. Coil |
|
|
|
|
Material (Fin/Tube) |
| Al/Al | Al/Al | Al/Al |
Coil type |
| Novation | Novation | Novation |
Rows / FPI |
| 1 / 20.3 | 1 / 20.3 | 1 / 20.3 |
Total face area (ft2) |
| 25.0 | 31.8 | 25.0 x 2 |
|
|
|
|
|
Cond. fan / motor |
|
|
|
|
Qty / Motor drive type |
| 2 / direct | 2 / direct | 3 / direct |
Motor HP / RPM |
| 1/4 / 1100 | 1/4 / 1100 | 1/4 / 1100 |
Fan diameter (in) |
| 22 | 22 | 22 |
Nominal Airflow (cfm) |
| 6,000 | 6,000 | 10,000 |
Watts (total) |
| 610 | 610 | 970 |
|
|
|
|
|
Note: 569J*25D model is not available with NOVATION | coil. |
|
|
|
Dual Circuit Models with RTPF |
| |||
| 569J*12D | 569J*14D | 569J*16D | 569J*25D |
Refrigeration System |
| 2 / 2 /Scroll |
|
|
# Circuits / # Comp. / Type | 2 / 2 / Scroll | 2 / 2 / Scroll | 2 / 2 / Scroll | |
R | 8.0 / 8.0 | 16.0 / 16.0 | 16.0 / 16.0 | 14.0 / 14.0 |
System charge w/ fan coil* | 11.0 / 11.0 | 22.0 / 22.0 | 22.0 / 22.0 | 19.0 / 19.0 |
Metering device | TXV | TXV | TXV | TXV |
630 / 505 | 630 / 505 | 630 / 505 | 630 / 505 | |
54 / 117 | 54 / 117 | 54 / 117 | 54 / 117 | |
|
|
|
|
|
Cond. Coil |
|
|
|
|
Material (Fin/Tube) | Al/Cu | Al/Cu | Al/Cu | Al/Cu |
Coil type | RTPF | RTPF | RTPF | RTPF |
Rows / FPI | 2 / 17 | 3 / 17 | 2 / 17 | 2 / 17 |
total face area (ft2) | 25.1 | 31.8 | 23.5 x 2 | 25.0 x 2 |
Cond. fan / motor |
|
|
|
|
Qty / Motor drive type | 2 / direct | 2 / direct | 3 / direct | 4 / direct |
Motor HP / RPM | 1/4 / 1100 | 1/4 / 1100 | 1/4 / 1100 | 1/4 / 1100 |
Fan diameter (in) | 22 | 22 | 22 | 22 |
Nominal Airflow (cfm) | 6,000 | 6,000 | 9,000 | 12,000 |
Watts (total) | 610 | 610 | 970 | 1150 |
* Approximate system charge with about 25 ft piping of sizes indicated with matched 524J
569J
7