APPLICATION DATA

569J

Operating limits

Maximum outdoor temperature . . . . . . . . . . . . . . . . 125_F Minimum return-air temperature (524J) . . . . . . . . . . 55_F Maximum return-air temperature (524J) . . . . . . . . . . 95_F

Range of acceptable saturation

suction temperature . . . . . . . . . . . . . . . . . . . 20 to 50_F Maximum discharge temperature . . . . . . . . . . . . . . 275_F Minimum discharge superheat . . . . . . . . . . . . . . . . . 60_F

NOTES:

1.Select air handler at no less than 300 cfm/ton (nomin- al condensing unit capacity).

2.Total combined draw of the field-supplied liquid line solenoid valve and air handler fan contactor must not exceed 22 va. If the specified va must be exceeded, use a remote relay to control the load.

MINIMUM OUTDOOR-AIR OPERATING TEMPERATURE

UNIT

 

MINIMUM OUTDOOR TEMP (_F)

569J

Std

 

With MotorMaster IControl†

07A

35

 

 

08A

35

 

 

12A

35

 

 

14A

35

 

 

16A

35

 

–20

25A

35

 

 

 

12D

35

 

 

14D

35

 

 

16D

35

 

 

25D

35

 

 

Wind baffles (field-supplied and field-installed) are re- commended for all units with MotorMaster Ir control. Refer to Low Ambient Temperature Control Installation Instructions for additional information.

Refrigerant piping

IMPORTANT: Do not bury refrigerant piping underground.

It is recommended that the refrigerant piping for all commercial split systems include a liquid line solenoid valve, a liquid line filter drier and a sight glass.

For refrigerant lines longer than 75 lineal ft, a liquid line solenoid valve installed at the indoor unit and a suction accumulator are required. Refer to the Refrigerant Specialties Part Numbers table.

REFRIGERANT SPECIALTIES PART NUMBERS

LIQUID LINE

LIQUID LINE

LLSV

SIGHT

SIZE (in.)

SOLENOID VALVE (LLSV)

COIL

GLASS

 

 

 

 

3/8

EF680033

EF680037

KM680008

1/2

EF680035

EF680037

KM680004

5/8

EF680036

EF680037

KM680005

NOTE: 569J* units require TWO sets of parts.

 

 

Puron-duty Filter Drier(s)

 

 

 

 

Model-Size

Qty

Liquid Line OD

Desiccant Volume

 

 

 

 

569J*07

1

3/8-in

8 cu. in.

569J*08

1

1/2-in

16 cu. in.

569J*12

1

1/2-in

16 cu. in.

569J*14

1

5/8-in

16 cu. in.

569J*16

1

5/8-in

30 cu. in.

569J*25

1

5/8-in

30 cu. in.

569J*12

2

3/8-in

8 cu. in.

569J*14

2

1/2-in

16 cu. in.

569J*16

2

1/2-in

16 cu. in.

569J*25

2

1/2-in

16 cu. in.

Part

Number Ref

KH43LG091

KH43LG085

KH43LG085

KH43LG086

KH43LG087

KH43LG087

KH43LG091

KH43LG085

KH43LG085

KH43LG085

48

Image 48
Contents Features / Benefits Product DataFactory-installed options FIOPs Indoor-air quality IAQ featuresEfficient operation Controls for performance dependabilityTable of Contents Model Number Nomenclature Sound Power LEVELS, dB Unit Compressors Capacity Power EER Ieer Circuits Tons MBHAHRI* Capacity Ratings Cooling NOM NET CoolingPhysical Data 569J*07A 569J*08A 569J*12A 569J*14A 569J*16A569J*07A 569J*12A 569J*14A 569J*16A569J*25D Dimensions Dimensions C101214 Options and Accessories 569J* factory-installed options569J* Options and Accessories Condenser Coil Options569J* field-installed accessories 524J factory-installed options524J field-installed accessories 524J Options and AccessoriesOptions and Accessories 524J with Economizer UV-C Germicidal Lamps Selection Procedure ControlsOperating sequences Typical Wiring Schematic Typical Wiring Schematic AIR Temperature Entering Condenser F Performance Data569J*07A 569J*08A569J*12A 569J*12D Dual CircuitAIR Temp ENT Condenser F 100 105 115 120569J*14A 569J*14D Dual Circuit569J*16A 569J*16D Dual Circuit105 115 125 569J*25A 569J*25D Dual Circuit569J*07A 524J*07 Combination Ratings569J*07A 524J*08 2250 Cfm2600 Cfm 569J*08A 524J*08 2625 Cfm3375 Cfm 3750 Cfm569J*08A 524J*12 Cfm3500 4000 Cfm569J*12A 524J*12 3500 Cfm5000 Cfm 569J*12 A- 524J*14 4300 Cfm5700 Cfm 569J*12D 524J*12 569J*12D 524J*14 569J*14A 524J*14 4375 Cfm5625 Cfm 6250 Cfm569J*14A 524J*16 5300 Cfm EA wb6000 Cfm 6800 Cfm569J*14D 524J*14 569J*14D 524J*16 5300 Cfm569J*16A 524J*16 569J*16A 524J*25 7000 Cfm8000 Cfm 9000 Cfm569J*16D- 524J*16 569J*16D 524J*25 8000 Cfm EA wb569J*25A 524J*25 7000 Cfm EA wb9000 Cfm EA wb 569J*25A- 524J*28 7500 Cfm8750 Cfm 569J*25D- 524J*25 569J*25D- 524J*28 8750 Cfm EA wb569J*07A Cooling Without Powered Convenience Outlet 569J*07A Cooling with Powered Convenience Outlet569J*08A Cooling with Powered Convenience Outlet 569J*08A Cooling Without Powered Convenience Outlet569J*12A Cooling Without Powered Convenience Outlet 569J*12A Cooling with Powered Convenience Outlet569J*12D Cooling Without Powered Convenience Outlet 569J*12D Cooling with Powered Convenience Outlet569J*14A Cooling Without Powered Convenience Outlet 569J*14A Cooling with Powered Convenience Outlet569J*14D Cooling Without Powered Convenience Outlet 569J*14D Cooling with Powered Convenience Outlet569J*16A Cooling Without Powered Convenience Outlet 569J*16D Cooling Without Powered Convenience Outlet569J*16A Cooling with Powered Convenience Outlet 569J*16D Cooling with Powered Convenience Outlet569J*25A Cooling Without Powered Convenience Outlet 569J*25D Cooling Without Powered Convenience Outlet569J*25A Cooling with Powered Convenience Outlet 569J*25D Cooling with Powered Convenience OutletMinimum OUTDOOR-AIR Operating Temperature Application DataOperating limits Refrigerant piping569J* 07-14 Piping Recommendations SINGLE-CIRCUIT Unit 569J 16-25 Piping Recommendations SINGLE-CIRCUIT Unit Model569J*16 569J*25569J 12-14 Piping Recommendations TWO-CIRCUIT Unit Model 569J*12569J 16-25 Piping Recommendations TWO-CIRCUIT Unit Typical Piping and Wiring Roof Installation and a Ceiling-Mounted Fan CoilRoof Installation and a Vertical Discharge Fan Coil Ground Level Installation and Vertical Discharge Fan Coil Dual Condensing Units and a Dual Circuit Fan Guide Specifications System Description569J 569J Catalog No. PDS569J---03