b.Evaporator coils shall be leak tested to 150 psig, pressure tested to 450 psig, and qualified to UL 1995 burst test at 1775 psig.

c.Condenser coils shall be leak tested to 150 psig, pressure tested to 650 psig, and qualified to UL 1995 burst test at 1980 psig.

2.Optional Pre-coated aluminum-fin condenser coils:

a.Shall have a durable epoxy-phenolic coating to provide protection in mildly corrosive coastal environments.

b.Coating shall be applied to the aluminum fin stock prior to the fin stamping process to create an inert barrier between the aluminum fin and copper tube.

c.Epoxy-phenolic barrier shall minimize galvanic action between dissimilar metals.

3.Optional Copper-fin evaporator and condenser coils:

a.Shall be constructed of copper fins mechanically bonded to copper tubes and copper tube sheets.

b.Galvanized steel tube sheets shall not be acceptable.

c.A polymer strip shall prevent coil assembly from contacting the sheet metal coil pan to minimize potential for galvanic corrosion between coil and pan.

4.Optional E-coated aluminum-fin evaporator and condenser coils:

a.Shall have a flexible epoxy polymer coating uniformly applied to all coil surface areas without material bridging between fins.

b.Coating process shall ensure complete coil encapsulation of tubes, fins and headers.

c.Color shall be high gloss black with gloss per ASTM D523-89.

d.Uniform dry film thickness from 0.8 to 1.2 mil on all surface areas including fin edges.

e.Superior hardness characteristics of 2H per ASTM D3363-92A and cross-hatch adhesion of 4B-5B per ASTM D3359-93.

f.Impact resistance shall be up to 160 in.-lb (ASTM D2794-93).

g.Humidity and water immersion resistance shall be up to minimum 1000 and 250 hours respectively (ASTM D2247-92 and ASTM D870-92).

h.Corrosion durability shall be confirmed through testing to be no less than 1000 hours salt spray per ASTM B117-90.

5.Standard All Aluminum Novation Coils:

a.Standard condenser coils shall have all aluminum Novation Heat Exchanger Technology design consisting of aluminum multi port flat tube design and aluminum fin. Coils shall be a furnace brazed design and contain epoxy lined shrink wrap on all aluminum to copper connections.

b.Condenser coils shall be leak tested to 150 psig, pressure tested to 650 psig, and qualified to UL 1995 burst test at 1980 psig.

6.Optional E-coated aluminum-fin, aluminum tube condenser coils:

a.Shall have a flexible epoxy polymer coating uniformly applied to all coil external surface areas without mater- ial bridging between fins or louvers.

b.Coating process shall ensure complete coil encapsulation, including all exposed fin edges.

c.E-coat thickness of 0.8 to 1.2 mil with top coat having a uniform dry film thickness from 1.0 to 2.0 mil on all external coil surface areas, including fin edges, shall be provided.

d.Shall have superior hardness characteristics of 2H per ASTM D3363-00 and cross-hatch adhesion of 4B-5B per ASTM D3359-02.

e.Shall have superior impact resistance with no cracking, chipping or peeling per NSF/ANSI 51-2002 Method 10.2.

F.Refrigeration Components:

Refrigeration circuit components shall include liquid line service valve, suction line service valve, a full charge of compressor oil, and a partial holding charge of refrigerant.

G.Controls and Safeties:

1.Minimum control functions shall include:

f.Control wire terminal blocks.

g.Compressor lockout on auto-reset safety until reset from thermostat.

h.Each unit shall utilize the Comfort Alertt Diagnostic Board that provides: (1.) System Pressure Trip fault code indication

(2.) Short Cycling fault code indication

(3.) Locked Rotor fault code indication

(4.) Open Circuit fault code indication

58

Image 58
Contents Features / Benefits Product DataEfficient operation Factory-installed options FIOPsIndoor-air quality IAQ features Controls for performance dependabilityTable of Contents Model Number Nomenclature AHRI* Capacity Ratings Sound Power LEVELS, dBUnit Compressors Capacity Power EER Ieer Circuits Tons MBH Cooling NOM NET Cooling569J*07A Physical Data569J*07A 569J*08A 569J*12A 569J*14A 569J*16A 569J*12A 569J*14A 569J*16A569J*25D Dimensions Dimensions C101214 569J* Options and Accessories Options and Accessories569J* factory-installed options Condenser Coil Options524J field-installed accessories 569J* field-installed accessories524J factory-installed options 524J Options and AccessoriesOptions and Accessories 524J with Economizer UV-C Germicidal Lamps Controls Selection ProcedureOperating sequences Typical Wiring Schematic Typical Wiring Schematic 569J*07A AIR Temperature Entering Condenser FPerformance Data 569J*08AAIR Temp ENT Condenser F 569J*12A569J*12D Dual Circuit 100 105 115 120569J*14A 569J*14D Dual Circuit569J*16D Dual Circuit 569J*16A105 115 125 569J*25A 569J*25D Dual Circuit569J*07A 524J*07 Combination Ratings2250 Cfm 569J*07A 524J*082600 Cfm 3375 Cfm 569J*08A 524J*082625 Cfm 3750 Cfm3500 569J*08A 524J*12Cfm 4000 Cfm3500 Cfm 569J*12A 524J*125000 Cfm 4300 Cfm 569J*12 A- 524J*145700 Cfm 569J*12D 524J*12 569J*12D 524J*14 5625 Cfm 569J*14A 524J*144375 Cfm 6250 Cfm6000 Cfm 569J*14A 524J*165300 Cfm EA wb 6800 Cfm569J*14D 524J*14 569J*14D 524J*16 5300 Cfm569J*16A 524J*16 8000 Cfm 569J*16A 524J*257000 Cfm 9000 Cfm569J*16D- 524J*16 569J*16D 524J*25 8000 Cfm EA wb7000 Cfm EA wb 569J*25A 524J*259000 Cfm EA wb 7500 Cfm 569J*25A- 524J*288750 Cfm 569J*25D- 524J*25 569J*25D- 524J*28 8750 Cfm EA wb569J*08A Cooling with Powered Convenience Outlet 569J*07A Cooling Without Powered Convenience Outlet569J*07A Cooling with Powered Convenience Outlet 569J*08A Cooling Without Powered Convenience Outlet569J*12D Cooling Without Powered Convenience Outlet 569J*12A Cooling Without Powered Convenience Outlet569J*12A Cooling with Powered Convenience Outlet 569J*12D Cooling with Powered Convenience Outlet569J*14D Cooling Without Powered Convenience Outlet 569J*14A Cooling Without Powered Convenience Outlet569J*14A Cooling with Powered Convenience Outlet 569J*14D Cooling with Powered Convenience Outlet569J*16A Cooling with Powered Convenience Outlet 569J*16A Cooling Without Powered Convenience Outlet569J*16D Cooling Without Powered Convenience Outlet 569J*16D Cooling with Powered Convenience Outlet569J*25A Cooling with Powered Convenience Outlet 569J*25A Cooling Without Powered Convenience Outlet569J*25D Cooling Without Powered Convenience Outlet 569J*25D Cooling with Powered Convenience OutletOperating limits Minimum OUTDOOR-AIR Operating TemperatureApplication Data Refrigerant piping569J* 07-14 Piping Recommendations SINGLE-CIRCUIT Unit 569J*16 569J 16-25 Piping Recommendations SINGLE-CIRCUIT UnitModel 569J*25569J 12-14 Piping Recommendations TWO-CIRCUIT Unit Model 569J*12569J 16-25 Piping Recommendations TWO-CIRCUIT Unit Typical Piping and Wiring Roof Installation and a Ceiling-Mounted Fan CoilRoof Installation and a Vertical Discharge Fan Coil Ground Level Installation and Vertical Discharge Fan Coil Dual Condensing Units and a Dual Circuit Fan Guide Specifications System Description569J 569J Catalog No. PDS569J---03