Bryant 569J manual Guide Specifications, System Description

Page 57

GUIDE SPECIFICATIONS

Commercial Air-Cooled Condensing Units

HVAC Guide Specifications

Size Range: 6 to 20 Tons, Nominal

Bryant Model Numbers: 569J*, Single Circuit (07 - 25 Models) 569J*, Dual Circuit (12 - 25 Models)

Part 1 — General

1.01 SYSTEM DESCRIPTION

Outdoor-mounted, air-cooled condensing unit suitable for on-the-ground or rooftop installation. Unit shall consist of a hermetic scroll air-conditioning compressor(s) assembly, an air-cooled coil, propeller-type condenser fans, and a control box. Unit shall discharge supply air upward as shown on contract drawings. Unit shall be used in a refrigeration circuit matched with a packaged air-handling unit.

1.02QUALITY ASSURANCE

A.Unit shall be rated in accordance with AHRI Standard 360.

B.Unit construction shall comply with ANSI/ASHRAE 15 safety code latest revision and comply with NEC.

C.Unit shall be constructed in accordance with UL 1995 standard and shall carry the UL and UL, Canada label.

D.Unit cabinet shall be capable of withstanding 500-hour salt spray exposure per ASTM B117 (scribed specimen).

E.Air-cooled condenser coils for hermetic scroll compressor units (569J*) and 569J* shall be leak tested at 150 psig, and pressure tested at 650 psig.

F.Unit shall be manufactured in a facility registered to ISO 9001:2000 manufacturing quality standard.

1.03 DELIVERY, STORAGE, AND HANDLING

Unit shall be shipped as single package only, and shall be stored and handled according to unit manufacturer’s recommendations.

1.04WARRANTY (FOR INCLUSION BY SPECIFYING ENGINEER.)

Part 2 — Products

2.01 EQUIPMENT

A. General:

Factory-assembled, single piece, air-cooled condensing unit. Contained within the unit enclosure shall be all factory wiring, piping, controls, compressor, holding charge, and special features required prior to field start-up.

B.Unit Cabinet:

1.Unit cabinet shall be constructed of galvanized steel, bonderized and coated with a prepainted baked enamel fin- ish.

2.A heavy-gauge roll-formed perimeter base rail with forklift slots and lifting holes shall be provided to facilitate rigging.

C.Condenser Fans:

1.Condenser fans shall be direct driven, propeller type, discharging air vertically upward.

2.Fan blades shall be balanced.

3.Condenser fan discharge openings shall be equipped with PVC-coated steel wire safety guards.

4.Condenser fan and motor shaft shall be corrosion resistant. D. Compressor:

1.Compressor shall be of the hermetic scroll type .

2.Compressor shall be mounted on rubber grommets.

3.Compressors shall include overload protection.

4.Compressors shall be equipped with a crankcase heater.

5.Compressor shall be equipped with internal high pressure and high temperature protection.

6.569J*16 and 25 sizes shall use two scroll compressors manifold together. E. Condenser Coils:

1.Standard Aluminum fin - Copper Tube Coils:

a.Standard evaporator and condenser coils shall have aluminum lanced plate fins mechanically bonded to seam- less internally grooved copper tubes with all joints brazed.

569J

57

Image 57
Contents Product Data Features / BenefitsIndoor-air quality IAQ features Factory-installed options FIOPsEfficient operation Controls for performance dependabilityTable of Contents Model Number Nomenclature Unit Compressors Capacity Power EER Ieer Circuits Tons MBH Sound Power LEVELS, dBAHRI* Capacity Ratings Cooling NOM NET Cooling569J*07A 569J*08A 569J*12A 569J*14A 569J*16A Physical Data569J*07A 569J*12A 569J*14A 569J*16A569J*25D Dimensions Dimensions C101214 569J* factory-installed options Options and Accessories569J* Options and Accessories Condenser Coil Options524J factory-installed options 569J* field-installed accessories524J field-installed accessories 524J Options and AccessoriesOptions and Accessories 524J with Economizer UV-C Germicidal Lamps Selection Procedure ControlsOperating sequences Typical Wiring Schematic Typical Wiring Schematic Performance Data AIR Temperature Entering Condenser F569J*07A 569J*08A569J*12D Dual Circuit 569J*12AAIR Temp ENT Condenser F 100 105 115 120569J*14D Dual Circuit 569J*14A569J*16A 569J*16D Dual Circuit105 115 125 569J*25D Dual Circuit 569J*25ACombination Ratings 569J*07A 524J*07569J*07A 524J*08 2250 Cfm2600 Cfm 2625 Cfm 569J*08A 524J*083375 Cfm 3750 CfmCfm 569J*08A 524J*123500 4000 Cfm569J*12A 524J*12 3500 Cfm5000 Cfm 569J*12 A- 524J*14 4300 Cfm5700 Cfm 569J*12D 524J*12 569J*12D 524J*14 4375 Cfm 569J*14A 524J*145625 Cfm 6250 Cfm5300 Cfm EA wb 569J*14A 524J*166000 Cfm 6800 Cfm569J*14D 524J*14 5300 Cfm 569J*14D 524J*16569J*16A 524J*16 7000 Cfm 569J*16A 524J*258000 Cfm 9000 Cfm569J*16D- 524J*16 8000 Cfm EA wb 569J*16D 524J*25569J*25A 524J*25 7000 Cfm EA wb9000 Cfm EA wb 569J*25A- 524J*28 7500 Cfm8750 Cfm 569J*25D- 524J*25 8750 Cfm EA wb 569J*25D- 524J*28569J*07A Cooling with Powered Convenience Outlet 569J*07A Cooling Without Powered Convenience Outlet569J*08A Cooling with Powered Convenience Outlet 569J*08A Cooling Without Powered Convenience Outlet569J*12A Cooling with Powered Convenience Outlet 569J*12A Cooling Without Powered Convenience Outlet569J*12D Cooling Without Powered Convenience Outlet 569J*12D Cooling with Powered Convenience Outlet569J*14A Cooling with Powered Convenience Outlet 569J*14A Cooling Without Powered Convenience Outlet569J*14D Cooling Without Powered Convenience Outlet 569J*14D Cooling with Powered Convenience Outlet569J*16D Cooling Without Powered Convenience Outlet 569J*16A Cooling Without Powered Convenience Outlet569J*16A Cooling with Powered Convenience Outlet 569J*16D Cooling with Powered Convenience Outlet569J*25D Cooling Without Powered Convenience Outlet 569J*25A Cooling Without Powered Convenience Outlet569J*25A Cooling with Powered Convenience Outlet 569J*25D Cooling with Powered Convenience OutletApplication Data Minimum OUTDOOR-AIR Operating TemperatureOperating limits Refrigerant piping569J* 07-14 Piping Recommendations SINGLE-CIRCUIT Unit Model 569J 16-25 Piping Recommendations SINGLE-CIRCUIT Unit569J*16 569J*25Model 569J*12 569J 12-14 Piping Recommendations TWO-CIRCUIT Unit569J 16-25 Piping Recommendations TWO-CIRCUIT Unit Roof Installation and a Ceiling-Mounted Fan Coil Typical Piping and WiringRoof Installation and a Vertical Discharge Fan Coil Ground Level Installation and Vertical Discharge Fan Coil Dual Condensing Units and a Dual Circuit Fan System Description Guide Specifications569J 569J Catalog No. PDS569J---03