569J
569J 16-25 PIPING RECOMMENDATIONS (TWO-CIRCUIT UNIT)
NOTE: 569J requires TWO sets of refrigeration piping
Equivalent Length |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| Ft |
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
| m |
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
| |
| Linear Length |
|
|
|
|
|
|
|
|
| |
| Ft |
|
|
|
|
| |||||
Model | m |
|
|
|
|
| |||||
569J*16 | Liquid Line |
| 1/2 | 1/2 | 1/2 |
| 1/2 |
| 1/2 |
| |
| Max Lift |
| 25 | 50 | 75 |
| 100 |
| 125 |
| |
|
|
|
|
|
|
|
|
|
|
| |
| Suction Line |
| 7/8 | 11/8 | 11/8 |
| 11/8 |
| 11/8 |
| |
| Charge ea. (lbs) |
|
|
|
|
|
|
|
|
| |
| Novation |
| 11.7 | 13.8 | 15.7 |
| 17.6 |
| 19.6 |
| |
| RTPF |
| 21.7 | 23.8 | 25.7 |
| 27.6 |
| 29.6 |
| |
|
|
|
|
|
|
|
|
|
|
| |
569J*25 | Liquid Line |
| 1/2 | 1/2 | 1/2 | 5/8 | 1/2 | 5/8 | 1/2 | 5/8 | |
| Max Lift |
| 25 | 50 | 54 | 75 | 60 | 99 | 46 | 95 | |
|
|
|
|
|
|
|
|
|
|
| |
| Suction Line |
| 11/8 | 11/8 | 11/8 |
| 11/8 | 13/8 | 13/8 |
| |
| Charge (lbs) 1 |
| 19.3 | 21.0 | 23.0 | 26.0 | 25.9 | 29.7 | 28.0 | 32.7 | |
|
| 2 |
| 18.3 | 20.3 | 22.0 | 25.0 | 24.9 | 28.7 | 27.0 | 31.7 |
|
|
|
|
|
|
|
|
|
|
|
|
Legend: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Equivalent | Equivalent tubing length, including effects of refrigeration specialties devices |
|
|
|
| ||||||
Length |
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| ||||||||
Linear Length | Typical linear tubing length (50% added to linear to define Equivalent Length for this table) |
|
| ||||||||
|
|
|
|
|
|
|
|
| |||
Liquid Line | Tubing size, inches OD. |
|
|
|
|
|
|
| |||
|
|
| |||||||||
Max Lift | Maximum liquid lift (indoor unit ABOVE outdoor unit only), at maximum permitted liquid line pressure drop — |
| |||||||||
| S | Linear Length Less than 75 ft (23 m): Minimum 2.0° F subcooling entering TXV |
|
|
| ||||||
| S | Linear Length Greater than 75 ft (23m): Minimum 0.5° F subcooling entering TXV |
|
|
| ||||||
|
|
|
|
|
|
|
|
| |||
Suction Line | Tube size, inches OD |
|
|
|
|
|
|
| |||
|
| ||||||||||
Charge | Charge Quantity, lbs. Calculated for both liquid line sizes (where applicable), but only with larger suction line size | ||||||||||
| (where applicable) |
|
|
|
|
|
|
|
| ||
|
| ||||||||||
NOTE: | For applications with equivalent length greater than 188 ft (57 m) and/0r linear length greater than 125 ft (38 m), | ||||||||||
| contact your local Bryant representative. |
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
52