Bryant 569J manual Selection Procedure, Controls, Operating sequences

Page 15

SELECTION PROCEDURE

Combination ratings for 569J* units matched with 524J Series air handlers are in this book. If unit is used with an air handler, use the Bryant Electronic Catalog AHU (Air-Handling Unit) selection program to obtain combined ratings.

I. Determine cooling load, evaporator-air temperature, and quantity.

Given:

Total Cooling Capacity

Required (TC) . . . . . . . . . . . . . . . . . . . 121,000 Btuh

Sensible Heat Capacity

Required (SHC) . . . . . . . . . . . . . . . . . . . 95,000 Btuh Compressor Type . . . . . . . . . . . . . . . . . . . . . . . . . Scroll

Temperature Air Entering

Condenser (Edb) . . . . . . . . . . . . . . . . . . . . . . . . . 95_F

Temperature Air Entering

Evaporator (db/wb) . . . . . . . . . . . . 80_F db, 67_F wb Evaporator Air Quantity . . . . . . . . . . . . . . . . . 4,000 cfm External Static Pressure . . . . . . . . . . . . . . . . . 0.4 in. wg

Length of Interconnecting

Refrigerant Piping . . . . . . . . . . . . . . . . . 25 ft (Linear) Power Supply (V-Ph-Hz) . . . . . . . . . . . . . 208/230-3-60

II.Select condensing unit air-handler combination.

For this example, select a 569J*12 matched with a 524J012 coil. This 569J*12/524J12 condensing unit air-handler combination provides 122,000 Btuh of total cooling capacity and 97,200 Btuh of sensible capacity at the given conditions. If other temperatures or airflow values are required, interpolate the values from the combination ratings.

III. Determine sizes of liquid and suction lines.

Enter Refrigerant Piping Sizes table. The sizes shown are based on an equivalent length of pipe. This equivalent length is equal to the linear length of pipe indicated at the top of each sizing column, plus a 50% allowance for fitting losses. (For a more accurate determination of actual equivalent length in place of using the estimated 50% value, refer to Bryant System Design Manual.) For this example, note in the linear length column that the proper pipe size is 1/2 in. for the liquid line and 13/8 in. for the suction line.

For extended line lengths over 100 feet, contact your Bryant representative or application engineer.

IV. Determine fan rpm and bhp (brake horsepower).

Refer to the 524J Air Handler Catalog - Fan Performance table. Enter the Air Handler Fan Performance table at 524J12 at 4000 cfm and move to the External Static Pressure (ESP) column. Note that the conditions require 803 rpm at 1.77 bhp.

V.Determine motor and drive.

Enter the Fan Motor Data tables and find the standard motor for 524J12 unit rated at 2.4 Hp. Since the bhp required is 1.77, a standard motor satisfies the requirement and should be used.

Next, find the type of drive that satisfies the 803 rpm requirement in the Drive Data tables. For the 524J012 unit, the Standard Drive table shows an rpm range of 666-863. Since the rpm required is 803, the standard drive satisfies the requirement and should be used.

CONTROLS

Operating sequences

When the wall thermostat calls for cooling, terminals G and Y1 are energized. As a result, the indoor fan contactor (IFC) and the compressor contactor (C1) are energized, causing the indoor fan motor (IFM), compressor #1, and outdoor fans (OFM) to start. The field-supplied and field-installed liquid line valve also opens, allowing the system to function in Cooling mode.

If the unit has 2 stages of cooling, the wall thermostat will additionally energize Y2. The Y2 signal will energize compressor contactor #2 (C2), causing compressor #2 to start.

Regardless of the number of stages, the field-supplied liquid line valve shall opens and the outdoor fan motors(OFM) runs continuously while unit is cooling.

When cooling demand decrease, the thermostat will de-energize Y2. Y2 signal will de-energize compressor contactor #2 (C2), causing compressor #2 to stop.

When cooling demand has been satisfied, the thermostat will de-energize Y1, and G terminals. Y1 and G signal will de-energize compressor contactor #1 (C1), causing compressor #1 to stop. If the wall thermostat is set to continuous (CONT), the indoor fan motor will continue to operate. Otherwise, the indoor fan motor will stop.

The outdoor fan motors (OFM) will turn off and field-supplied liquid line valve shall close , minimizing the potential for refrigerant migration.

569J

15

Image 15
Contents Product Data Features / BenefitsControls for performance dependability Factory-installed options FIOPsIndoor-air quality IAQ features Efficient operationTable of Contents Model Number Nomenclature Cooling NOM NET Cooling Sound Power LEVELS, dBUnit Compressors Capacity Power EER Ieer Circuits Tons MBH AHRI* Capacity Ratings569J*12A 569J*14A 569J*16A Physical Data569J*07A 569J*08A 569J*12A 569J*14A 569J*16A 569J*07A569J*25D Dimensions Dimensions C101214 Condenser Coil Options Options and Accessories569J* factory-installed options 569J* Options and Accessories524J Options and Accessories 569J* field-installed accessories524J factory-installed options 524J field-installed accessoriesOptions and Accessories 524J with Economizer UV-C Germicidal Lamps Selection Procedure ControlsOperating sequences Typical Wiring Schematic Typical Wiring Schematic 569J*08A AIR Temperature Entering Condenser FPerformance Data 569J*07A100 105 115 120 569J*12A569J*12D Dual Circuit AIR Temp ENT Condenser F569J*14D Dual Circuit 569J*14A569J*16A 569J*16D Dual Circuit105 115 125 569J*25D Dual Circuit 569J*25ACombination Ratings 569J*07A 524J*07569J*07A 524J*08 2250 Cfm2600 Cfm 3750 Cfm 569J*08A 524J*082625 Cfm 3375 Cfm4000 Cfm 569J*08A 524J*12Cfm 3500569J*12A 524J*12 3500 Cfm5000 Cfm 569J*12 A- 524J*14 4300 Cfm5700 Cfm 569J*12D 524J*12 569J*12D 524J*14 6250 Cfm 569J*14A 524J*144375 Cfm 5625 Cfm6800 Cfm 569J*14A 524J*165300 Cfm EA wb 6000 Cfm569J*14D 524J*14 5300 Cfm 569J*14D 524J*16569J*16A 524J*16 9000 Cfm 569J*16A 524J*257000 Cfm 8000 Cfm569J*16D- 524J*16 8000 Cfm EA wb 569J*16D 524J*25569J*25A 524J*25 7000 Cfm EA wb9000 Cfm EA wb 569J*25A- 524J*28 7500 Cfm8750 Cfm 569J*25D- 524J*25 8750 Cfm EA wb 569J*25D- 524J*28569J*08A Cooling Without Powered Convenience Outlet 569J*07A Cooling Without Powered Convenience Outlet569J*07A Cooling with Powered Convenience Outlet 569J*08A Cooling with Powered Convenience Outlet569J*12D Cooling with Powered Convenience Outlet 569J*12A Cooling Without Powered Convenience Outlet569J*12A Cooling with Powered Convenience Outlet 569J*12D Cooling Without Powered Convenience Outlet569J*14D Cooling with Powered Convenience Outlet 569J*14A Cooling Without Powered Convenience Outlet569J*14A Cooling with Powered Convenience Outlet 569J*14D Cooling Without Powered Convenience Outlet569J*16D Cooling with Powered Convenience Outlet 569J*16A Cooling Without Powered Convenience Outlet569J*16D Cooling Without Powered Convenience Outlet 569J*16A Cooling with Powered Convenience Outlet569J*25D Cooling with Powered Convenience Outlet 569J*25A Cooling Without Powered Convenience Outlet569J*25D Cooling Without Powered Convenience Outlet 569J*25A Cooling with Powered Convenience OutletRefrigerant piping Minimum OUTDOOR-AIR Operating TemperatureApplication Data Operating limits569J* 07-14 Piping Recommendations SINGLE-CIRCUIT Unit 569J*25 569J 16-25 Piping Recommendations SINGLE-CIRCUIT UnitModel 569J*16Model 569J*12 569J 12-14 Piping Recommendations TWO-CIRCUIT Unit569J 16-25 Piping Recommendations TWO-CIRCUIT Unit Roof Installation and a Ceiling-Mounted Fan Coil Typical Piping and WiringRoof Installation and a Vertical Discharge Fan Coil Ground Level Installation and Vertical Discharge Fan Coil Dual Condensing Units and a Dual Circuit Fan System Description Guide Specifications569J 569J Catalog No. PDS569J---03