Bard QW5S1, QW4S1, QW3S1 Wiring Main Power, Wiring LOW Voltage Wiring, Operating Voltage Range

Page 18

WIRING – MAIN POWER

Refer to the unit rating plate and/or Table 2 for wire sizing information and maximum fuse or “HACR Type” circuit breaker size. Each unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75°C copper) for all models, including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.

The unit rating plate lists a “Maximum Time Delay Relay Fuse” or “HACR Type” circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection, and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.

The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect.

The field wiring connections are located behind the top panel in the circuit breaker panel. The return air panel must be removed first. This panel is equipped with a door switch, which shuts the unit down when it is removed. The filter rack must be removed next.

TABLE 2

OPERATING VOLTAGE RANGE

TAP

RANGE

 

 

240V

253 - 216

 

 

208V

220 - 187

 

 

NOTE: The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).

The standard Climate Control Option X is a remote thermostat connection terminal block. See Figure 14 for wiring diagram. Compatible thermostats are listed in Table 3.

The Climate Control Option D is an electronic, programmable thermostat. The subbase of the thermostat is factory wired to the front panel of the unit. See Figure 15 for wiring diagram. Compatible for use with Energy Recovery Ventilator or Economizer.

The Climate Control Option H is an electronic, programmable thermostat and CO2 controller. The subbase of the thermostat and CO2 controller are factory wired to the front panel of the unit. See Figure 16 for wiringdiagram.

GENERAL

This unit is equipped with a variable speed ECM motor. The motor is designed to maintain rated airflow up to the maximum static allowed. It is important that the blower motor plugs are not plugged in or unplugged while the power is on. Failure to remove power prior to unplugging or plugging in the motor could result in motor failure.

WIRING – LOW VOLTAGE WIRING

230/208V, 1 PHASE AND 3 PHASE EQUIPMENT DUAL PRIMARY VOLTAGE TRANSFORMERS

All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are as noted in Table 2.

CAUTION

Do not plug in or unplug blower motor con- nectors while the power is on. Failure to do so may result in motor failure.

 

TABLE 3

 

WALL THERMOSTATS

 

 

Thermostat

Predominant Features

 

 

 

3 stage Cool; 3 stage Heat

8403-060

Programmable/Non-Programmable Electronic

(1120-445)

HP or Conventional

 

Auto or Manual changeover

 

 

Manual

2100-532B

Page

18 of 46

Image 18
Contents QW2S1 QW3S1 QW4S1 QW5S1 Bryan, OhioContents Figures Getting Other Information and Publications For More INFORMATION, Contact These PublishersElectrical Specifications QW Model NomenclatureUnit Dimensions Handling Unit After Removal from Skid Shipping DamageUnit Removal from Skid Removal of Unit from SkidMinimum Installation Height GeneralProper Handling of Unit After Removal from Skid Installation of Unit Through Wall with Wall Sleeve Installation with Free Blow Plenum Ducted ApplicationCondensate Drain Duct WorkFilters Supply Duct ConnectionsCondensate Drain Optional Rear DrainRear Drain TOP View Commercial Room Ventilator OptionTEC Energy Recovery Ventilator Option Removal of the Q-TEC Energy Recovery VentilatorInstallation Instructions Mounting the UnitRemoving Locking Screws from Wheels Unit Mounting Without Ventilation Wall Sleeve Component Location Operating Voltage Range Wiring Main PowerWiring LOW Voltage Wiring Wall ThermostatsBlower Motor LOW Voltage Wire Harness Plug LOW Voltage ConnectionsLOW Voltage Connections for DDC Control Remote Thermostat Wiring Diagram Option 24VACRemote Thermostat Wiring Diagram Thermostat Option Plug #1 Description of Standard Equipment AdjustmentsStart UP Compressor Control ModulePhase Monitor Optional CFM Service HintsImportant Installer Note Delay on Make TimingPressure Service Ports Piping Access to UnitIndoor Blower Performance Opening Rear of Unit Fluid Access From Floor Fluid Connections on Unit with Ventilation Wall SleeveFluid Connections on Unit Without Ventilation Wall Sleeve Pressure Table Flow Rate for Various FluidsOptional Accessories Circulation System Design Copper Water Coil ApplicationCirculation System Start UP Procedure for Closed Loop System Water Temperature and Pressure ProcedurePerformance Model DORFC-1 Loop Pump Module Performance Model DORFC-2 Loop Pump ModulePiping Diagram Water ConnectionsConstant Flow Valves System Start UP Procedure for Open Loop Applications Well Pump SizingRemedies of Water Problems Water CorrosionLake and Pond Installations Cleaning Water CoilWater Well System Cooling Tower / Boiler Application Water Flow and Pressure DropWater Source Heat Pump Water Source Heat Pump Service Unbrazing System ComponentsTroubleshooting GE ECM Motors Don’tTroubleshooting GE ECM Motors CONT’D Replacing ECM Control ModuleCommon Cause Occasional Cause Denotes Ground Source Heat Pump Performance Report Following Information is Needed To Check Performance of Unit