Bard QW2S1, QW4S1, QW3S1, QW5S1 installation instructions LOW Voltage Connections for DDC Control

Page 19

LOW VOLTAGE CONNECTIONS

The “R” terminal is the 24 VAC hot terminal and is supplied through Pin #10 of Plug P2.

The “C” terminal is the 24 VAC common/grounded terminal and feeds through Pin #11 of Plug P2.

The “G” terminal is the indoor blower input signal and feeds through Pin #6 of Plug P2.

The “Y1” terminal is the compressor starting signal and feeds through Pin #7 of Plug P2.

The “Y2” terminal is the compressor staging solenoid signal and feeds through Pin #4 of Plug P2.

The “O” terminal is the reversing valve signal and feeds through Pin #8 of Plug P2.

The “A” terminal is the ventilation demand signal and outputs a signal for ventilation during occupied programming conditions, and feeds through Pin #5 of Plug P2.

The “W2” terminal is the electric heat signal and feeds through Pin #9 of Plug P2.

The “W1/E” terminal is the emergency heat signal and feeds through Pin #3 of Plug P2.

The “L” terminal is used as an input terminal when a CS2000 infrared occupancy device is used. It feeds through Pin #12 of Plug P2.

The “D” terminal is used only of dehumidification models and feeds through Pin #1 of Plug P2.

LOW VOLTAGE CONNECTIONS FOR

DDC CONTROL

Fan Only

Energize G

Ventilation

Energize G, A (any mode of operation)

Part Load Cooling

Energize G, Y1, O

Full Load Cooling

Energize G, Y1, Y2, O

Part Load HP Heating

Energize G, Y1

Full Load HP Heating

Energize G, Y1, Y2

Electric Heat

Energize G, W2

Dehumidification

Energize G, D, O

FIGURE 13

BLOWER MOTOR LOW VOLTAGE

WIRE HARNESS PLUG

MIS-1285

Manual

2100-532B

Page

19 of 46

Image 19
Contents Bryan, Ohio QW2S1 QW3S1 QW4S1 QW5S1Contents Figures For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsQW Model Nomenclature Electrical SpecificationsUnit Dimensions Removal of Unit from Skid Shipping DamageUnit Removal from Skid Handling Unit After Removal from SkidGeneral Minimum Installation HeightProper Handling of Unit After Removal from Skid Installation of Unit Through Wall with Wall Sleeve Ducted Application Installation with Free Blow PlenumSupply Duct Connections Duct WorkFilters Condensate DrainOptional Rear Drain Condensate DrainCommercial Room Ventilator Option Rear Drain TOP ViewRemoval of the Q-TEC Energy Recovery Ventilator TEC Energy Recovery Ventilator OptionMounting the Unit Installation InstructionsRemoving Locking Screws from Wheels Unit Mounting Without Ventilation Wall Sleeve Component Location Wall Thermostats Wiring Main PowerWiring LOW Voltage Wiring Operating Voltage RangeLOW Voltage Connections Blower Motor LOW Voltage Wire Harness PlugLOW Voltage Connections for DDC Control 24VAC Remote Thermostat Wiring Diagram OptionRemote Thermostat Wiring Diagram Thermostat Option Plug #1 Compressor Control Module AdjustmentsStart UP Description of Standard EquipmentDelay on Make Timing Optional CFM Service HintsImportant Installer Note Phase MonitorPiping Access to Unit Pressure Service PortsIndoor Blower Performance Fluid Connections on Unit with Ventilation Wall Sleeve Opening Rear of Unit Fluid Access From FloorFluid Connections on Unit Without Ventilation Wall Sleeve Flow Rate for Various Fluids Pressure TableOptional Accessories Copper Water Coil Application Circulation System DesignCirculation System Water Temperature and Pressure Procedure Start UP Procedure for Closed Loop SystemPerformance Model DORFC-2 Loop Pump Module Performance Model DORFC-1 Loop Pump ModuleWater Connections Piping DiagramConstant Flow Valves Well Pump Sizing System Start UP Procedure for Open Loop ApplicationsWater Corrosion Remedies of Water ProblemsCleaning Water Coil Lake and Pond InstallationsWater Well System Water Flow and Pressure Drop Cooling Tower / Boiler ApplicationWater Source Heat Pump Water Source Heat Pump Unbrazing System Components ServiceDon’t Troubleshooting GE ECM MotorsReplacing ECM Control Module Troubleshooting GE ECM Motors CONT’DCommon Cause Occasional Cause Denotes Ground Source Heat Pump Performance Report Following Information is Needed To Check Performance of Unit