Bard QW2S1 Installation Instructions, Mounting the Unit, Removing Locking Screws from Wheels

Page 15

INSTALLATION INSTRUCTIONS

MOUNTING THE UNIT

When installing a QW unit near an interior wall on the left side, a minimum of 8 inches is required; 12 inches is preferred.

When installing a QW unit near an interior wall on the right side, a minimum of 12 inches is required as additional space is required to connect the drain.

This clearance is required to allow for the attachment of the unit to the wall mounting brackets and the side trim pieces to the wall.

This unit is to be secured to the wall when there is not a vent sleeve used with the wall mounting brackets provided. (NOTE: Wall mounting brackets are only shipped on units with no vent inside.) The unit itself, the supply duct, and the free blow plenum are suitable for “0” clearance to combustible material.

NOTE: When a wall sleeve is to be used attach the unit to the sleeve with bracket supplied with the wall sleeve.

Following are the steps for mounting the QW units. For reference see Figure 11.

1.Attach wall mounting bracket to the structure wall with field supplied lag bolts. The fluid piping connections are to be within the confines of this bracket. See Figure 1 for cabinet openings and location of fluid coil connection points.

2.Position the unit in front of the wall mounting bracket.

3.Remove the locking screws from the wheels. Refer to Figure 10.

4.Roll the unit up to the wall mounting bracket. The unit must be level from side to side. If any adjustments are necessary, shim up under the rollers with sheets of steel or any substance that is not affected by moisture.

5.Secure the unit to the wall bracket with provided #10 hex head sheet metal screws. There are prepunched holes in the cabinet sides, and the bracket has slotted holes to allow for some misalignment.

6.Position the bottom trim piece to the unit and attach with provided screws (dark colored).

7.Position side trim pieces to the wall and attach with field supplied screws. There are two long and two short pieces supplied. The long pieces are to enclose the gap behind the unit. The short pieces are to fill the gap behind the cabinet extension or the free blow plenum box. They may be cut to suit the ceiling height or overlap the unit side trim. There is sufficient length to trim up to a 10'2" ceiling.

FIGURE 10

REMOVING LOCKING SCREWS FROM

WHEELS

REMOVE SCREWS

FROM WHEELS

BEFORE ROLLING

INTO PLACE

Manual

2100-532B

Page

15 of 46

Image 15
Contents Bryan, Ohio QW2S1 QW3S1 QW4S1 QW5S1Contents Figures For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsQW Model Nomenclature Electrical SpecificationsUnit Dimensions Removal of Unit from Skid Shipping DamageUnit Removal from Skid Handling Unit After Removal from SkidMinimum Installation Height GeneralProper Handling of Unit After Removal from Skid Installation of Unit Through Wall with Wall Sleeve Ducted Application Installation with Free Blow PlenumSupply Duct Connections Duct WorkFilters Condensate DrainOptional Rear Drain Condensate DrainCommercial Room Ventilator Option Rear Drain TOP ViewRemoval of the Q-TEC Energy Recovery Ventilator TEC Energy Recovery Ventilator OptionInstallation Instructions Mounting the UnitRemoving Locking Screws from Wheels Unit Mounting Without Ventilation Wall Sleeve Component Location Wall Thermostats Wiring Main PowerWiring LOW Voltage Wiring Operating Voltage RangeBlower Motor LOW Voltage Wire Harness Plug LOW Voltage ConnectionsLOW Voltage Connections for DDC Control 24VAC Remote Thermostat Wiring Diagram OptionRemote Thermostat Wiring Diagram Thermostat Option Plug #1 Compressor Control Module AdjustmentsStart UP Description of Standard EquipmentDelay on Make Timing Optional CFM Service HintsImportant Installer Note Phase MonitorPressure Service Ports Piping Access to UnitIndoor Blower Performance Fluid Connections on Unit with Ventilation Wall Sleeve Opening Rear of Unit Fluid Access From FloorFluid Connections on Unit Without Ventilation Wall Sleeve Flow Rate for Various Fluids Pressure TableOptional Accessories Circulation System Design Copper Water Coil ApplicationCirculation System Water Temperature and Pressure Procedure Start UP Procedure for Closed Loop SystemPerformance Model DORFC-2 Loop Pump Module Performance Model DORFC-1 Loop Pump ModulePiping Diagram Water ConnectionsConstant Flow Valves Well Pump Sizing System Start UP Procedure for Open Loop ApplicationsWater Corrosion Remedies of Water ProblemsCleaning Water Coil Lake and Pond InstallationsWater Well System Water Flow and Pressure Drop Cooling Tower / Boiler ApplicationWater Source Heat Pump Water Source Heat Pump Unbrazing System Components ServiceDon’t Troubleshooting GE ECM MotorsReplacing ECM Control Module Troubleshooting GE ECM Motors CONT’DCommon Cause Occasional Cause Denotes Ground Source Heat Pump Performance Report Following Information is Needed To Check Performance of Unit