Page 16

Single-Compressor Module

Installation

 

 

2.6.2Oil Cooler Fan Control

The Compressor Module temperature is controlled by managing module oil flow and temperature. The module’s precise temperature control is critical to system performance and equipment life. Maintaining proper temperature control also reduces the possibility of gas condensing into liquids during operation.

Cooling fans require 24VDC, 4.5A (105 Watts) for the Compressor Module. Fan speed is controlled by a 0-10VDC control signal that is applied to the yellow lead on the fan terminal strip. Standard Compressor Modules use a nonlinear PTC thermistor to monitor oil temperature and provide a speed signal.

High temperature Compressor Modules use a linear NTC thermistor to monitor oil temperature. This signal is available to support a customer-provided fan speed control circuit.

All power connections are wired to terminal strips in a junction box on the Compressor Module.

Figure 6 Brushless DC Fan

+24VDC

DC common

RED

Blue

No connection feedback

White

0-10VDC speed signal

Figure 7 Basic Fan Control System

PTC Thermistor

Dropping ResistorIn Thermowell

One Fan 100 K Ohms

Two Fans 60.4 K Ohms

Yellow

Red Wire – 24VDC

Yellow Wire – 0-24VDC

Blue Wire – DC Common

To fan speed control

 

 

The PTC Thermistor is nonlinear and switches to high resistance in the 170-190°F (77-88°C) range.

10

2008SSD-34 (5/11)

Image 16
Contents Copeland Scroll Compressor Module Page Table of Contents Table of Contents Figures Compressor Module Nomenclature Important Safety Information Safety Alert Symbol Safety Symbols Used in This ManualCompressor Module IntroductionCompressor Compressor PackageInstallation Guidelines General Installation GuidelinesInlet and Discharge Pressures Required Component-Inlet Gas ScrubberAmbient Temperature Range Installation Clearance and Dimensions Compressor Module Dimensions, in. mmProcess and Instrumentation Diagrams P&IDs Switches SwitchStatusElectrical Controls General ConsiderationsOil Cooler Fan Control Brushless DC FanSingle-Compressor Module Installation Motor Control Typical Compressor Module power supply requirements Compressor Power data based on 480VAC Variable SpeedElectrical Requirements Code DescriptionWiring Control Circuit Terminations Control Wiring TerminationsInitial Startup Compressor Module Pre-Startup ChecklistVariable Frequency Drive VFD Terminations Post-Startup Checklist During Initial OPERATION, Perform These ChecksMaintenance Routine MaintenanceMaintenance summary Maintenance Tools Maintenance ToolsOil Service SymptomsHigh Oil Carryover Possible CauseSingle-Compressor Module Maintenance Cleaning the Inlet Screen Servicing the Scavenge Line OrificeTroubleshooting Guide TroubleshootingVFD fault codes and descriptions Changing the Second-Stage Separator ElementPlatform Symptoms Diagnosis Platform troubleshooting guidelinesSpecifications Compressor Module Specifications Appendix A - Material Data Safety Sheet SupplierEmergency Number 989 Product Name and Information Components and Hazard StatementSpill or Leak Procedures Fire and Explosion HazardsReactivity Data Health Hazard DataPage EmersonClimate.com