Single-Compressor Module

Installation

2.6Electrical Controls

2.6.1General Considerations

All shutdown devices are dry contact switches rated Class I, Division II that are wired to a terminal box for connection to the packager supplied control circuit. The common wires on all switches are connected together. All switches are closed unless a fault condition is detected.

All safety and protective devices must be installed and used in accordance with applicable codes and regulations.

Switches

All switch connections are wired to terminal strips in a junction box on the Compressor Module.

SwitchStatus

• Low Inlet Gas Pressure Normally Open, closes on pressure rise

High Discharge Gas Pressure Normally Closed, opens on pressure rise

• High Temperature

Normally Closed, opens on temperature rise

Electrical Considerations - Variable Speed Compressor Module

Compressor power for a variable speed Compressor Module is the Variable Frequency Drive (VFD).

Compressor speed control can be either a 4-20 mA or 0-10V signal (transducer supplied by customer) applied to the VFD. Speed can also be manually controlled with a potentiometer or the VFD can be set for a fixed speed.

The Compressor is protected by the VFD.

The customer control circuit must supply an Enable signal to the VFD before the drive will accept a Run Fwd signal.

The VFD will start when the Enable signal is on and a Run Fwd signal is applied.

The VFD will stop if the Run Fwd signal is off or the Enable signal is removed.

NOTE

The drive provides 24V for the Enable and Run Fwd signals.

The installer must connect the Enable and Run Forward terminals to the drive’s 24V terminal.

9

2008SSD-34 (5/11)

Image 15
Contents Copeland Scroll Compressor Module Page Table of Contents Table of Contents Figures Compressor Module Nomenclature Important Safety Information Safety Symbols Used in This Manual Safety Alert SymbolIntroduction Compressor ModuleCompressor Package CompressorRequired Component-Inlet Gas Scrubber Installation GuidelinesGeneral Installation Guidelines Inlet and Discharge PressuresAmbient Temperature Range Compressor Module Dimensions, in. mm Installation Clearance and DimensionsProcess and Instrumentation Diagrams P&IDs General Considerations SwitchesSwitchStatus Electrical ControlsBrushless DC Fan Oil Cooler Fan ControlSingle-Compressor Module Installation Motor Control Code Description Typical Compressor Module power supply requirementsCompressor Power data based on 480VAC Variable Speed Electrical RequirementsControl Circuit Terminations Control Wiring Terminations WiringPre-Startup Checklist Initial Startup Compressor ModuleVariable Frequency Drive VFD Terminations During Initial OPERATION, Perform These Checks Post-Startup ChecklistRoutine Maintenance MaintenanceMaintenance summary Maintenance Tools Maintenance ToolsPossible Cause Oil ServiceSymptoms High Oil CarryoverSingle-Compressor Module Maintenance Servicing the Scavenge Line Orifice Cleaning the Inlet ScreenChanging the Second-Stage Separator Element Troubleshooting GuideTroubleshooting VFD fault codes and descriptionsPlatform troubleshooting guidelines Platform Symptoms DiagnosisSpecifications Compressor Module Specifications Components and Hazard Statement Appendix A - Material Data Safety SheetSupplier Emergency Number 989 Product Name and InformationHealth Hazard Data Spill or Leak ProceduresFire and Explosion Hazards Reactivity DataPage EmersonClimate.com