Carrier 48VT(N) Start-upCooling and Make Adjust- ments, Rollout Switch, LED Indications, 48VT--A

Page 16
Table 5 – LED Indications

48VT-- A

completes the control circuit. The direct-spark ignition system cycles and the unit returns to normal heating operation.

Table 5 – LED Indications

STATUS CODE

LED INDICATION

Normal Operation2

On

No Power Hardware Failure

Off

Limit Switch Fault

2 Flashes

Flame Sense Fault

3 Flashes

Four Consecutive Limit Switch Faults

4 Flashes

Ignition Lockout Fault

5 Flashes

Pressure Switch Fault

6 Flashes

Rollout Switch Fault

7 Flashes

Internal Control Fault

8 Flashes

Temporary 1 hr auto reset1

9 Flashes

NOTES:

1.This code indicates an internal processor fault that will reset itself in one hr. Fault can be caused by stray RF signals in the structure or nearby. This is a UL requirement.

2.LED indicates acceptable operation. Do not change ignition control board.

3.When W is energized the burners will remain on for a minimum of 60 sec.

4.If more than one error mode exists they will be displayed on the LED in sequence.

Rollout Switch

The function of the rollout switch is to close the main gas valve in the event of flame rollout. The switch is located above the main burners. When the temperature at the rollout switch reaches the maximum allowable temperature, the control circuit trips, closing the gas valve and stopping gas flow to the burners. The indoor (evaporator) fan motor (IFM) and induced draft motor continue to run until switch is reset. The IGC LED will display FAULT CODE 7.

Step 4 — Start-up Cooling and Make Adjust- ments

Complete the required procedures given in the Pre-Start-Up section before starting the unit. Do not jumper any safety devices when operating the unit. Do not operate the compressor when the outdoor temperature is below 40°F (4.4°C) (unless accessory low-ambient kit is installed). Do not rapid-cycle the compressor. Allow 5 minutes between on cycles to prevent compressor damage.

Checking Cooling Control Operation

Start and check the unit for proper cooling control operation as follows:

1.Place room thermostat SYSTEM switch in OFF position. Observe that blower motor starts when FAN switch is placed in ON position and shuts down when FAN switch is placed in AUTO position.

2.Place SYSTEM switch in COOL position and FAN switch in AUTO position. Set cooling control below room temperature. Observe that compressor, condenser fan, and evaporator blower motors start. Observe that cooling cycle shuts down when control setting is satisfied. The evaporator fan will continue to run for 90 sec.

IMPORTANT: Three-phase, scroll compressors units are direction oriented. Unit must be checked to ensure proper compressor 3-phase power lead orientation. If not corrected within 5 minutes, the internal protector will shut off the compressor. The 3-phase power leads to the unit must be reversed to correct rotation. When turning backwards, the difference between compressor suction and discharge pressures will be near zero.

Checking and Adjusting Refrigerant Charge

The refrigerant system is fully charged with PuronR (R-410A) refrigerant and is tested and factory sealed. Allow system to operate a minimum of 15 minutes before checking or adjusting charge.

NOTE: Adjustment of the refrigerant charge is not required unless the unit is suspected of not having the proper PuronR (R-410A) charge.

The charging label and the tables shown refer to system temperatures and pressures in cooling mode only. A refrigerant charging label is attached to the inside of the compressor access panel (see Fig. 19). The chart includes the required liquid line temperature at given discharge line pressures and outdoor ambient temperatures.

An accurate thermocouple- or thermistor-type thermometer, and a gauge manifold are required when using the subcooling charging method for evaluating the unit charge. Do not use mercury or small dial-type thermometers because they are not adequate for this type of measurement.

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in unit damage.

When evaluating the refrigerant charge, an indicated adjustment to the specified factory charge must always be very minimal. If a substantial adjustment is indicated, an abnormal condition exists somewhere in the cooling system, such as insufficient airflow across either coil or both coils.

Proceed as follows:

1.Remove caps from low- and high-pressure service fittings.

2.Using hoses with valve core depressors, attach low- and high-pressure gauge hoses to low- and high-pressure service fittings, respectively.

3.Start unit in Cooling Mode and let unit run until system pressures stabilize.

4.Measure and record the following:

a.Outdoor ambient-air temperature (°F (°C) db).

b.Liquid line temperature (°F (°C).

c.Discharge (high-side) pressure (psig).

d.Suction (low-side) pressure (psig) (for reference only).

5.Using “Cooling Charging Charts,” compare outdoor-air temperature(°F (°C) db) with the discharge line pressure (psig) to determine desired system operating liquid line temperature (See Fig. 17).

6.Compare actual liquid line temperature with desired liquid line temperature. Using a tolerance of ± 2°F (±1.1°C), add refrigerant if actual temperature is more than 2°F (1.1°C) higher than proper liquid line temperature, or remove refrigerant if actual temperature is more than 2°F (1.1°C) lower than required liquid line temperature.

NOTE: If the problem causing the inaccurate readings is a refrigerant leak, refer to the Check for Refrigerant Leaks section.

Indoor Airflow and Airflow Adjustments

!CAUTION

UNIT OPERATION HAZARD

Failure to follow this caution may result in unit damage.

For cooling operation, the recommended airflow is 350 to 450 cfm for each 12,000 Btuh of rated cooling capacity. For heating operation, the airflow must produce a temperature rise that falls within the range stamped on the unit rating plate.

NOTE: Be sure that all supply-and return-air grilles are open, free from obstructions, and adjusted properly.

16

Image 16
Contents TABLE OF CONTENTS SAFETY CONSIDERATIONSFig. 1 - Unit 48VT-A Installation InstructionsRECEIVING AND INSTALLATION INTRODUCTIONStep 1 - Check Equipment Step 2 - Provide Unit Support48VT--A Fig. 2 - 48VT-A24-30Unit DimensionsA09146 48VT--A Fig. 3 - 48VT-A36-60Unit DimensionsA09147 Fig. 4 - Roof Curb Dimensions 48VTSMALL CURB ROOF CURB DETAILACCESS PANELS MUST BE IN PLACE WHEN RIGGING Step 5 - Rig and Place UnitInspection Rigging/Lifting of Unit See FigStep 7 - Install Flue Hood Step 8 - Install Gas PipingStep 6 - Connect Condensate Drain Fig. 6 - Condensate TrapStep 9 - Install Duct Connections Configuring Units for Downflow Vertical DischargeFig. 7 - Sediment Trap FIRE OR EXPLOSION HAZARDTable 1 - Physical Data - Unit 48VT-A Fig. 8 - Supply and Return Duct Opening48VT--A Horizontal Duct CoversTable 1 - Physical Data - Unit 48VT-ACont’d Table 2 - Maximum Gas Flow CapacityTable 3 - Heating Inputs 48VT--AStep 10 - Install Electrical Connections Special Procedures for 208-VOperationHigh-VoltageConnections Control Voltage ConnectionsBalance Point Setting-Thermidistator Hybrid PRE-START-UPTransformer Protection ThermostatStep 3 - Start-upHeating and Make Adjust- ments START-UPStep 1 - Check for Refrigerant Leaks Step 2 - Unit Sequence of OperationAdjust Gas Input Fig. 11 - Burner AssemblyCheck Heating Control Check Gas InputLimit Switches Check Burner FlameNormal Operation Airflow and Temperature RiseStep 4 - Start-upCooling and Make Adjust- ments Rollout SwitchChecking and Adjusting Refrigerant Charge Indoor Airflow and Airflow AdjustmentsGas Heating Fan Speed Set-up Continuous Fan OperationTable 6 - Color Coding for Indoor Fan Motor Leads 48VT--AFig. 14 - Interface Fan Board IFB Table 8 - 48VT-AWet Coil Pressure Drop48VT--A Table 7 - Filter Pressure Drop Table IN. W.C48VT--A UNIT48VT--A Heating48VT--A 129548VT--A 144548VT--A 1448Fig. 15 - 208/230-1-60Wiring Diagram, Unit 48VT-A 48VT A48VT--A Fig. 16 - 208/230-3-60Wiring Diagram, Unit 48VT-AA09209 Fig. 17 - Cooling Charging Table-Subcooling 48VT--A50VT500173 REV A09099MAINTENANCE Cleaning the Blower Motor and WheelAir Filter Indoor Blower and MotorLimit Switch Induced Draft combustion air Blower AssemblyFig. 18 - Blower Housing and Flue Collector Box Fig. 19 - Unit Access PanelsElectrical Controls and Wiring Outdoor FanRefrigerant Circuit Fig. 20 - Removal of Motor and Blower WheelPressure Switches Loss of Charge SwitchHigh-PressureSwitch Gas InputPage HPS - High Pressure Switch LCS - Loss of Charge SwitchFig. 24 - Refrigerant Circuit AccuraterMetering De viceTROUBLESHOOTING START-UPCHECKLISTUNIT OPERATION AND SAFETY HAZARD Synthetic Roof Precautionary ProcedurePURONR R-410AQUICK REFERENCE GUIDE 48VT--ASYMPTOM 48VT--ATable 13 - Troubleshooting Guide-LEDStatus Codes Table 12 - Troubleshooting Guide-Heating48VT--A Remove and Store in Job Files I. PRELIMINARY INFORMATION MODEL NOTEMPERATURES PRESSURES48VT--A Catalog No 48VT---05SIEdition Date 04/09 Replaces 48VT---04SI