Installation Procedure

Electric wiring

Wire connection for built-in indoor unit

Insert from outside the connection wire and signal transmission wire through the wall hole with pipeline already arranged.

Pull out the front ends of connection wire and signal wire and make a circle on the signal wire.

Connect the connection wire according to the connection method and indoor and outdoor wiring diagram.

Pull the connecting conductor outwards slightly to confirm it is clamped tightly.

Connect the plug for connecting the signal wire with the plug of the signal wire connected from the indoor unit.

After wire connection is finished, install wire clips using the same method for connection wire clamping.

Note: When connecting the indoor unit and the outdoor unit, please do connect the wires with the same color terminals.

Notes:

Before connecting the conductors between indoor unit and outdoor unit, check for the number on the indoor and outdoor units connecting terminals. Connect the terminals with the same color and number with a wire.

Wrong connection would damage the controller of the air conditioner or the machine couldnt operate.

Do not connect the connection wire and signal wire with the same cable. They shall be connected respectively to ensure system normal operation.

Field setting

Field setting the unit number

In order to realize central control of the MRV air conditioning system, its necessary to set the indoor unit number (control address).

Indoor unit number setting

Indoor unit number setting switch and confirmation of the settings.

There is a 4-position dial switch for setting the indoor unit number on the computer board of the indoor unit.

Setting way is as follows:

Before connecting the power supply, please set the indoor unit number manually according to the following table

Matrix of the dial switch and indoor unit number

Position 1 Position 2 Position 3 Representing unit number

0

0

0

1

1

0

0

2

0

1

0

3

1

1

0

4

0

0

1

5

1

0

1

6

Example:

1 0 0

Pos.1 Pos.2 Pos.3 Pos.4

Setting for No. 2

Disabled

indoor unit

 

: 0

: 1

33

Image 34
Contents Contents CeilingconcealedtypeairconditionerindoorunitPage DB C AE072FCAKA AE242FCAKA Fig1 Calibration of clock Remote controller Operation of remote controller 20 1.ON/OFF button Clock set Important Points of Safety Smell etc. occurs, stop running Important Points of Safety Recommendations Timer Operation Operating InstructionsTimer ON-OFF Sleep Function Health Function Trouble Shooting Following cases are not troublesSystem couldnt start Is power on/off switched on? Poor cooling or heating When Fault OccursPoor cooling Information about application Installation Precautions Installing tools Electrical requirementsInstallation Procedure Figure showing installation dimensions unitmmInstallation of indoor unit Transitive air duct New concrete slab Installation of remote controller Remove upper cover of wire controllerInstallation of receive display Drain pipe RequirementsRefrigerant piping Pipe expansion dimensions as followsPipe cutting and expanding Open all valves Electric wiring Ring terminal connection methodField setting Indoor unit malfunction display code MalfunctionOutdoor unit malfunction display code Indoor unit malfunction Outdoor unit malfunction