GE 1601-0149-A2 manual Memory Map Sheet 2, Addr Name Range Step Units Format Default

Page 16

 

 

 

 

 

 

 

 

 

 

 

 

489

 

 

 

 

Modbus Memory Map

 

Communications Guide

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 1: 489 Memory Map (Sheet 2 of 29)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ADDR

NAME

RANGE

STEP

UNITS

FORMAT

DEFAULT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

023D

Reactive Power Mvar Pretrip

–2000000 to 2000000

1

Mvar

F13

0

 

 

 

 

 

 

 

 

 

 

 

023F

Apparent Power MVA Pretrip

0 to 2000000

1

MVA

F13

0

 

 

 

 

 

 

 

 

 

 

 

0241

Last Trip Data Stator RTD

1 to 12

1

F1

1

 

 

 

 

 

 

 

 

 

 

 

0242

Hottest Stator RTD Temperature

–50 to 250

1

°C

F4

0

 

 

 

 

 

 

 

 

 

 

 

0243

Last Trip Data Bearing RTD

1 to 12

1

F1

1

 

 

 

 

 

 

 

 

 

 

 

0244

Hottest Bearing RTD Temperature

–50 to 250

1

°C

F4

0

 

 

 

 

 

 

 

 

 

 

 

0245

Last Trip Data Other RTD

1 to 12

1

F1

1

 

 

 

 

 

 

 

 

 

 

 

0246

Hottest Other RTD Temperature

–50 to 250

1

°C

F4

0

 

 

 

 

 

 

 

 

 

 

 

0247

Last Trip Data Ambient RTD

1 to 12

1

F1

1

 

 

 

 

 

 

 

 

 

 

 

0248

Hottest Ambient RTD Temperature

–50 to 250

1

°C

F4

0

 

 

 

 

 

 

 

 

 

 

 

0249

Analog Input 1 Pretrip

–50000 to 50000

1

Units

F12

0

 

 

 

 

 

 

 

 

 

 

 

024B

Analog Input 2 Pretrip

–50000 to 50000

1

Units

F12

0

 

 

 

 

 

 

 

 

 

 

 

024D

Analog Input 3 Pretrip

–50000 to 50000

1

Units

F12

0

 

 

 

 

 

 

 

 

 

 

 

024F

Analog Input 4 Pretrip

–50000 to 50000

1

Units

F12

0

 

 

 

 

 

 

 

 

 

 

 

025C

Hottest Stator RTD Temperature

–50 to 250

1

°F

F4

0

 

 

 

 

 

 

 

 

 

 

 

025D

Hottest Bearing RTD Temperature

–50 to 250

1

°F

F4

0

 

 

 

 

 

 

 

 

 

 

 

025E

Hottest Other RTD Temperature

–50 to 250

1

°F

F4

0

 

 

 

 

 

 

 

 

 

 

 

025F

Hottest Ambient RTD Temperature

–50 to 250

1

°F

F4

0

 

 

 

 

 

 

 

 

 

 

 

0260

Neutral Voltage Fundamental Pretrip

0 to 250000

1

Volts

F10

0

 

 

 

 

 

 

 

 

 

 

 

0262

Neutral Voltage 3rd Harmonic Pretrip

0 to 250000

1

Volts

F10

0

 

 

 

 

 

 

 

 

 

 

 

0264

Pre-Trip Vab/Iab

0 to 65535

1

ohms s

F2

0

 

 

 

 

 

 

 

 

 

 

 

0265

Pre-Trip Vab/Iab Angle

0 to 359

1

°

F1

0

 

 

 

 

 

 

 

 

 

 

 

STATUS / TRIP PICKUPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0280

Input A Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0281

Input B Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0282

Input C Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0283

Input D Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0284

Input E Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0285

Input F Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0286

Input G Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0287

Sequential Trip Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0288

Field-Breaker Discrepancy Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0289

Tachometer Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

028A

Offline Overcurrent Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

028B

Inadvertent Energization Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

028C

Phase Overcurrent Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

028D

Negative Sequence Overcurrent Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

028E

Ground Overcurrent Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

028F

Phase Differential Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0290

Undervoltage Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0291

Overvoltage Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0292

Volts/Hertz Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0293

Phase Reversal Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0294

Underfrequency Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0295

Overfrequency Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0296

Neutral Overvoltage (Fundamental) Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0297

Neutral Undervoltage (3rd Harmonic) Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0298

Reactive Power Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0299

Reverse Power Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

029A

Low Forward Power Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

029B

Thermal Model Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

029C

RTD #1 Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

029D

RTD #2 Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

1, 2, 3 See Table footnotes on page 39

12

http://www.GEindustrial.com/multilin

GE Multilin

Image 16
Contents 489 Page Table of Contents Table of Contents Copyright 2004 GE Multilin Electrical Interface Modbus RTU DescriptionGE Multilin Modbus Functions Values Message Format and ExampleModbus Functions Function Code Request status from slave Modbus Functions Function Code 16 Store Multiple Setpoints Error Responses Illegal Data AddressMemory Map Information Event RecorderWaveform Capture Dual Setpoints Passcode Operation 489 Memory Map Sheet 1 489 Memory Map Sheet 2 Addr Name Range Step Units Format DefaultStatus / Trip Pickups Status / Alarm Pickups 489 Memory Map Sheet 3489 Memory Map Sheet 4 Status / Digital InputsStatus / Real Time Clock Metering Data / Current MeteringMetering Data / Power Metering Metering Data / Temperature489 Memory Map Sheet 5 Metering Data / Voltage Metering489 Memory Map Sheet 6 Maintenance / Trip Counters Maintenance / General Counters489 Memory Map Sheet 7 Learned Data / Analog in MIN/MAX489 Memory Map Sheet 8 489 Memory Map Sheet 9 489 Memory Map Sheet 10 Digital Inputs / General Input CDigital Inputs / General Input D Digital Inputs / General Input E489 Memory Map Sheet 11 489 Memory Map Sheet 12 489 Memory Map Sheet 13 Current Elements / Negative Sequence 489 Memory Map Sheet 14Current Elements / Ground O/C 489 Memory Map Sheet 15 Current Elements / Phase Differential Current Elements / HIGH-SET Phase Overcurrent489 Memory Map Sheet 16 Current Elements / Ground Directional489 Memory Map Sheet 17 489 Memory Map Sheet 18 Voltage Elements / Neutral Overvoltage FundamentalVoltage Elements / Loss of Excitation Voltage Elements / Distance Element489 Memory Map Sheet 19 489 Memory Map Sheet 20 489 Memory Map Sheet 21 RTD Temperature / RTD #12 RTD Temperature / Open RTD SensorRTD Temperature / RTD SHORT/LOW Temperature Thermal Model / Model Setup489 Memory Map Sheet 23 489 Memory Map Sheet 24 489 Memory Map Sheet 25 489 Memory Map Sheet 26 Analog INPUT/OUTPUT / Analog InputTesting / PRE-FAULT Setup Testing / Simulation Mode489 Memory Map Sheet 27 489 Memory Map Sheet 28 489 Memory Map Sheet 29 Waveform Memory SetupWaveform Memory Samples Code Type Definition Unsigned ValueDecimal Place Decimal PlacesSwitch Alarm / Trip TypeReset Mode ALARM/TRIP StatusInput Switch Analog OutputParameter Overcurrent CurveData Formats Sheet 7 Simulation Mode Curve Reset TypeSwitch Status Order CodeUndervoltage Trip Element TypeBreaker Operation Assignable InputDNP Protocol DNP 3.0 Device Profile Document DNP Implementation Table Default VariationsVariation Binary Input / Binary 01/02Binary Inputs Sheet 1 Binary Inputs Sheet 2Binary Inputs Sheet 3 Binary Inputs Sheet 410/12 Binary / Control RelayBinary Output Point List DNP Point Lists Binary / Frozen Counter Objects 20/21 Counters Point ListAnalog Inputs Point List Sheet 1 Assigned toAnalog Inputs Point List Sheet 2 Impedance angleAnalog Inputs Point List Sheet 3 Analog Inputs Point List Sheet 4 Table NotesIndex GE Multilin