GE 1601-0149-A2 manual Analog Inputs Point List Sheet 1, Assigned to

Page 57

DNP Point Lists

Analog Input / Input Change (Objects 30/32)

489

Communications Guide

In the following table, the Format column indicates that the associated data point format is determined by the entry in Data Formats on page 40. For example, an “F1” format is described in that table as a (16-bit) unsigned value without any decimal places. Therefore, the value read should be interpreted in this manner. Many of the values reported by the 489 have a size of 32-bits and have had their upper and lower 16-bit components assigned to separate points. Where indicated, refer to the appropriate note following the table for more detail.

Table 8: Analog Inputs Point List (Sheet 1 of 4)

INDEX

FOR-

DESCRIPTION

EVENT CLASS

NOTES

 

MAT

 

ASSIGNED TO

 

 

 

 

 

 

 

 

 

 

 

0

F133

Generator Status

Class 1

Note 3

 

 

 

 

 

1

F1

Generator Thermal Capacity Used

Class 1

 

 

 

 

 

 

2

F1

Estimated Trip Time On Overload

Class 1

 

 

 

(seconds, 65535 means never)

 

 

 

 

 

 

 

3

F134

Cause Of Last Trip

Class 1

Note 3

 

 

 

 

 

4

F19

Time Of Last Trip (Upper 16 Bits)

Class 1

Notes 3,4

 

 

 

 

 

5

F19

Time Of Last Trip (Lower 16 Bits)

Class 1

Notes 3,4

 

 

 

 

 

6

F18

Date Of Last Trip (Upper 16 Bits)

Class 1

Notes 3,4

 

 

 

 

 

7

F18

Date Of Last Trip (Lower 16 Bits)

Class 1

Notes 3,4

 

 

 

 

 

8

F1

Tachometer Pre-Trip

Class 1

Note 3

 

 

 

 

 

9

F1

Scale factor for pre-trip current readings

Class 1

Note 3

 

 

(pre-trip points marked with “Note 6”).

 

 

 

 

Will always be a power of 10 (1, 10, 100,

 

 

 

 

etc.). Changes only when the configuration

 

 

 

 

setpoints are changed.

 

 

 

 

 

 

 

10

F1

Phase A Pre-Trip Current

Class 1

Notes 3, 6

 

 

 

 

 

11

F1

Phase B Pre-Trip Current

Class 1

Notes 3, 6

 

 

 

 

 

12

F1

Phase C Pre-Trip Current

Class 1

Notes 3, 6

 

 

 

 

 

13

F1

Phase A Pre-Trip Differential Current

Class 1

Notes 3, 6

 

 

 

 

 

14

F1

Phase B Pre-Trip Differential Current

Class 1

Notes 3, 6

 

 

 

 

 

15

F1

Phase C Pre-Trip Differential Current

Class 1

Notes 3, 6

 

 

 

 

 

16

F1

Pre-Trip Negative Sequence Current

Class 1

Note 3

 

 

 

 

 

17

F1

Ground Current Scale Factor. Will always

Class 1

Note 3

 

 

be a power of 10 (1, 10, 100, etc.).

 

 

 

 

Changes only when the configuration

 

 

 

 

setpoints are changed.

 

 

 

 

 

 

 

18

F6

Pre-Trip Ground Current (scaled according

Class 1

Note 3

 

 

to previous setpoint)

 

 

 

 

 

 

 

19

F1

Phase A-B Pre-Trip Voltage

Class 1

Note 3

 

 

 

 

 

20

F1

Phase B-C Pre-Trip Voltage

Class 1

Note 3

 

 

 

 

 

21

F1

Phase C-A Pre-Trip Voltage

Class 1

Note 3

 

 

 

 

 

22

F3

Pre-Trip Frequency

Class 1

Note 3

 

 

 

 

 

23

F1

Pre-Trip Real Power (MW)

Class 1

Notes 3,8

 

 

 

 

 

24

F1

Pre-Trip Real Power (kW)

Class 1

Notes 3,8

 

 

 

 

 

25

F1

Pre-Trip Reactive Power (Mar

Class 1

Notes 3,8

 

 

 

 

 

26

F1

Pre-Trip Reactive Power (kvar)

Class 1

Notes 3,8

 

 

 

 

 

27

F1

Pre-Trip Apparent Power (MVA)

Class 1

Notes 3,8

 

 

 

 

 

28

F1

Pre-Trip Apparent Power (kVA)

Class 1

Notes 3,8

 

 

 

 

 

29

F1

Last Trip Stator RTD

Class 1

Note 3

 

 

 

 

 

30

F4

Last Trip Hottest Stator RTD Temperature

Class 1

Note 3

 

 

(°C)

 

 

 

 

 

 

 

31

F1

Last Trip Bearing RTD

Class 1

Note 3

 

 

 

 

 

32

F4

Last Trip Hottest Bearing RTD Temperature

Class 1

Note 3

 

 

(°C)

 

 

 

 

 

 

 

33

F1

Last Trip Other RTD

Class 1

Note 3

 

 

 

 

 

34

F4

Last Trip Hottest Other RTD Temperature

Class 1

Note 3

 

 

(°C)

 

 

 

 

 

 

 

GE Multilin

http://www.GEindustrial.com/multilin

53

Image 57
Contents 489 Page Table of Contents Table of Contents Electrical Interface Modbus RTU Description Copyright 2004 GE MultilinGE Multilin Modbus Functions Message Format and Example ValuesModbus Functions Function Code Request status from slave Modbus Functions Function Code 16 Store Multiple Setpoints Illegal Data Address Error ResponsesEvent Recorder Memory Map InformationWaveform Capture Dual Setpoints Passcode Operation 489 Memory Map Sheet 1 Addr Name Range Step Units Format Default 489 Memory Map Sheet 2Status / Trip Pickups 489 Memory Map Sheet 3 Status / Alarm PickupsStatus / Digital Inputs 489 Memory Map Sheet 4Status / Real Time Clock Metering Data / Current MeteringMetering Data / Temperature Metering Data / Power Metering489 Memory Map Sheet 5 Metering Data / Voltage Metering489 Memory Map Sheet 6 Maintenance / General Counters Maintenance / Trip Counters489 Memory Map Sheet 7 Learned Data / Analog in MIN/MAX489 Memory Map Sheet 8 489 Memory Map Sheet 9 Digital Inputs / General Input C 489 Memory Map Sheet 10Digital Inputs / General Input D Digital Inputs / General Input E489 Memory Map Sheet 11 489 Memory Map Sheet 12 489 Memory Map Sheet 13 489 Memory Map Sheet 14 Current Elements / Negative SequenceCurrent Elements / Ground O/C 489 Memory Map Sheet 15 Current Elements / HIGH-SET Phase Overcurrent Current Elements / Phase Differential489 Memory Map Sheet 16 Current Elements / Ground Directional489 Memory Map Sheet 17 Voltage Elements / Neutral Overvoltage Fundamental 489 Memory Map Sheet 18Voltage Elements / Loss of Excitation Voltage Elements / Distance Element489 Memory Map Sheet 19 489 Memory Map Sheet 20 489 Memory Map Sheet 21 RTD Temperature / Open RTD Sensor RTD Temperature / RTD #12RTD Temperature / RTD SHORT/LOW Temperature Thermal Model / Model Setup489 Memory Map Sheet 23 489 Memory Map Sheet 24 489 Memory Map Sheet 25 Analog INPUT/OUTPUT / Analog Input 489 Memory Map Sheet 26Testing / Simulation Mode Testing / PRE-FAULT Setup489 Memory Map Sheet 27 489 Memory Map Sheet 28 Waveform Memory Setup 489 Memory Map Sheet 29Waveform Memory Samples Unsigned Value Code Type DefinitionDecimal Place Decimal PlacesAlarm / Trip Type SwitchReset Mode ALARM/TRIP StatusAnalog Output Input SwitchParameter Overcurrent CurveData Formats Sheet 7 Curve Reset Type Simulation ModeSwitch Status Order CodeElement Type Undervoltage TripBreaker Operation Assignable InputDNP Protocol DNP 3.0 Device Profile Document Default Variations DNP Implementation TableVariation 01/02 Binary Input / BinaryBinary Inputs Sheet 1 Binary Inputs Sheet 2Binary Inputs Sheet 4 Binary Inputs Sheet 3Binary / Control Relay 10/12Binary Output Point List Counters Point List DNP Point Lists Binary / Frozen Counter Objects 20/21Assigned to Analog Inputs Point List Sheet 1Impedance angle Analog Inputs Point List Sheet 2Analog Inputs Point List Sheet 3 Table Notes Analog Inputs Point List Sheet 4Index GE Multilin