GE 1601-0149-A2 manual Memory Map Sheet 9

Page 23

Modbus Memory Map

Table 1: 489 Memory Map (Sheet 9 of 29)

489

Communications Guide

ADDR

NAME

RANGE

STEP

UNITS

FORMAT

DEFAULT

 

 

 

 

 

 

 

1138

Clear Breaker Information

0 to 1

1

F103

0

 

 

 

 

 

 

 

SYSTEM SETUP / CURRENT SENSING

 

 

 

 

 

 

 

 

 

 

 

 

1180

Phase CT Primary

10 to 50001

1

Amps

F1

50001

 

 

 

 

 

 

 

1181

Ground CT

0 to 3

1

F104

0

 

 

 

 

 

 

 

1182

Ground CT Ratio

10 to 10000

1

: 1 / :5

F1

100

 

 

 

 

 

 

 

SYSTEM SETUP / VOLTAGE SENSING

 

 

 

 

 

 

 

 

 

 

 

 

11A0

VT Connection Type

0 to 2

1

F106

0

 

 

 

 

 

 

 

11A1

Voltage Transformer Ratio

100 to 30000

1

: 1

F3

500

 

 

 

 

 

 

 

11A2

Neutral VT Ratio

100 to 24000

1

: 1

F3

500

 

 

 

 

 

 

 

11A3

Neutral Voltage Transformer

0 to 1

1

F103

0

 

 

 

 

 

 

 

SYSTEM SETUP / GEN. PARAMETERS

 

 

 

 

 

 

 

 

 

 

 

 

11C0

Generator Rated MVA

50 to 2000001

1

MVA

F13

2000001

 

 

 

 

 

 

 

11C2

Generator Rated Power Factor

5 to 100

1

F3

100

 

 

 

 

 

 

 

11C3

Generator Voltage Phase-Phase

100 to 30001

1

V

F1

30001

 

 

 

 

 

 

 

11C4

Generator Nominal Frequency

0 to 3

1

Hz

F107

0

 

 

 

 

 

 

 

11C5

Generator Phase Sequence

0 to 2

1

F124

0

 

 

 

 

 

 

 

SYSTEM SETUP / SERIAL START/STOP

 

 

 

 

 

 

 

 

 

 

 

 

11E0

Serial Start/Stop Initiation

0 to 1

1

F105

0

 

 

 

 

 

 

 

11E1

Startup Initiation Relays (2-5)

1 to 4

1

F50

0

 

 

 

 

 

 

 

11E2

Shutdown Initiation Relays (1-4)

0 to 3

1

F50

0

 

 

 

 

 

 

 

11E3

Serial Start/Stop Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

DIGITAL INPUTS / BREAKER STATUS

1200 Breaker Status

0 to 1

1

F209

1

DIGITAL INPUTS / GENERAL INPUT A

1210

Assign Digital Input

0 to 7

1

F210

0

 

 

 

 

 

 

 

1211

Asserted Digital Input State

0 to 1

1

F131

0

 

 

 

 

 

 

 

1212

Input Name

0 to 12

1

F22

_

 

 

 

 

 

 

 

1218

Block Input From Online

0 to 5000

1

s

F1

0

 

 

 

 

 

 

 

1219

General Input A Control

0 to 1

1

F105

0

 

 

 

 

 

 

 

121A

Pulsed Control Relay Dwell Time

0 to 250

1

s

F2

0

 

 

 

 

 

 

 

121B

Assign Control Relays (1-5)

0 to 4

1

F50

0

 

 

 

 

 

 

 

121C

General Input A Control Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

121D

General Input A Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

121E

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

121F

General Input A Alarm Delay

1 to 50000

1

s

F2

50

 

 

 

 

 

 

 

1220

General Input A Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

1221

General Input A Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

1222

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

1223

General Input A Trip Delay

1 to 50000

1

s

F2

50

 

 

 

 

 

 

 

DIGITAL INPUTS / GENERAL INPUT B

 

 

 

 

 

 

 

 

 

 

 

 

1230

Assign Digital Input

0 to 7

1

F210

0

 

 

 

 

 

 

 

1231

Asserted Digital Input State

0 to 1

1

F131

0

 

 

 

 

 

 

 

1232

Input Name

0 to 12

1

F22

_

 

 

 

 

 

 

 

1238

Block Input From Online

0 to 5000

1

s

F1

0

 

 

 

 

 

 

 

1239

General Input B Control

0 to 1

1

F105

0

 

 

 

 

 

 

 

123A

Pulsed Control Relay Dwell Time

0 to 250

1

s

F2

0

 

 

 

 

 

 

 

123B

Assign Control Relays (1-5)

0 to 4

1

F50

0

 

 

 

 

 

 

 

123C

General Input B Control Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

123D

General Input B Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

123E

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

123F

General Input B Alarm Delay

1 to 50000

1

s

F2

50

 

 

 

 

 

 

 

1240

General Input B Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

1241

General Input B Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

1, 2, 3 See Table footnotes on page 39

GE Multilin

http://www.GEindustrial.com/multilin

19

Image 23
Contents 489 Page Table of Contents Table of Contents Electrical Interface Modbus RTU Description Copyright 2004 GE MultilinGE Multilin Modbus Functions Message Format and Example ValuesModbus Functions Function Code Request status from slave Modbus Functions Function Code 16 Store Multiple Setpoints Illegal Data Address Error ResponsesEvent Recorder Memory Map InformationWaveform Capture Dual Setpoints Passcode Operation 489 Memory Map Sheet 1 Status / Trip Pickups Addr Name Range Step Units Format Default489 Memory Map Sheet 2 489 Memory Map Sheet 3 Status / Alarm PickupsMetering Data / Current Metering 489 Memory Map Sheet 4Status / Digital Inputs Status / Real Time ClockMetering Data / Voltage Metering Metering Data / Power MeteringMetering Data / Temperature 489 Memory Map Sheet 5489 Memory Map Sheet 6 Learned Data / Analog in MIN/MAX Maintenance / Trip CountersMaintenance / General Counters 489 Memory Map Sheet 7489 Memory Map Sheet 8 489 Memory Map Sheet 9 Digital Inputs / General Input E 489 Memory Map Sheet 10Digital Inputs / General Input C Digital Inputs / General Input D489 Memory Map Sheet 11 489 Memory Map Sheet 12 489 Memory Map Sheet 13 Current Elements / Ground O/C 489 Memory Map Sheet 14Current Elements / Negative Sequence 489 Memory Map Sheet 15 Current Elements / Ground Directional Current Elements / Phase DifferentialCurrent Elements / HIGH-SET Phase Overcurrent 489 Memory Map Sheet 16489 Memory Map Sheet 17 Voltage Elements / Distance Element 489 Memory Map Sheet 18Voltage Elements / Neutral Overvoltage Fundamental Voltage Elements / Loss of Excitation489 Memory Map Sheet 19 489 Memory Map Sheet 20 489 Memory Map Sheet 21 Thermal Model / Model Setup RTD Temperature / RTD #12RTD Temperature / Open RTD Sensor RTD Temperature / RTD SHORT/LOW Temperature489 Memory Map Sheet 23 489 Memory Map Sheet 24 489 Memory Map Sheet 25 Analog INPUT/OUTPUT / Analog Input 489 Memory Map Sheet 26489 Memory Map Sheet 27 Testing / Simulation ModeTesting / PRE-FAULT Setup 489 Memory Map Sheet 28 Waveform Memory Samples Waveform Memory Setup489 Memory Map Sheet 29 Decimal Places Code Type DefinitionUnsigned Value Decimal PlaceALARM/TRIP Status SwitchAlarm / Trip Type Reset ModeOvercurrent Curve Input SwitchAnalog Output ParameterData Formats Sheet 7 Order Code Simulation ModeCurve Reset Type Switch StatusAssignable Input Undervoltage TripElement Type Breaker OperationDNP Protocol DNP 3.0 Device Profile Document Variation Default VariationsDNP Implementation Table Binary Inputs Sheet 2 Binary Input / Binary01/02 Binary Inputs Sheet 1Binary Inputs Sheet 4 Binary Inputs Sheet 3Binary Output Point List Binary / Control Relay10/12 Counters Point List DNP Point Lists Binary / Frozen Counter Objects 20/21Assigned to Analog Inputs Point List Sheet 1Impedance angle Analog Inputs Point List Sheet 2Analog Inputs Point List Sheet 3 Table Notes Analog Inputs Point List Sheet 4Index GE Multilin