GE 1601-0149-A2 Memory Map Sheet 22, RTD Temperature / RTD #12, RTD Temperature / Open RTD Sensor

Page 36

 

 

 

 

 

 

 

 

 

 

 

 

489

 

 

 

 

Modbus Memory Map

 

Communications Guide

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 1: 489 Memory Map (Sheet 22 of 29)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ADDR

NAME

RANGE

STEP

UNITS

FORMAT

DEFAULT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26A4

RTD #11 Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

 

 

 

 

26A5

RTD #11 Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

26A6

RTD #11 Trip Voting

1 to 12

1

F122

11

 

 

 

 

 

 

 

 

 

 

 

26A7

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

 

 

 

 

26A8

RTD #11 Trip Temperature

1 to 250

1

°C

F1

90

 

 

 

 

 

 

 

 

 

 

 

26A9

RTD #11 Name

0 to 8

1

F22

_

 

 

 

 

 

 

 

 

 

 

 

RTD TEMPERATURE / RTD #12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26E0

RTD #12 Application

0 to 4

1

F121

3

 

 

 

 

 

 

 

 

 

 

 

26E1

RTD #12 Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

26E2

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

 

 

 

 

26E3

RTD #12 Alarm Temperature

1 to 250

1

°C

F1

60

 

 

 

 

 

 

 

 

 

 

 

26E4

RTD #12 Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

 

 

 

 

26E5

RTD #12 Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

26E6

RTD #12 Trip Voting

1 to 12

1

F122

12

 

 

 

 

 

 

 

 

 

 

 

26E7

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

 

 

 

 

26E8

RTD #12 Trip Temperature

1 to 250

1

°C

F1

80

 

 

 

 

 

 

 

 

 

 

 

26E9

RTD #12 Name

0 to 8

1

F22

_

 

 

 

 

 

 

 

 

 

 

 

RTD TEMPERATURE / OPEN RTD SENSOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2720

Open RTD Sensor Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

2721

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

 

 

 

 

2722

Open RTD Sensor Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

 

 

 

 

RTD TEMPERATURE / RTD SHORT/LOW TEMPERATURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2740

RTD Short/Low Temperature Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

2741

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

 

 

 

 

2742

RTD Short/Low Temperature Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

 

 

 

 

THERMAL MODEL / MODEL SETUP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2800

Enable Thermal Model

0 to 1

1

F103

0

 

 

 

 

 

 

 

 

 

 

 

2801

Overload Pickup Level

101 to 125

1

FLA

F3

101

 

 

 

 

 

 

 

 

 

 

 

2802

Unbalance Bias K Factor

0 to 12

1

F1

0

 

 

 

 

 

 

 

 

 

 

 

2803

Cool Time Constant Online

0 to 500

1

min

F1

15

 

 

 

 

 

 

 

 

 

 

 

2804

Cool Time Constant Offline

0 to 500

1

min

F1

30

 

 

 

 

 

 

 

 

 

 

 

2805

Hot/Cold Safe Stall Ratio

1 to 100

1

F3

100

 

 

 

 

 

 

 

 

 

 

 

2806

Enable RTD Biasing

0 to 1

1

F103

0

 

 

 

 

 

 

 

 

 

 

 

2807

RTD Bias Minimum

0 to 250

1

°C

F1

40

 

 

 

 

 

 

 

 

 

 

 

2808

RTD Bias Center Point

0 to 250

1

°C

F1

130

 

 

 

 

 

 

 

 

 

 

 

2809

RTD Bias Maximum

0 to 250

1

°C

F1

155

 

 

 

 

 

 

 

 

 

 

 

280A

Select Curve Style

0 to 2

1

F142

0

 

 

 

 

 

 

 

 

 

 

 

280B

Standard Overload Curve Number

1 to 15

1

F1

4

 

 

 

 

 

 

 

 

 

 

 

280C

Time to Trip at 1.01 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

 

 

 

 

280E

Time to Trip at 1.05 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

 

 

 

 

2810

Time to Trip at 1.10 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

 

 

 

 

2812

Time to Trip at 1.20 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

 

 

 

 

2814

Time to Trip at 1.30 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

 

 

 

 

2816

Time to Trip at 1.40 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

 

 

 

 

2818

Time to Trip at 1.50 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

 

 

 

 

281A

Time to Trip at 1.75 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

 

 

 

 

281C

Time to Trip at 2.00 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

 

 

 

 

281E

Time to Trip at 2.25 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

 

 

 

 

2820

Time to Trip at 2.50 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

 

 

 

 

2822

Time to Trip at 2.75 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

 

 

 

 

2824

Time to Trip at 3.00 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

 

 

 

 

2826

Time to Trip at 3.25 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

 

 

 

 

2828

Time to Trip at 3.50 FLA

5 to 999999

1

s

F10

5

 

 

 

 

 

 

 

 

 

 

 

1, 2, 3 See Table footnotes on page 39

32

http://www.GEindustrial.com/multilin

GE Multilin

Image 36
Contents 489 Page Table of Contents Table of Contents Copyright 2004 GE Multilin Electrical Interface Modbus RTU DescriptionGE Multilin Modbus Functions Values Message Format and ExampleModbus Functions Function Code Request status from slave Modbus Functions Function Code 16 Store Multiple Setpoints Error Responses Illegal Data AddressMemory Map Information Event RecorderWaveform Capture Dual Setpoints Passcode Operation 489 Memory Map Sheet 1 Addr Name Range Step Units Format Default 489 Memory Map Sheet 2Status / Trip Pickups Status / Alarm Pickups 489 Memory Map Sheet 3489 Memory Map Sheet 4 Status / Digital InputsStatus / Real Time Clock Metering Data / Current MeteringMetering Data / Power Metering Metering Data / Temperature489 Memory Map Sheet 5 Metering Data / Voltage Metering489 Memory Map Sheet 6 Maintenance / Trip Counters Maintenance / General Counters489 Memory Map Sheet 7 Learned Data / Analog in MIN/MAX489 Memory Map Sheet 8 489 Memory Map Sheet 9 489 Memory Map Sheet 10 Digital Inputs / General Input CDigital Inputs / General Input D Digital Inputs / General Input E489 Memory Map Sheet 11 489 Memory Map Sheet 12 489 Memory Map Sheet 13 489 Memory Map Sheet 14 Current Elements / Negative SequenceCurrent Elements / Ground O/C 489 Memory Map Sheet 15 Current Elements / Phase Differential Current Elements / HIGH-SET Phase Overcurrent489 Memory Map Sheet 16 Current Elements / Ground Directional489 Memory Map Sheet 17 489 Memory Map Sheet 18 Voltage Elements / Neutral Overvoltage FundamentalVoltage Elements / Loss of Excitation Voltage Elements / Distance Element489 Memory Map Sheet 19 489 Memory Map Sheet 20 489 Memory Map Sheet 21 RTD Temperature / RTD #12 RTD Temperature / Open RTD SensorRTD Temperature / RTD SHORT/LOW Temperature Thermal Model / Model Setup489 Memory Map Sheet 23 489 Memory Map Sheet 24 489 Memory Map Sheet 25 489 Memory Map Sheet 26 Analog INPUT/OUTPUT / Analog InputTesting / Simulation Mode Testing / PRE-FAULT Setup489 Memory Map Sheet 27 489 Memory Map Sheet 28 Waveform Memory Setup 489 Memory Map Sheet 29Waveform Memory Samples Code Type Definition Unsigned ValueDecimal Place Decimal PlacesSwitch Alarm / Trip TypeReset Mode ALARM/TRIP StatusInput Switch Analog OutputParameter Overcurrent CurveData Formats Sheet 7 Simulation Mode Curve Reset TypeSwitch Status Order CodeUndervoltage Trip Element TypeBreaker Operation Assignable InputDNP Protocol DNP 3.0 Device Profile Document Default Variations DNP Implementation TableVariation Binary Input / Binary 01/02Binary Inputs Sheet 1 Binary Inputs Sheet 2Binary Inputs Sheet 3 Binary Inputs Sheet 4Binary / Control Relay 10/12Binary Output Point List DNP Point Lists Binary / Frozen Counter Objects 20/21 Counters Point ListAnalog Inputs Point List Sheet 1 Assigned toAnalog Inputs Point List Sheet 2 Impedance angleAnalog Inputs Point List Sheet 3 Analog Inputs Point List Sheet 4 Table NotesIndex GE Multilin