GE 1601-0149-A2 manual Memory Map Sheet 10, Digital Inputs / General Input C

Page 24

 

 

 

 

 

 

 

 

 

 

 

 

489

 

 

 

 

Modbus Memory Map

 

Communications Guide

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 1: 489 Memory Map (Sheet 10 of 29)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ADDR

NAME

RANGE

STEP

UNITS

FORMAT

DEFAULT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1242

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

 

 

 

 

1243

General Input B Trip Delay

1 to 50000

1

s

F2

50

 

 

 

 

 

 

 

 

 

 

 

DIGITAL INPUTS / GENERAL INPUT C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1250

Assign Digital Input

0 to 7

1

F210

0

 

 

 

 

 

 

 

 

 

 

 

1251

Asserted Digital Input State

0 to 1

1

F131

0

 

 

 

 

 

 

 

 

 

 

 

1252

Input Name

0 to 12

1

F22

_

 

 

 

 

 

 

 

 

 

 

 

1258

Block Input From Online

0 to 5000

1

s

F1

0

 

 

 

 

 

 

 

 

 

 

 

1259

General Input C Control

0 to 1

1

F105

0

 

 

 

 

 

 

 

 

 

 

 

125A

Pulsed Control Relay Dwell Time

0 to 250

1

s

F2

0

 

 

 

 

 

 

 

 

 

 

 

125B

Assign Control Relays (1-5)

0 to 4

1

F50

0

 

 

 

 

 

 

 

 

 

 

 

125C

General Input C Control Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

 

 

 

 

125D

General Input C Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

125E

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

 

 

 

 

125F

General Input C Alarm Delay

1 to 50000

1

s

F2

50

 

 

 

 

 

 

 

 

 

 

 

1260

General Input C Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

 

 

 

 

1261

General Input C Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

1262

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

 

 

 

 

1263

General Input C Trip Delay

1 to 50000

1

s

F2

50

 

 

 

 

 

 

 

 

 

 

 

DIGITAL INPUTS / GENERAL INPUT D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1270

Assign Digital Input

0 to 7

1

F210

0

 

 

 

 

 

 

 

 

 

 

 

1271

Asserted Digital Input State

0 to 1

1

F131

0

 

 

 

 

 

 

 

 

 

 

 

1272

Input Name

0 to 12

1

F22

_

 

 

 

 

 

 

 

 

 

 

 

1278

Block Input From Online

0 to 5000

1

s

F1

0

 

 

 

 

 

 

 

 

 

 

 

1279

General Input D Control

0 to 1

1

F105

0

 

 

 

 

 

 

 

 

 

 

 

127A

Pulsed Control Relay Dwell Time

0 to 250

1

s

F2

0

 

 

 

 

 

 

 

 

 

 

 

127B

Assign Control Relays (1-5)

0 to 4

1

F50

0

 

 

 

 

 

 

 

 

 

 

 

127C

General Input D Control Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

 

 

 

 

127D

General Input D Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

127E

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

 

 

 

 

127F

General Input D Alarm Delay

1 to 50000

1

s

F2

50

 

 

 

 

 

 

 

 

 

 

 

1280

General Input D Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

 

 

 

 

1281

General Input D Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

1282

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

 

 

 

 

1283

General Input D Trip Delay

1 to 50000

1

s

F2

50

 

 

 

 

 

 

 

 

 

 

 

DIGITAL INPUTS / GENERAL INPUT E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1290

Assign Digital Input

0 to 7

1

F210

0

 

 

 

 

 

 

 

 

 

 

 

1291

Asserted Digital Input State

0 to 1

1

F131

0

 

 

 

 

 

 

 

 

 

 

 

1292

Input Name

0 to 12

1

F22

_

 

 

 

 

 

 

 

 

 

 

 

1298

Block Input From Online

0 to 5000

1

s

F1

0

 

 

 

 

 

 

 

 

 

 

 

1299

General Input E Control

0 to 1

1

F105

0

 

 

 

 

 

 

 

 

 

 

 

129A

Pulsed Control Relay Dwell Time

0 to 250

1

s

F2

0

 

 

 

 

 

 

 

 

 

 

 

129B

Assign Control Relays (1-5)

0 to 4

1

F50

0

 

 

 

 

 

 

 

 

 

 

 

129C

General Input E Control Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

 

 

 

 

129D

General Input E Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

129E

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

 

 

 

 

129F

General Input E Alarm Delay

1 to 50000

1

s

F2

50

 

 

 

 

 

 

 

 

 

 

 

12A0

General Input E Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

 

 

 

 

12A1

General Input E Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

12A2

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

 

 

 

 

12A3

General Input E Trip Delay

1 to 50000

1

s

F2

50

 

 

 

 

 

 

 

 

 

 

 

DIGITAL INPUTS / GENERAL INPUT F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12B0

Assign Digital Input

0 to 7

1

F210

0

 

 

 

 

 

 

 

 

 

 

 

12B1

Asserted Digital Input State

0 to 1

1

F131

0

 

 

 

 

 

 

 

 

 

 

 

1, 2, 3 See Table footnotes on page 39

20

http://www.GEindustrial.com/multilin

GE Multilin

Image 24
Contents 489 Page Table of Contents Table of Contents Copyright 2004 GE Multilin Electrical Interface Modbus RTU DescriptionGE Multilin Modbus Functions Values Message Format and ExampleModbus Functions Function Code Request status from slave Modbus Functions Function Code 16 Store Multiple Setpoints Error Responses Illegal Data AddressMemory Map Information Event RecorderWaveform Capture Dual Setpoints Passcode Operation 489 Memory Map Sheet 1 Addr Name Range Step Units Format Default 489 Memory Map Sheet 2Status / Trip Pickups Status / Alarm Pickups 489 Memory Map Sheet 3489 Memory Map Sheet 4 Status / Digital InputsStatus / Real Time Clock Metering Data / Current MeteringMetering Data / Power Metering Metering Data / Temperature489 Memory Map Sheet 5 Metering Data / Voltage Metering489 Memory Map Sheet 6 Maintenance / Trip Counters Maintenance / General Counters489 Memory Map Sheet 7 Learned Data / Analog in MIN/MAX489 Memory Map Sheet 8 489 Memory Map Sheet 9 489 Memory Map Sheet 10 Digital Inputs / General Input CDigital Inputs / General Input D Digital Inputs / General Input E489 Memory Map Sheet 11 489 Memory Map Sheet 12 489 Memory Map Sheet 13 489 Memory Map Sheet 14 Current Elements / Negative SequenceCurrent Elements / Ground O/C 489 Memory Map Sheet 15 Current Elements / Phase Differential Current Elements / HIGH-SET Phase Overcurrent489 Memory Map Sheet 16 Current Elements / Ground Directional489 Memory Map Sheet 17 489 Memory Map Sheet 18 Voltage Elements / Neutral Overvoltage FundamentalVoltage Elements / Loss of Excitation Voltage Elements / Distance Element489 Memory Map Sheet 19 489 Memory Map Sheet 20 489 Memory Map Sheet 21 RTD Temperature / RTD #12 RTD Temperature / Open RTD SensorRTD Temperature / RTD SHORT/LOW Temperature Thermal Model / Model Setup489 Memory Map Sheet 23 489 Memory Map Sheet 24 489 Memory Map Sheet 25 489 Memory Map Sheet 26 Analog INPUT/OUTPUT / Analog InputTesting / Simulation Mode Testing / PRE-FAULT Setup489 Memory Map Sheet 27 489 Memory Map Sheet 28 Waveform Memory Setup 489 Memory Map Sheet 29Waveform Memory Samples Code Type Definition Unsigned ValueDecimal Place Decimal PlacesSwitch Alarm / Trip TypeReset Mode ALARM/TRIP StatusInput Switch Analog OutputParameter Overcurrent CurveData Formats Sheet 7 Simulation Mode Curve Reset TypeSwitch Status Order CodeUndervoltage Trip Element TypeBreaker Operation Assignable InputDNP Protocol DNP 3.0 Device Profile Document Default Variations DNP Implementation TableVariation Binary Input / Binary 01/02Binary Inputs Sheet 1 Binary Inputs Sheet 2Binary Inputs Sheet 3 Binary Inputs Sheet 4Binary / Control Relay 10/12Binary Output Point List DNP Point Lists Binary / Frozen Counter Objects 20/21 Counters Point ListAnalog Inputs Point List Sheet 1 Assigned toAnalog Inputs Point List Sheet 2 Impedance angleAnalog Inputs Point List Sheet 3 Analog Inputs Point List Sheet 4 Table NotesIndex GE Multilin