Modbus Memory Map
Table 1: 489 Memory Map (Sheet 21 of 29)
489
Communications Guide
ADDR | NAME | RANGE | STEP | UNITS | FORMAT | DEFAULT |
|
|
|
|
|
|
|
2566 | RTD #6 Trip Voting | 1 to 12 | 1 | – | F122 | 6 |
|
|
|
|
|
|
|
2567 | Assign Trip Relays | 0 to 3 | 1 | – | F50 | 1 |
|
|
|
|
|
|
|
2568 | RTD #6 Trip Temperature | 1 to 250 | 1 | °C | F1 | 155 |
|
|
|
|
|
|
|
2569 | RTD #6 Name | 0 to 8 | 1 | – | F22 | _ |
|
|
|
|
|
|
|
RTD TEMPERATURE / RTD #7 |
|
|
|
|
| |
|
|
|
|
|
|
|
25A0 | RTD #7 Application | 0 to 4 | 1 | – | F121 | 2 |
|
|
|
|
|
|
|
25A1 | RTD #7 Alarm | 0 to 2 | 1 | – | F115 | 0 |
|
|
|
|
|
|
|
25A2 | Assign Alarm Relays | 1 to 4 | 1 | – | F50 | 16 |
|
|
|
|
|
|
|
25A3 | RTD #7 Alarm Temperature | 1 to 250 | 1 | °C | F1 | 80 |
|
|
|
|
|
|
|
25A4 | RTD #7 Alarm Events | 0 to 1 | 1 | – | F105 | 0 |
|
|
|
|
|
|
|
25A5 | RTD #7 Trip | 0 to 2 | 1 | – | F115 | 0 |
|
|
|
|
|
|
|
25A6 | RTD #7 Trip Voting | 1 to 12 | 1 | – | F122 | 7 |
|
|
|
|
|
|
|
25A7 | Assign Trip Relays | 0 to 3 | 1 | – | F50 | 1 |
|
|
|
|
|
|
|
25A8 | RTD #7 Trip Temperature | 1 to 250 | 1 | °C | F1 | 90 |
|
|
|
|
|
|
|
25A9 | RTD #7 Name | 0 to 8 | 1 | – | F22 | _ |
|
|
|
|
|
|
|
RTD TEMPERATURE / RTD #8 |
|
|
|
|
| |
|
|
|
|
|
|
|
25E0 | RTD #8 Application | 0 to 4 | 1 | – | F121 | 2 |
|
|
|
|
|
|
|
25E1 | RTD #8 Alarm | 0 to 2 | 1 | – | F115 | 0 |
|
|
|
|
|
|
|
25E2 | Assign Alarm Relays | 1 to 4 | 1 | – | F50 | 16 |
|
|
|
|
|
|
|
25E3 | RTD #8 Alarm Temperature | 1 to 250 | 1 | °C | F1 | 80 |
|
|
|
|
|
|
|
25E4 | RTD #8 Alarm Events | 0 to 1 | 1 | – | F105 | 0 |
|
|
|
|
|
|
|
25E5 | RTD #8 Trip | 0 to 2 | 1 | – | F115 | 0 |
|
|
|
|
|
|
|
25E6 | RTD #8 Trip Voting | 1 to 12 | 1 | – | F122 | 8 |
|
|
|
|
|
|
|
25E7 | Assign Trip Relays | 0 to 3 | 1 | – | F50 | 1 |
|
|
|
|
|
|
|
25E8 | RTD #8 Trip Temperature | 1 to 250 | 1 | °C | F1 | 90 |
|
|
|
|
|
|
|
25E9 | RTD #8 Name | 0 to 8 | 1 | – | F22 | _ |
|
|
|
|
|
|
|
RTD TEMPERATURE / RTD #9 |
|
|
|
|
| |
|
|
|
|
|
|
|
2620 | RTD #9 Application | 0 to 4 | 1 | – | F121 | 2 |
|
|
|
|
|
|
|
2621 | RTD #9 Alarm | 0 to 2 | 1 | – | F115 | 0 |
|
|
|
|
|
|
|
2622 | Assign Alarm Relays | 1 to 4 | 1 | – | F50 | 16 |
|
|
|
|
|
|
|
2623 | RTD #9 Alarm Temperature | 1 to 250 | 1 | °C | F1 | 80 |
|
|
|
|
|
|
|
2624 | RTD #9 Alarm Events | 0 to 1 | 1 | – | F105 | 0 |
|
|
|
|
|
|
|
2625 | RTD #9 Trip | 0 to 2 | 1 | – | F115 | 0 |
|
|
|
|
|
|
|
2626 | RTD #9 Trip Voting | 1 to 12 | 1 | – | F122 | 9 |
|
|
|
|
|
|
|
2627 | Assign Trip Relays | 0 to 3 | 1 | – | F50 | 1 |
|
|
|
|
|
|
|
2628 | RTD #9 Trip Temperature | 1 to 250 | 1 | °C | F1 | 90 |
|
|
|
|
|
|
|
2629 | RTD #9 Name | 0 to 8 | 1 | – | F22 | _ |
|
|
|
|
|
|
|
RTD TEMPERATURE / RTD #10 |
|
|
|
|
| |
|
|
|
|
|
|
|
2660 | RTD #10 Application | 0 to 4 | 1 | – | F121 | 2 |
|
|
|
|
|
|
|
2661 | RTD #10 Alarm | 0 to 2 | 1 | – | F115 | 0 |
|
|
|
|
|
|
|
2662 | Assign Alarm Relays | 1 to 4 | 1 | – | F50 | 16 |
|
|
|
|
|
|
|
2663 | RTD #10 Alarm Temperature | 1 to 250 | 1 | °C | F1 | 80 |
|
|
|
|
|
|
|
2664 | RTD #10 Alarm Events | 0 to 1 | 1 | – | F105 | 0 |
|
|
|
|
|
|
|
2665 | RTD #10 Trip | 0 to 2 | 1 | – | F115 | 0 |
|
|
|
|
|
|
|
2666 | RTD #10 Trip Voting | 1 to 12 | 1 | – | F122 | 10 |
|
|
|
|
|
|
|
2667 | Assign Trip Relays | 0 to 3 | 1 | – | F50 | 1 |
|
|
|
|
|
|
|
2668 | RTD #10 Trip Temperature | 1 to 250 | 1 | °C | F1 | 90 |
|
|
|
|
|
|
|
2669 | RTD #10 Name | 0 to 8 | 1 | – | F22 | _ |
|
|
|
|
|
|
|
RTD TEMPERATURE / RTD #11 |
|
|
|
|
| |
|
|
|
|
|
|
|
26A0 | RTD #11 Application | 0 to 4 | 1 | – | F121 | 4 |
|
|
|
|
|
|
|
26A1 | RTD #11 Alarm | 0 to 2 | 1 | – | F115 | 0 |
|
|
|
|
|
|
|
26A2 | Assign Alarm Relays | 1 to 4 | 1 | – | F50 | 16 |
|
|
|
|
|
|
|
26A3 | RTD #11 Alarm Temperature | 1 to 250 | 1 | °C | F1 | 80 |
|
|
|
|
|
|
|
1, 2, 3 See Table footnotes on page 39
GE Multilin |
http://www.GEindustrial.com/multilin
31 |