GE 1601-0149-A2 manual Memory Map Sheet 11

Page 25

Modbus Memory Map

Table 1: 489 Memory Map (Sheet 11 of 29)

489

Communications Guide

ADDR

NAME

RANGE

STEP

UNITS

FORMAT

DEFAULT

 

 

 

 

 

 

 

12B2

Input Name

0 to 12

1

F22

_

 

 

 

 

 

 

 

12B8

Block Input From Online

0 to 5000

1

s

F1

0

 

 

 

 

 

 

 

12B9

General Input F Control

0 to 1

1

F105

0

 

 

 

 

 

 

 

12BA

Pulsed Control Relay Dwell Time

0 to 250

1

s

F2

0

 

 

 

 

 

 

 

12BB

Assign Control Relays (1-5)

0 to 4

1

F50

0

 

 

 

 

 

 

 

12BC

General Input F Control Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

12BD

General Input F Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

12BE

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

12BF

General Input F Alarm Delay

1 to 50000

1

s

F2

50

 

 

 

 

 

 

 

12C0

General Input F Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

12C1

General Input F Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

12C2

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

12C3

General Input F Trip Delay

1 to 50000

1

s

F2

50

 

 

 

 

 

 

 

DIGITAL INPUTS / GENERAL INPUT G

 

 

 

 

 

 

 

 

 

 

 

 

12D0

Assign Digital Input

0 to 7

1

F210

0

 

 

 

 

 

 

 

12D1

Asserted Digital Input State

0 to 1

1

F131

0

 

 

 

 

 

 

 

12D2

Input Name

0 to 12

1

F22

_

 

 

 

 

 

 

 

12D8

Block Input From Online

0 to 5000

1

s

F1

0

 

 

 

 

 

 

 

12D9

General Input G Control

0 to 1

1

F105

0

 

 

 

 

 

 

 

12DA

Pulsed Control Relay Dwell Time

0 to 250

1

s

F2

0

 

 

 

 

 

 

 

12DB

Assign Control Relays (1-5)

0 to 4

1

F50

0

 

 

 

 

 

 

 

12DC

General Input G Control Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

12DD

General Input G Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

12DE

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

12DF

General Input G Alarm Delay

1 to 50000

1

s

F2

50

 

 

 

 

 

 

 

12E0

General Input G Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

12E1

General Input G Trip

0 to 2

1

F115

0

 

 

 

 

 

 

 

12E2

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

12E3

General Input G Trip Delay

1 to 50000

1

s

F2

50

 

 

 

 

 

 

 

DIGITAL INPUTS / REMOTE RESET

 

 

 

 

 

 

 

 

 

 

 

 

1300

Assign Digital Input

0 to 7

1

F210

0

 

 

 

 

 

 

 

DIGITAL INPUTS / TEST INPUT

 

 

 

 

 

 

 

 

 

 

 

 

1310

Assign Digital Input

0 to 7

1

F210

0

 

 

 

 

 

 

 

DIGITAL INPUTS / THERMAL RESET

 

 

 

 

 

1320 Assign Digital Input

0 to 7

1

F210

0

DIGITAL INPUTS / DUAL SETPOINTS

1340

Assign Digital Input

0 to 7

1

F210

0

 

 

 

 

 

 

 

1341

Active Setpoint Group

0 to 1

1

F118

0

 

 

 

 

 

 

 

1342

Edit Setpoint Group

0 to 1

1

F118

0

 

 

 

 

 

 

 

DIGITAL INPUTS / SEQUENTIAL TRIP

 

 

 

 

 

 

 

 

 

 

 

 

1360

Assign Digital Input

0 to 7

1

F210

0

 

 

 

 

 

 

 

1361

Sequential Trip Type

0 to 1

1

F206

0

 

 

 

 

 

 

 

1362

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

1363

Sequential Trip Level

2 to 99

1

Rated MW

F14

5

 

 

 

 

 

 

 

1365

Sequential Trip Delay

2 to 1200

1

s

F2

10

 

 

 

 

 

 

 

DIGITAL INPUTS / FIELD-BREAKER DISCREPANCY

 

 

 

 

 

 

 

 

 

 

 

 

1380

Assign Digital Input

0 to 7

1

F210

0

 

 

 

 

 

 

 

1381

Field Status Contact

0 to 1

1

F109

0

 

 

 

 

 

 

 

1382

Assign Trip Relays (1-4)

0 to 3

1

F50

1

 

 

 

 

 

 

 

1383

Field-Breaker Discrepancy Trip Delay

1 to 5000

1

s

F2

10

 

 

 

 

 

 

 

DIGITAL INPUTS / TACHOMETER

 

 

 

 

 

 

 

 

 

 

 

 

13A0

Assign Digital Input

0 to 7

1

F210

0

 

 

 

 

 

 

 

13A1

Rated Speed

100 to 3600

1

RPM

F1

3600

 

 

 

 

 

 

 

1, 2, 3 See Table footnotes on page 39

GE Multilin

http://www.GEindustrial.com/multilin

21

Image 25
Contents 489 Page Table of Contents Table of Contents Electrical Interface Modbus RTU Description Copyright 2004 GE MultilinGE Multilin Modbus Functions Message Format and Example ValuesModbus Functions Function Code Request status from slave Modbus Functions Function Code 16 Store Multiple Setpoints Illegal Data Address Error ResponsesEvent Recorder Memory Map InformationWaveform Capture Dual Setpoints Passcode Operation 489 Memory Map Sheet 1 489 Memory Map Sheet 2 Addr Name Range Step Units Format DefaultStatus / Trip Pickups 489 Memory Map Sheet 3 Status / Alarm PickupsStatus / Digital Inputs 489 Memory Map Sheet 4Status / Real Time Clock Metering Data / Current MeteringMetering Data / Temperature Metering Data / Power Metering489 Memory Map Sheet 5 Metering Data / Voltage Metering489 Memory Map Sheet 6 Maintenance / General Counters Maintenance / Trip Counters489 Memory Map Sheet 7 Learned Data / Analog in MIN/MAX489 Memory Map Sheet 8 489 Memory Map Sheet 9 Digital Inputs / General Input C 489 Memory Map Sheet 10Digital Inputs / General Input D Digital Inputs / General Input E489 Memory Map Sheet 11 489 Memory Map Sheet 12 489 Memory Map Sheet 13 Current Elements / Negative Sequence 489 Memory Map Sheet 14Current Elements / Ground O/C 489 Memory Map Sheet 15 Current Elements / HIGH-SET Phase Overcurrent Current Elements / Phase Differential489 Memory Map Sheet 16 Current Elements / Ground Directional489 Memory Map Sheet 17 Voltage Elements / Neutral Overvoltage Fundamental 489 Memory Map Sheet 18Voltage Elements / Loss of Excitation Voltage Elements / Distance Element489 Memory Map Sheet 19 489 Memory Map Sheet 20 489 Memory Map Sheet 21 RTD Temperature / Open RTD Sensor RTD Temperature / RTD #12RTD Temperature / RTD SHORT/LOW Temperature Thermal Model / Model Setup489 Memory Map Sheet 23 489 Memory Map Sheet 24 489 Memory Map Sheet 25 Analog INPUT/OUTPUT / Analog Input 489 Memory Map Sheet 26Testing / PRE-FAULT Setup Testing / Simulation Mode489 Memory Map Sheet 27 489 Memory Map Sheet 28 489 Memory Map Sheet 29 Waveform Memory SetupWaveform Memory Samples Unsigned Value Code Type DefinitionDecimal Place Decimal PlacesAlarm / Trip Type SwitchReset Mode ALARM/TRIP StatusAnalog Output Input SwitchParameter Overcurrent CurveData Formats Sheet 7 Curve Reset Type Simulation ModeSwitch Status Order CodeElement Type Undervoltage TripBreaker Operation Assignable InputDNP Protocol DNP 3.0 Device Profile Document DNP Implementation Table Default VariationsVariation 01/02 Binary Input / BinaryBinary Inputs Sheet 1 Binary Inputs Sheet 2Binary Inputs Sheet 4 Binary Inputs Sheet 310/12 Binary / Control RelayBinary Output Point List Counters Point List DNP Point Lists Binary / Frozen Counter Objects 20/21Assigned to Analog Inputs Point List Sheet 1Impedance angle Analog Inputs Point List Sheet 2Analog Inputs Point List Sheet 3 Table Notes Analog Inputs Point List Sheet 4Index GE Multilin