GE 1601-0149-A2 manual Memory Map Sheet 24

Page 38

 

 

 

 

 

 

 

 

 

 

 

 

489

 

 

 

 

Modbus Memory Map

 

Communications Guide

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 1: 489 Memory Map (Sheet 24 of 29)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ADDR

NAME

RANGE

STEP

UNITS

FORMAT

DEFAULT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2A65

Current Demand Alarm Events

0 to 1

1

A

F105

0

 

 

 

 

 

 

 

 

 

 

 

MONITORING / MW DEMAND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2A70

MW Demand Period

5 to 90

1

min

F1

15

 

 

 

 

 

 

 

 

 

 

 

2A71

MW Demand Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

2A72

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

 

 

 

 

2A73

MW Demand Limit

10 to 200

1

Rated

F14

125

 

 

 

 

 

 

 

 

 

 

 

2A75

MW Demand Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

 

 

 

 

MONITORING / Mvar DEMAND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2A80

Mvar Demand Period

5 to 90

1

min

F1

15

 

 

 

 

 

 

 

 

 

 

 

2A81

Mvar Demand Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

2A82

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

 

 

 

 

2A83

Mvar Demand Limit

10 to 200

1

Rated

F14

125

 

 

 

 

 

 

 

 

 

 

 

2A85

Mvar Demand Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

 

 

 

 

MONITORING / MVA DEMAND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2A90

MVA Demand Period

5 to 90

1

min

F1

15

 

 

 

 

 

 

 

 

 

 

 

2A91

MVA Demand Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

2A92

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

 

 

 

 

2A93

MVA Demand Limit

10 to 200

1

Rated

F14

125

 

 

 

 

 

 

 

 

 

 

 

2A95

MVA Demand Alarm Events

0 to 1

1

F105

0

 

 

 

 

 

 

 

 

 

 

 

MONITORING / PULSE OUTPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2AB0

Positive kWh Pulse Output Relays (2-5)

1 to 4

1

F50

0

 

 

 

 

 

 

 

 

 

 

 

2AB1

Positive kWh Pulse Output Interval

1 to 50000

1

F1

10

 

 

 

 

 

 

 

 

 

 

 

2AB2

Positive kvarh Pulse Output Relays (2-5)

1 to 4

1

F50

0

 

 

 

 

 

 

 

 

 

 

 

2AB3

Positive kvarh Pulse Output Interval

1 to 50000

1

F1

10

 

 

 

 

 

 

 

 

 

 

 

2AB4

Negative kvarh Pulse Output Relays (2-5)

1 to 4

1

F50

0

 

 

 

 

 

 

 

 

 

 

 

2AB5

Negative kvarh Pulse Output Interval

1 to 50000

1

F1

10

 

 

 

 

 

 

 

 

 

 

 

2AB6

Pulse Width

200 to 1000

1

F1

200

 

 

 

 

 

 

 

 

 

 

 

MONITORING / RUNNING HOUR SETUP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2AC0

Initial Generator Running Hours

0 to 999999

1

h

F12

0

 

 

 

 

 

 

 

 

 

 

 

2AC2

Generator Running Hour Alarm

0 to 2

1

F115

0

 

 

 

 

 

 

 

 

 

 

 

2AC3

Assign Alarm Relays (2-5)

1 to 4

1

F50

16

 

 

 

 

 

 

 

 

 

 

 

2AC4

Generator Running Hour Limit

1 to 1000000

1

h

F12

1000

 

 

 

 

 

 

 

 

 

 

 

2AC6

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ANALOG INPUT/OUTPUT / ANALOG OUTPUT 1

 

 

 

 

 

 

2B00 Analog Output 1

0 to 42

1

F127

0

ANALOG INPUT/OUTPUT / ANALOG OUTPUT 2

2B01 Analog Output 2

0 to 42

1

F127

0

ANALOG INPUT/OUTPUT / ANALOG OUTPUT 3

2B02 Analog Output 3

0 to 42

1

F127

0

ANALOG INPUT/OUTPUT / ANALOG OUTPUT 4

2B03 Analog Output 4

0 to 42

1

F127

0

ANALOG INPUT/OUTPUT / ANALOG OUTPUTS

2B04

Ia Output Current Minimum

0 to 2000

1

FLA

F3

0

 

 

 

 

 

 

 

2B05

Ia Output Current Maximum

0 to 2000

1

FLA

F3

125

 

 

 

 

 

 

 

2B06

Ib Output Current Minimum

0 to 2000

1

FLA

F3

0

 

 

 

 

 

 

 

2B07

Ib Output Current Maximum

0 to 2000

1

FLA

F3

125

 

 

 

 

 

 

 

2B08

Ic Output Current Minimum

0 to 2000

1

FLA

F3

0

 

 

 

 

 

 

 

2B09

Ic Output Current Maximum

0 to 2000

1

FLA

F3

125

 

 

 

 

 

 

 

2B0A

Average Output Current Minimum

0 to 2000

1

FLA

F3

0

 

 

 

 

 

 

 

2B0B

Average Output Current Maximum

0 to 2000

1

FLA

F3

125

 

 

 

 

 

 

 

2B0C

Negative Sequence Current Minimum

0 to 2000

1

%FLA

F1

0

 

 

 

 

 

 

 

2B0D

Negative Sequence Current Maximum

0 to 2000

1

%FLA

F1

100

 

 

 

 

 

 

 

2B0E

Averaged Generator Load Minimum

0 to 2000

1

FLA

F3

0

 

 

 

 

 

 

 

1, 2, 3 See Table footnotes on page 39

34

http://www.GEindustrial.com/multilin

GE Multilin

Image 38
Contents 489 Page Table of Contents Table of Contents Copyright 2004 GE Multilin Electrical Interface Modbus RTU DescriptionGE Multilin Modbus Functions Values Message Format and ExampleModbus Functions Function Code Request status from slave Modbus Functions Function Code 16 Store Multiple Setpoints Error Responses Illegal Data AddressMemory Map Information Event RecorderWaveform Capture Dual Setpoints Passcode Operation 489 Memory Map Sheet 1 Status / Trip Pickups Addr Name Range Step Units Format Default489 Memory Map Sheet 2 Status / Alarm Pickups 489 Memory Map Sheet 3Status / Real Time Clock 489 Memory Map Sheet 4Status / Digital Inputs Metering Data / Current Metering489 Memory Map Sheet 5 Metering Data / Power MeteringMetering Data / Temperature Metering Data / Voltage Metering489 Memory Map Sheet 6 489 Memory Map Sheet 7 Maintenance / Trip CountersMaintenance / General Counters Learned Data / Analog in MIN/MAX489 Memory Map Sheet 8 489 Memory Map Sheet 9 Digital Inputs / General Input D 489 Memory Map Sheet 10Digital Inputs / General Input C Digital Inputs / General Input E489 Memory Map Sheet 11 489 Memory Map Sheet 12 489 Memory Map Sheet 13 Current Elements / Ground O/C 489 Memory Map Sheet 14Current Elements / Negative Sequence 489 Memory Map Sheet 15 489 Memory Map Sheet 16 Current Elements / Phase DifferentialCurrent Elements / HIGH-SET Phase Overcurrent Current Elements / Ground Directional489 Memory Map Sheet 17 Voltage Elements / Loss of Excitation 489 Memory Map Sheet 18Voltage Elements / Neutral Overvoltage Fundamental Voltage Elements / Distance Element489 Memory Map Sheet 19 489 Memory Map Sheet 20 489 Memory Map Sheet 21 RTD Temperature / RTD SHORT/LOW Temperature RTD Temperature / RTD #12RTD Temperature / Open RTD Sensor Thermal Model / Model Setup489 Memory Map Sheet 23 489 Memory Map Sheet 24 489 Memory Map Sheet 25 489 Memory Map Sheet 26 Analog INPUT/OUTPUT / Analog Input489 Memory Map Sheet 27 Testing / Simulation ModeTesting / PRE-FAULT Setup 489 Memory Map Sheet 28 Waveform Memory Samples Waveform Memory Setup489 Memory Map Sheet 29 Decimal Place Code Type DefinitionUnsigned Value Decimal PlacesReset Mode SwitchAlarm / Trip Type ALARM/TRIP StatusParameter Input SwitchAnalog Output Overcurrent CurveData Formats Sheet 7 Switch Status Simulation ModeCurve Reset Type Order CodeBreaker Operation Undervoltage TripElement Type Assignable InputDNP Protocol DNP 3.0 Device Profile Document Variation Default VariationsDNP Implementation Table Binary Inputs Sheet 1 Binary Input / Binary01/02 Binary Inputs Sheet 2Binary Inputs Sheet 3 Binary Inputs Sheet 4Binary Output Point List Binary / Control Relay10/12 DNP Point Lists Binary / Frozen Counter Objects 20/21 Counters Point ListAnalog Inputs Point List Sheet 1 Assigned toAnalog Inputs Point List Sheet 2 Impedance angleAnalog Inputs Point List Sheet 3 Analog Inputs Point List Sheet 4 Table NotesIndex GE Multilin