GE 1601-0149-A2 manual Memory Map Sheet 4, Status / Digital Inputs, Status / Real Time Clock

Page 18

 

 

 

 

 

 

 

 

 

 

 

 

489

 

 

 

 

Modbus Memory Map

 

Communications Guide

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 1: 489 Memory Map (Sheet 4 of 29)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ADDR

NAME

RANGE

STEP

UNITS

FORMAT

DEFAULT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0320

RTD #12 Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0321

Open Sensor Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0322

Short/Low Temperature Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0323

Thermal Model Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0324

Trip Counter Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0325

Breaker Failure Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0326

Trip Coil Monitor Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0327

VT Fuse Failure Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0328

Current Demand Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0329

MW Demand Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

032A

Mvar Demand Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

032B

MVA Demand Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

032C

Analog Input 1 Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

032D

Analog Input 2 Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

032E

Analog Input 3 Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

032F

Analog Input 4 Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0330

Not Programmed Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0331

Simulation Mode Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0332

Output Relays Forced Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0333

Analog Output Forced Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0334

Test Switch Shorted Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0335

Ground Directional Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0336

IRIG-B Alarm Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

0337

Generator Running Hour Pickup

0 to 4

1

F123

0

 

 

 

 

 

 

 

 

 

 

 

STATUS / DIGITAL INPUTS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0380

Access Switch State

0 to 1

1

F207

0

 

 

 

 

 

 

 

 

 

 

 

0381

Breaker Status Switch State

0 to 1

1

F207

0

 

 

 

 

 

 

 

 

 

 

 

0382

Assignable Digital Input 1 State

0 to 1

1

F207

0

 

 

 

 

 

 

 

 

 

 

 

0383

Assignable Digital Input 2 State

0 to 1

1

F207

0

 

 

 

 

 

 

 

 

 

 

 

0384

Assignable Digital Input 3 State

0 to 1

1

F207

0

 

 

 

 

 

 

 

 

 

 

 

0385

Assignable Digital Input 4 State

0 to 1

1

F207

0

 

 

 

 

 

 

 

 

 

 

 

0386

Assignable Digital Input 5 State

0 to 1

1

F207

0

 

 

 

 

 

 

 

 

 

 

 

0387

Assignable Digital Input 6 State

0 to 1

1

F207

0

 

 

 

 

 

 

 

 

 

 

 

0388

Assignable Digital Input 7 State

0 to 1

1

F207

0

 

 

 

 

 

 

 

 

 

 

 

0389

Trip Coil Supervision

0 to 1

1

F132

0

 

 

 

 

 

 

 

 

 

 

 

STATUS / REAL TIME CLOCK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03FC

Date (Read-only)

N/A

N/A

N/A

F18

N/A

 

 

 

 

 

 

 

 

 

03FE

Time (Read-only)

N/A

N/A

N/A

F19

N/A

 

 

 

 

 

 

 

 

 

 

METERING DATA / CURRENT METERING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0400

Phase A Output Current

0 to 999999

1

Amps

F12

0

 

 

 

 

 

 

 

 

 

 

 

0402

Phase B Output Current

0 to 999999

1

Amps

F12

0

 

 

 

 

 

 

 

 

 

 

 

0404

Phase C Output Current

0 to 999999

1

Amps

F12

0

 

 

 

 

 

 

 

 

 

 

 

0406

Phase A Neutral-Side Current

0 to 999999

1

Amps

F12

0

 

 

 

 

 

 

 

 

 

 

 

0408

Phase B Neutral-Side Current

0 to 999999

1

Amps

F12

0

 

 

 

 

 

 

 

 

 

 

 

040A

Phase C Neutral-Side Current

0 to 999999

1

Amps

F12

0

 

 

 

 

 

 

 

 

 

 

 

040C

Phase A Differential Current

0 to 999999

1

Amps

F12

0

 

 

 

 

 

 

 

 

 

 

 

040E

Phase B Differential Current

0 to 999999

1

Amps

F12

0

 

 

 

 

 

 

 

 

 

 

 

0410

Phase C Differential Current

0 to 999999

1

Amps

F12

0

 

 

 

 

 

 

 

 

 

 

 

0412

Average Phase Current

0 to 999999

1

Amps

F12

0

 

 

 

 

 

 

 

 

 

 

 

0414

Generator Load

0 to 2000

1

% FLA

F1

0

 

 

 

 

 

 

 

 

 

 

 

0415

Negative Sequence Current

0 to 2000

1

% FLA

F1

0

 

 

 

 

 

 

 

 

 

 

 

0416

Ground Current

0 to 10000

1

Amps

F14

0

 

 

 

 

 

 

 

 

 

 

 

0420

Phase A Current Angle

0 to 359

1

°

F1

0

 

 

 

 

 

 

 

 

 

 

 

1, 2, 3 See Table footnotes on page 39

14

http://www.GEindustrial.com/multilin

GE Multilin

Image 18
Contents 489 Page Table of Contents Table of Contents Copyright 2004 GE Multilin Electrical Interface Modbus RTU DescriptionGE Multilin Modbus Functions Values Message Format and ExampleModbus Functions Function Code Request status from slave Modbus Functions Function Code 16 Store Multiple Setpoints Error Responses Illegal Data AddressMemory Map Information Event RecorderWaveform Capture Dual Setpoints Passcode Operation 489 Memory Map Sheet 1 Addr Name Range Step Units Format Default 489 Memory Map Sheet 2Status / Trip Pickups Status / Alarm Pickups 489 Memory Map Sheet 3Status / Real Time Clock 489 Memory Map Sheet 4Status / Digital Inputs Metering Data / Current Metering489 Memory Map Sheet 5 Metering Data / Power MeteringMetering Data / Temperature Metering Data / Voltage Metering489 Memory Map Sheet 6 489 Memory Map Sheet 7 Maintenance / Trip CountersMaintenance / General Counters Learned Data / Analog in MIN/MAX489 Memory Map Sheet 8 489 Memory Map Sheet 9 Digital Inputs / General Input D 489 Memory Map Sheet 10Digital Inputs / General Input C Digital Inputs / General Input E489 Memory Map Sheet 11 489 Memory Map Sheet 12 489 Memory Map Sheet 13 489 Memory Map Sheet 14 Current Elements / Negative SequenceCurrent Elements / Ground O/C 489 Memory Map Sheet 15 489 Memory Map Sheet 16 Current Elements / Phase DifferentialCurrent Elements / HIGH-SET Phase Overcurrent Current Elements / Ground Directional489 Memory Map Sheet 17 Voltage Elements / Loss of Excitation 489 Memory Map Sheet 18Voltage Elements / Neutral Overvoltage Fundamental Voltage Elements / Distance Element489 Memory Map Sheet 19 489 Memory Map Sheet 20 489 Memory Map Sheet 21 RTD Temperature / RTD SHORT/LOW Temperature RTD Temperature / RTD #12RTD Temperature / Open RTD Sensor Thermal Model / Model Setup489 Memory Map Sheet 23 489 Memory Map Sheet 24 489 Memory Map Sheet 25 489 Memory Map Sheet 26 Analog INPUT/OUTPUT / Analog InputTesting / Simulation Mode Testing / PRE-FAULT Setup489 Memory Map Sheet 27 489 Memory Map Sheet 28 Waveform Memory Setup 489 Memory Map Sheet 29Waveform Memory Samples Decimal Place Code Type DefinitionUnsigned Value Decimal PlacesReset Mode SwitchAlarm / Trip Type ALARM/TRIP StatusParameter Input SwitchAnalog Output Overcurrent CurveData Formats Sheet 7 Switch Status Simulation ModeCurve Reset Type Order CodeBreaker Operation Undervoltage TripElement Type Assignable InputDNP Protocol DNP 3.0 Device Profile Document Default Variations DNP Implementation TableVariation Binary Inputs Sheet 1 Binary Input / Binary01/02 Binary Inputs Sheet 2Binary Inputs Sheet 3 Binary Inputs Sheet 4Binary / Control Relay 10/12Binary Output Point List DNP Point Lists Binary / Frozen Counter Objects 20/21 Counters Point ListAnalog Inputs Point List Sheet 1 Assigned toAnalog Inputs Point List Sheet 2 Impedance angleAnalog Inputs Point List Sheet 3 Analog Inputs Point List Sheet 4 Table NotesIndex GE Multilin