Heatcraft Refrigeration Products 25000102 operation manual Henry Relief Valve Capacity Rating

Page 24

Installation and Operations Manual

Table 17. Henry Relief Valve Capacity Rating

Type

Catalog

Size Connection

 

Standard Pressure Settings PSIG

 

Number

Inlet

Outlet

350

 

400

425

 

450

 

 

 

Angle

526E

3/8 MPT

3/8 FLARE

10.2

 

11.6

12.3

 

13.0

 

 

 

 

 

 

 

 

 

527E

1/2 MPT

5/8 FLARE

28.5

 

32.4

34.4

 

36.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5231

3/8 MPT

3/8 FLARE

11.2

 

12.7

13.5

 

14.3

 

5231-A

3/8 MPT

1/2 FLARE

18.6

 

21.1

22.4

 

23.7

 

 

 

 

 

 

 

 

 

 

 

5231

1/2 MPT

5/8 FLARE

18.6

 

21.1

22.4

 

23.7

 

 

 

 

 

 

 

 

 

 

Straight

5232

1/2 MPT

5/8 FLARE

28.1

 

32.0

33.9

 

35.8

Through

5240-1/2

1/2 MPT

3/4 FPT

41.2

 

46.8

49.1

 

52.5

 

 

 

 

 

 

 

 

 

 

 

5242-3/4

3/4 MPT

3/4 FPT

41.2

 

46.8

49.1

 

52.5

 

 

 

 

 

 

 

 

 

 

 

5244-1

1 MPT

1 FPT

74.0

 

84.2

89.3

 

94.4

 

5246-1-1/4

1-1/4 MPT

1-1/4 FPT

129.7

 

147.5

156.4

 

165.4

 

 

 

 

 

 

 

 

 

 

Table 18. Discharge Piping Table

Maximum Length of Discharge Pipe in Feet

* For 400 PSIG Pressure Setting

Relief Device

Soft Copper Tube (OD)

 

 

Schedule 40 Pipe

 

 

Capacity

 

 

 

 

 

 

 

 

 

3/8”

1/2”

5/8”

1/2”

3/4”

1”

1-1/4”

1-1/2”

2”

Lbs. Air/Min.

 

 

 

 

 

 

 

 

 

10

3-1/2

19-1/4

61

108

445

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

2-1/2

12-1/4

44

75

308

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

2

9-1/2

32

56

228

 

 

 

 

18

 

5-1/4

19-1/4

33

137

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

4-1/4

16

28

110

371

 

 

 

 

 

 

 

 

 

 

 

 

 

25

 

2-1/2

9-1/2

18

72

238

 

 

 

30

 

2

7

12

49

165

 

 

 

 

 

 

 

 

 

 

 

 

 

35

 

2

5-1/4

9

37

121

 

 

 

 

 

 

 

 

 

 

 

 

 

40

 

 

3-1/2

7

28

93

366

 

 

50

 

 

2-1/2

4

18

60

233

 

 

 

 

 

 

 

 

 

 

 

 

70

 

 

 

3

9

30

119

257

 

 

 

 

 

 

 

 

 

 

 

80

 

 

 

2

7

23

91

198

 

90

 

 

 

2

5

18

72

156

 

 

 

 

 

 

 

 

 

 

 

125

 

 

 

 

3

10

37

81

282

 

 

 

 

 

 

 

 

 

 

150

 

 

 

 

2

7

26

56

196

For Relief Devices set at 400 psig

Obtain the capacity at 400 psig setting

Locate this capacity or the nearest larger capacity in the left-hand column of the discharge piping table above and read across to obtain the maximum lengths for each tube and pipe size

For relief devices set at 350 psig, use the above table and multiply by .75 to determine maximum lengths For relief devices set at 425 psig, use the above table and multiply by 1.15 to determine maximum lengths For relief devices set at 450 psig, use the above table and multiply by 1.25 to determine maximum lengths

24

Part # 25000102

Image 24
Contents Parallel Compressor Systems Table of Contents Introduction InspectionUnit Designation Model DefinitionSystem Warranty RiggingLocation Of Equipment Indoor Clearances Floor & Foundation RequirementsLocation of Equipment Outdoor Ground MountingRoof Mounting Unit Vibration IsolationUnit Access Vertical ClearanceDecorative Fences Units in PitsVentilation Requirements Indoor Units ElectricalRefrigerant Piping Suction P-TrapsRefrigerant Line Insulation Refrigerant Line SupportExpansion Loops Table of Values for LRef. Line Amount of Expansion Pressure Loss of Liquid Refrigerants Equivalent Feet of PipeLiquid Line Rise in Feet Refrigerant 10’ 20’ 25’ 30’ 40’ 50’ 75’ 100’Weight of Refrigerants in Copper Lines During Operation Suction Line at Suction TemperatureLine 40F 20F Recommended Line Sizes for R-404A/R-507 Liquid Line Size Expansion ValveLengths 100’ 150’ 200’ 25’Recommended Line Sizes for R-22 Suction Line SizeCapacity 40˚F 20˚F 10˚F Liquid Line Size Suction Temperature 10˚FRecommended Remote Condenser Line Sizes Net12 & R-134A 502 507 & R-404A TotalLeak Checking, Evacuation and Start-up EvacuationStart-up Refrigerant Distribution Off-CycleElectric Defrost Priority I Hot Gas DefrostElectronic Control System System BalancingSystem Superheat Evaporator SuperheatCompressors Copeland Compressors 4D/6D Solid State ModulesTypical Voltage Ranges Unloader FactorsOil Safety Switch Oil ChargesApproved Copeland Lubricants Carlyle CompressorsPhase Voltage Monitor Part Load Performance MultipliersRequired Differential Pressure for Unloader Operation Sight Glass & Moisture Indicator Sight Glass Safety Relief DevicesHenry Relief Valve Capacity Rating Discharge Piping TableAuto Reset Models Manual Reset ModelsLiquid Level Switch Level Switch TableModule Replacement Oil ControlOil Separators Temprite Valve Adjustment Temprite ModelsOil Level Regulators Troubleshooting Oil System AC&R Model RegulatorsLiquid Filter-Driers & Suction Filters Sporlan Valve CoCompressorMotorBurnoutCleanupProcedure Suction FilterSporlan Valve Company Replaceable Suction FilterType DF for cleanup Type AFD for cleanupSuperior Valve Company Type F FilterRecommended Valve Settings Field AdjustmentHot Gas Bypass Regulator Adjustment Liquid Drain Control MethodControl Settings Control Settings for R-404A/R-507Control Settings for R-22 Low Pressure Switch Setting for RmccGeneral Maintenance Schedule WeeklyMonthly QuarterlySymptom Cause Remedy Compressor TemperatureDoes Not Run Unit ShortSymptom Cause Remedy Low Switch OpenHigh Suction Low SuctionService Record System Reference Data