Heatcraft Refrigeration Products 25000102 Temprite Valve Adjustment, Temprite Models

Page 27

Parallel Compressor Systems

to the compressor.

Before the oil separator is installed, an initial charge of oil must be added to it. This initial charge of oil is the amount that is needed to just float the needle valve float. This amount of oil will stay in the oil separator when in operation and will seal the needle and prevent damage to the float mechanism. Oil Precharge is very important. Failure to Precharge the separator sump may result in damage to the oil return float mechanism by the turbulent hot gas bouncing the float and causing the needle valve to leak.

New systems from the factory have been Precharged. Use the same type of oil that is in the compressor crankcase.

See the table below for the proper amount of oil to be Precharged.

Temprite Valve Adjustment

Turn in (clockwise) to increase pressure. Turn out (counterclockwise) to decrease pressure. Approximately 7 psi per turn. Factory set at 40 psi ±2.

Table 21. Temprite Models

Temprite Model

 

No.

Oil Precharge

922R, 923R

77 oz. / 2.2 L

 

 

924R , 925R

109 oz. / 3.22 L

 

 

926R, 927R

1.8 gal./ 6.7 L

928R

3.5 gal. / 13.25 L

 

 

930R

5.7 gal . / 21.25 L

 

 

Figure 17. Temprite Oil System

Table 20. AC&R Models

Helical

Oil

Model No.

Precharge

S-5180, S-5181

4 oz. / 11 cl

S-5182, 85, 87, 88

14 oz. / 40 cl

 

 

S-5190, 92, 94

40 oz. / 114 cl

 

 

S-5200 / S-5410 series

25 oz. / 71 cl

Conventional

Oil

Model No.

Precharge

S-5500 series

12 oz. / 34 cl

S-5600 series

30 oz. / 86 cl

 

 

S-1900, S-5700 series

25 oz. / 71 cl

 

 

S-5800 series

12 oz. / 34 cl

Temprite Models

The Temprite brand used is the coalescent filter type separator. Because this filter is finer than a filter/drier, it will pick up any and all effluent and dirt circulating in the system down to 0.3 microns. These filters should be changed after 24 to 48 hours of initial run time. A second filter is supplied with the system for this purpose. If the filter becomes dirty, it will not function at its optimum performance level. In the event of a compressor burnout, all the effluent will be contained in the oil separator.

When the Temprite coalescent separator is used, the separate oil reservoir is not required. The oil separator serves the additional function as the reservoir. There is a constant pressure valve used between the oil return outlet and the oil level regulators to maintain a low pressure oil flow to the regulators. This valve should be adjusted to maintain oil pressure to the level regulators at 20 psig higher than the highest suction pressure group. This valve can be adjusted by removing the external cap and rotating the adjusting spring in or out as required.

The valve currently used is manufactured by Parker and is a model A7 constant pressure expansion valve with a range of 0 to 90 psig. Temprite Part No. is 67070000. An alternative valve manufactured by Sporlan is Model ADRI - 11/4 - 0/90.

Oil Level Regulators

The AC&R adjustable oil regulators are designed to feed oil between 1/4 and 5/8 sight glass levels. The regulator may adjust beyond this range due to the actual oil pressure. Adjustable regulators include an adjustment mechanism to raise or lower the oil set point. The AC&R design eliminates the need to shut the system down in order to adjust the oil level. The oil level may be adjusted while the system is under pressure and running. Adjust the oil level by removing the seal cap, the locking disk (S-9130 & S-9190 series only), and rotating the adjustment clockwise to lower, counter clockwise to raise the oil level. Replace the cap and locking disk when done. Each full turn of the adjustment mechanism moves the oil level approximately 1/16”. Oil levels on these regulators are typically factory set just below 1/2 sight glass.

All level regulators have a operating pressure differential range that should not be confused with its working pressure. The operating differential is the difference of pressure between the oil feeding into the regulator and the component where the regulator is controlling oil level. Specifically, the reservoir pressure minus the crankcase pressure. If the differential pressure is too low for that regulator, insufficient oil flow to the compressor may result. If the differential pressure is too high, the regulator will overfill.

Parallel Compressor Systems Installation & Operations Manual, October 2004

27

Image 27
Contents Parallel Compressor Systems Table of Contents Model Definition IntroductionInspection Unit DesignationFloor & Foundation Requirements System WarrantyRigging Location Of Equipment Indoor ClearancesUnit Vibration Isolation Location of Equipment OutdoorGround Mounting Roof MountingUnits in Pits Unit AccessVertical Clearance Decorative FencesSuction P-Traps Ventilation Requirements Indoor UnitsElectrical Refrigerant PipingRefrigerant Line Support Refrigerant Line InsulationExpansion Loops Table of Values for LRef. Line Amount of Expansion 20’ 25’ 30’ 40’ 50’ 75’ 100’ Pressure Loss of Liquid RefrigerantsEquivalent Feet of Pipe Liquid Line Rise in Feet Refrigerant 10’Weight of Refrigerants in Copper Lines During Operation Suction Line at Suction TemperatureLine 40F 20F Recommended Line Sizes for R-404A/R-507 100’ 150’ 200’ 25’ Liquid Line SizeExpansion Valve LengthsRecommended Line Sizes for R-22 Suction Line SizeCapacity 40˚F 20˚F 10˚F 10˚F Liquid Line Size Suction TemperatureTotal Recommended Remote Condenser Line SizesNet 12 & R-134A 502 507 & R-404ALeak Checking, Evacuation and Start-up EvacuationStart-up Priority I Hot Gas Defrost Refrigerant DistributionOff-Cycle Electric DefrostEvaporator Superheat Electronic Control SystemSystem Balancing System SuperheatUnloader Factors CompressorsCopeland Compressors 4D/6D Solid State Modules Typical Voltage RangesCarlyle Compressors Oil Safety SwitchOil Charges Approved Copeland LubricantsPhase Voltage Monitor Part Load Performance MultipliersRequired Differential Pressure for Unloader Operation Sight Glass Safety Relief Devices Sight Glass & Moisture IndicatorDischarge Piping Table Henry Relief Valve Capacity RatingLevel Switch Table Auto Reset ModelsManual Reset Models Liquid Level SwitchModule Replacement Oil ControlOil Separators Temprite Valve Adjustment Temprite ModelsOil Level Regulators Sporlan Valve Co Troubleshooting Oil SystemAC&R Model Regulators Liquid Filter-Driers & Suction FiltersReplaceable Suction Filter CompressorMotorBurnoutCleanupProcedureSuction Filter Sporlan Valve CompanyType F Filter Type DF for cleanupType AFD for cleanup Superior Valve CompanyLiquid Drain Control Method Recommended Valve SettingsField Adjustment Hot Gas Bypass Regulator AdjustmentLow Pressure Switch Setting for Rmcc Control SettingsControl Settings for R-404A/R-507 Control Settings for R-22Quarterly General Maintenance ScheduleWeekly MonthlyUnit Short Symptom Cause Remedy CompressorTemperature Does Not RunLow Suction Symptom Cause Remedy LowSwitch Open High SuctionSystem Reference Data Service Record