TABLE 2
| Model | Heater kW | Power Cord Kit | Voltage | Amperage | Receptacle |
| PDE07K | 0.0 | PXPC23000 | 230/208 | 15 | NEMA |
| PDE/PDH07K | 2.0 | PXPC23015 | 230/208 | 15 | NEMA |
|
| 3.0 | STD | 230/208 | 20 | NEMA |
| PDE09K | 0.0 | PXPC23000 | 230/208 | 15 | NEMA |
| PDE/PDH09K | 2.0 | PXPC23015 | 230/208 | 15 | NEMA |
|
| 3.0 | STD | 230/208 | 20 | NEMA |
|
| 5.0 | PXPC23030 | 230/208 | 30 | NEMA |
| PDE12K | 0.0 | PXPC23000 | 230/208 | 15 | NEMA |
| PDE/PDH12K | 2.0 | PXPC23015 | 230/208 | 15 | NEMA |
|
| 3.0 | STD | 230/208 | 20 | NEMA |
|
| 5.0 | PXPC23030 | 230/208 | 30 | NEMA |
| PDE15K | 0.0 | PXPC23000 | 230/208 | 15 | NEMA |
| PDE/PDH15K | 2.0 | PXPC23015 | 230/208 | 15 | NEMA |
|
| 3.0 | PXPC23020 | 230/208 | 20 | NEMA |
|
| 5.0 | STD | 230/208 | 30 | NEMA |
| PDE/PDH07R | 2.0 | PXPC26515 | 265 | 15 | NEMA |
|
| 3.0 | STD | 265 | 20 | NEMA |
| PDE/PDH09R | 2.0 | PXPC26515 | 265 | 15 | NEMA |
|
| 3.0 | STD | 265 | 20 | NEMA |
|
| 5.0 | PXPC26530 | 265 | 30 | NEMA |
| PDE/PDH12R | 2.0 | PXPC26515 | 265 | 15 | NEMA |
|
| 3.0 | STD | 265 | 20 | NEMA |
|
| 5.0 | PXPC26530 | 265 | 30 | NEMA |
| PDE/PDH15R | 2.0 | PXPC26515 | 265 | 15 | NEMA |
|
| 3.0 | PXPC26520 | 265 | 20 | NEMA |
|
| 5.0 | STD | 265 | 30 | NEMA |
Electrical Wiring for 265 Volt Models
Power Cord Installation
All 265V PTAC/PTHP units come with a factory installed
NOTE: It is recommended that the PXSB subbase assembly, the PXCJA conduit kit (or equivalent) be installed on all hardwire units. If installing a
To install the line voltage power leads and conduit to chassis, follow the instructions below and refer to Figures
1.Follow the removal process of the chassis’s junction box
(Figure 25, step 2, page 19).
2.Prepare the 265V (or 230V) power cord for connection to the chas- sis’ power cord connector by cutting the cord to the appropriate length (refer to Figure 26 and follow Figure 15). Power cord harness selection shown on Table 2 on page 14.
WARNING
Electrical Shock Hazard
Turn off electrical power before service or installation.
ALL electrical connections and wiring MUST be installed by a qualified electrician and conform to the National Code and all local codes which have jurisdiction.
Failure to do so can result in property damage, personal injury and/or death.
14