Digital Control User Input Configuration
The adjustable control dip switches are located at the lower left hand portion of the digital Smart Center. The inputs are only visible and accessible with the front cover removed from the PTAC.
Dip Switch Setting
1.Emergency Heat Override – Switch 1
In the unlikely event of a compressor failure a heat pump unit may be switched to operate in only the electric heat mode until repairs can be made. Moving Dip Switch 1 to ‘ON’.
2.Wall Thermostat Switch 2
In order to enable the wall thermostat move Dip Switch to 'ON'.
3.Fan Cycle Control – Switch 3-4
All PTACs are shipped from the factory with Dip Switch
4.Electronic Temperature Limiting – Switches 5-6
The digital control is set from the factory to allow a temperature range between 61° F and 86° F in both heating and cooling mode. Dip Switches
From the factory switches are in the down 'OFF' position. The chart below shows the available electronic limiting ranges.
5.Room Freeze Protection – Switch 7
Units are shipped from the factory with the room freeze protection enabled. Room Freeze Protection can be switched off at the owner’s preference by moving Dip Switch 7 to ‘OFF’. This feature will monitor the indoor room conditions and in the event that the room falls below 40°F the unit will cycle on high fan with the electric heater. This occurs regardless of mode.
Figure 31
Dip Switches
DIP SWITCH
UP
1 2 3 4 5 6 7 DOWN
|
|
|
|
| LOCATION OF |
|
|
|
| |||
|
|
| Freeze guard |
| DIP SWITCHES |
|
|
|
| |||
|
|
|
| ON UNIT |
|
|
|
|
| |||
|
|
| Setpoint Limit 2 |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
| Setpoint Limit 1 |
|
|
|
|
|
|
|
|
|
|
|
| Fan CON/CYC for cooling |
|
|
|
|
|
| |||
|
|
| Fan CON/CYC for heating |
|
|
|
|
|
| |||
|
|
| Wall Thermostat enable |
|
|
|
|
|
|
|
| |
|
|
| Electric heat only (for Heat Pumps) |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| FRP028 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Switch | Description | Function | Factory Setting |
|
| Option |
|
|
| ||
| 1 | Emergency Heat Override | Enables electric heat only operation in the event of a com- | Down - Normal Operation |
| Up - Overrides compressor operation. | ||||||
|
| for PDH Heat Pump | pressor failure on HP models. |
|
|
|
|
| (PDH models only) |
|
| |
|
| Models |
|
|
|
|
|
|
|
|
|
|
| 2 | Wall Thermostat Switch | Enables the use of a wall thermostat or unit controls | Down - Unit Controls |
|
| Up - Enables Wall Thermostat Usage | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| 3 | Fan Cycle for Heating | Allows selection of continuous fan or cycling in heating mode. | Down - Cycle |
|
| Up - Continuous |
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| 4 | Fan Cycle for Cooling | Allows selection of continuous fan or cycling in cooling mode. | Down - Continuous |
|
| Up - Cycle |
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| 5 | Setpoint Switch 1 | Allows the temperature setpoint range to be adjusted. | Down |
| Up | Down | Up | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| 6 | Setpoint Switch 2 |
| Down |
| Down | Up | Up | ||||
|
|
|
|
|
|
|
|
|
|
|
| |
| 7 | Room Freeze Protection | Allows the unit to ensure the indoor room temperature does | Down - Freeze Protection Enabled | Up - Freeze Protection Disabled | |||||||
|
|
| not fall below 40F even when turned off. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|