Friedrich 920-087-09 Wall Sleeve Installation Instructions Pdxws, Falling Object Hazard

Page 8

Wall Sleeve Installation Instructions (PDXWS)

NOTE: Insure that the unit is only installed in a wall structurally adequate to support the unit including the sleeve, chassis and accessories. If the sleeve projects more than 8" into the room, a subbase or other means of support MUST be used. Please read these instructions completely before attempting installation.

WARNING

Falling Object Hazard

Not following Installation Instructions for mounting your air conditioner can result in property damage, injury, or death.

NOTICE

DO NOT allow any pitch toward the inside.

Flashing on all 4 sides of the opening is recommended.

Potential property damage can occur if instructions are not followed.

For Deep Wall Installation (Greater than 13 1/4") See Page 9

The following instructions apply ONLY to walls less than 13 ¼" in depth.

1.The PXDR10 Drain Kit (optional for new construction) see page 10 if applicable, must be installed before the wall sleeve is installed into the wall.

2.The External Drain (for new construction or unit replacement) see page 11, if applicable, must be installed before the wall sleeve is installed into the wall.

Figure 3

Typical Wall Sleeve Installation

LINTEL TO SUPPORT

42-¼"

MIN.

MASONRY WALLS

 

3.From inside the building, position the wall sleeve in the opening and push it into the wall until it protrudes at least ¼” on the outside. Do not allow sleeve to be pulled. (See Figure 11, Page 10).

4.Position the wall sleeve with a slight tilt towards the outside to facilitate condensate drainage. It should be level side-to-side and the front should be ¼ bubble higher than the back.

ELECTRICAL

RECEPTACLE

16-¼"

60"

 

 

MAX.

 

20" MAX.

13-¾"

SMOOTH SIDE OF SCREW CLIP FACING INTO ROOM

ELECTRICAL

INSULATION

RECEPTACLE

WALL OPENING

WALL SLEEVE

INSULATION

NOTE: All 230/208V units are manufactured with a 60” power cord and all 265V units with a18 ” power cord.

FRP008

6

Image 8
Contents Ptac Page Table of Contents Page General Instructions Read Installation Operation ManualCongratulations General Specifications Installation ChecklistPtac Installation Recommendations Typical Building Plan ViewWall Sleeve Installation Instructions Pdxws For Deep Wall Installation Greater than 13 1/4 SeeTypical Wall Sleeve Installation Falling Object HazardAlternate Wall Installations Panel WallFrame and Brick Veneer Curtain WallDimensions Wall Sleeve AttachmentOne-Piece Deep Wall Sleeve Installation Pdxwsext Lintel InstallationDrain Kit Location and Installation Internal DrainDrain Kit Installation Cover Plate InstallationDrain Tube Installation See Figure Pxga Standard Grille Installation Instructions Standard GrilleElectrical Rating Tables Power Cord Information 230/208V models onlyAll 230/208 volt units are equipped with power cords Electrical Shock Hazard Electrical Wiring for 265 Volt ModelsPower Cord Installation To Chassis Junction Chassis Install Preparation Suffocation HazardsShipping Screw Location Unit Damage HazardShipping Tape Location Securing Unit Chassis InstallationExcessive Weight Hazard How To Connect Power ConnectionFriedrich Ptac Digital Control and Unit Features Page System Configuration Dip Switches Digital Control User Input ConfigurationDip Switch Setting Digital Control Operation Remote Control Thermostat Installation Desk Control Terminals Energy ManagementRoutine Maintenance Basic Troubleshooting Complaint Cause SolutionService & Assistance Accessories New Construction AccessoriesPxcja Room AIR Conditioners Limited Warranty Page 66129906249