PTAC Installation Recommendations
For proper PTAC unit performance and maximum operating life refer to the minimum installation clearances below:
Figure 1
PTAC units should be installed no closer than 12" apart when two units are side by side. If three or more PTAC units are to operate next to one another allow a minimum of 36" between units. Also, a vertical clearance of 60" should be maintained between units installed. In the interior of the room the unit should be located a minimum of 1/4" from the floor and a minimum of 36" from the ceiling.
60" VERTICAL MIMUMUM BETWEEN PTACs
THREE OR MORE PTACs
ADJACENT 36" MINIMUM
TYPICAL
WINDOW
36"
60" | TWO ADJACENT PTACs | |
12" MINIMUM | ||
| ||
| GROUND FLOOR PTACs | |
| 6" MINIMUM FROM GRADE |
12" 6"
VIEW: OUTSIDE BUILDING ELEVATION
FRP001
For PTACs on the ground floor or anytime obstructions are present, use the following guidelines:
Figure 2
• | For minor obstructions |
| such as lamp poles or small |
| shrubbery a clearance of |
| 12" from the outdoor louver |
| should be maintained. |
• | For major obstructions such |
TYPICAL BUILDING ( PLAN VIEW )
as a solid fence, wall or |
other heat rejecting device |
like a condensing unit, a |
minimum distance of 36" |
should be kept. |
| 36" |
| 36" |
PTAC |
| PTAC |
|
|
| 12" |
|
12" MINIMUM, MINOR | POLE | 36" | SHRUB |
| |||
OBSTRUCTIONS |
|
|
|
36" MIMUMUM, MAJOR |
|
|
|
OBSTRUCTIONS |
| FENCE OR WALL |
CONDENSING UNIT
PTAC
FRP002
The above suggestions are for reference only and do not represent all possible installations. Please contact Friedrich for information regarding affects of other installation arrangements. By following these simple recommendations you can be confident that your Friedrich PTAC will provide years of worry free operation.