SEQUENCE OF OPERATIONS
(For serial numbers before 2038616 w/ analog control)
MODEL | NAT. GAS | 230 VAC | 50 HZ. | 1 PHASE |
MODEL | LP GAS | 230 VAC | 50 HZ. | 1 PHASE |
POWER SUPPLY
Electrical power to be supplied to the oven by a three conductor service.
CONTROL BOX AUTO COOL DOWN
When the temperature in the control box reaches 120° F, ± 3° (48.9°C, ± 1.7°C), the cooling fan thermostat will switch power to the control box cooling fan. The thermostat will interrupt power to the cooling fan when the control
box temperature falls to 100° F, ± 3° (37.8°C, ± 1.7°C).
MAIN FAN CIRCUIT
Power is permanently supplied through the 10A oven fuse, through the normally closed control box
BURNER CIRCUIT
Closing the oven fan switch supplies line voltage through the normally open gas pressure switch (located in the gas valve and closed when gas pressure is present), through the normally open air pressure switch (closed by air pressure from the main fan), through the normally closed oven cavity
IGNITION CONTROL
The ignition control switches line voltage to the combustion blower motor, the combustion air switch switches from normally closed to normally open upon sensing air pressure in the burner housing. After a
TEMPERATURE CONTROL
Closing the oven fan switch supplies line voltage to the temperature control. The 1K ohm temperature pot. is adjusted to desired temperature. The thermocouple will provide varying millivolts to the temperature control. The temperature control supplies line voltage to the temperature regulation valve at intermittent intervals to maintain desired temperature. The heat lamp is energized with the temperature regulation valve.
CONVEYOR DRIVE
Closing the oven fan switch supplies line voltage to the motor control board. AC volts are converted to DC volts and are supplied to the conveyor motor at terminals A+ and
NOTE: The conveyor control uses a sensor and magnet, mounted on the conveyor motor, that senses the motor
speed. Any change in motor load (± RPM) is detected by the sensor and the voltage to the motor is adjusted accordingly.
TEMPERATURE DISPLAY
Closing the switch supplies line voltage to primary of the temperature display transformer. The secondary of this transformer supplies 12VAC to the temperature display. The thermocouple supplies DC millivolts to the temperature display. The display converts this millivolt reading to a temperature reading.
2 | Impinger II – |