Energy Tech Laboratories Modular Direct Fired Heaters manual Main Burner Adjustment

Page 11
Maxitrol MR212 Low
Fire Bypass Screw
Maxitrol M511 and M611 Low Fire Bypass Screw
Firing Mode
Low Fire
Modulation
High Fire
Volts DC
0 to 5 VDC
5 to 15 VDC
15 to 20 VDC
Mod Valve Voltage Summary

Main Burner Adjustment

1. Once the pilot has been properly established, the manifold gas pressure or temperature rise should be adjusted to jobsite conditions. The gas pressure regulator (integral to the combination gas control on size

1-3 heaters and located in the modulating valve on size 4-5 heaters) is adjusted at the factory for average gas

conditions. It is important that the gas be supplied to the burner in accordance with the input rating on the rating plate.

2. Create a high fire call for heat. This should be done with the blower on and all gas controls on. High fire can be achieved by removing the wire at terminal #4 (remove wires #2 and #4 for Maxitrol 44 systems) from the Maxitrol 14 amplifier.

3. The manifold pressure should be checked

 

 

Average Manifold Pressure vs. Firing Rate/Ft. of Burner

 

at the pressure tap downstream of the

 

 

 

 

6.00

 

 

 

 

 

 

modulating valve. The graph to the right

 

 

 

 

 

 

 

 

indicates the proper manifold pressure for

 

5.00

 

 

 

 

 

 

the desired amount of BTUs per foot of

(in. w.c.)

 

Natural Gas

Propane Gas

 

 

 

burner. For natural gas systems, the high

4.00

 

 

 

 

 

 

 

 

 

 

 

 

 

fire manifold pressure should not exceed 5

3.00

 

 

 

 

 

 

in. w.c. For propane gas, the high fire

Pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

manifold pressure should not exceed 2.5

2.00

 

 

 

 

 

 

in. w.c. Another method of checking high

Manifold

 

 

 

 

 

 

 

fire is to measure the temperature rise of

1.00

 

 

 

 

 

 

the unit. The temperature rise should be

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

set to design conditions and typically is

 

0.00

 

 

 

 

 

 

minimum 70°F.

 

 

 

 

 

 

 

 

4. Remove the cap from the combination gas

 

-1.00

 

 

 

 

 

 

 

0

100000

200000

300000

400000

500000

600000

valve regulator adjustment (size 1-3) or

 

 

Firing Rate (BTU/Hr/Ft. of Burner)

 

 

the cap from the MR212 valve (size 4-5).

Using the regulator pressure adjusting screw, adjust the high fire manifold pressure to 5 in. w.c. maximum for natural gas and 2.5 in. w.c. maximum for propane gas. High fire should be set to generate the desired temperature rise. If the high fire screw is at the end of its adjustment and more pressure is needed, then adjust the main building gas pressure regulator spring (located external to the unit) to achieve the proper manifold pressure. Turning the regulator screw clockwise will increase pressure and counter-clockwise will decrease pressure. Remember -

The high fire DC voltage should read 12 VDC minimum and should typically be 15 VDC on the Flame Safety Controller test jacks.

5.Reconnect the wire on the Maxitrol 14 amplifier at terminal #4 (wires #2 and #4 for Maxitrol 44).

6.The low fire manifold pressure must now be set. Low fire can be achieved

by removing the wire at terminal #5 from the Maxitrol 14 amplifier (remove #8 for Maxitrol 44). Check the low fire flame signal to ensure that the DC voltage is 12 VDC minimum on the Flame Safety Controller test jacks.

7.Using the bypass screw (located on the side of the M511 and M611 valves, and under the cap of the MR212 valve), adjust low the low fire manifold pressure until there is a very thin flame along the entire length of the burner. No dark spots should be seen in the burner. The burner may be observed through the view-port located on the external wall of the heater. Replace the cap to the Maxitrol valve and restore all of the original wiring on the

Maxitrol amplifier and gas components.

8. A final gas leak check shall be performed to verify the gas-tightness of the heater’s components and piping under normal operating conditions. This can be done by measuring the gas pressure at the ¼” gas plug just downstream of the modulating valve.

11

Image 11
Contents Installation, Operation, and Maintenance Manual Table of Contents Warranty Site Preparation InstallationAssembly MechanicalRecommended Supply Ductwork Sizes Roof Mount Installation Installation with Exhaust FanPage Gas Pressure Table GasGas Connection Sizes Motorized Intake Damper Copper Wire AmpacityElectrical Fan to Building Wiring Connection Remote Control PanelStart Up OperationMain Burner Adjustment Heater Start Up Summary Yes Adjust pilot flame Lock unit into High fireSetscrew Torque Final Start Up ProcedureMaximum RPM and HP Chart Pulley Adjustment Illustration Pulley Adjustment10 20 IN. Blower Pulley Combination ChartSequence of Operation Flame Safety ControlFlame Safety Controller DC Flame Signal Air Flow SwitchOperation Summary Maxitrol Amplifier High Temperature LimitModulating Gas System Optional Remote Panel Circuit Blower SwitchComponents Remote Panel Option Airflow Troubleshooting Chart TroubleshootingProper Spark Gap Burner Troubleshooting ChartLight Indication Condition Possible Cause Remote Panel Troubleshooting ChartNothing Happens Troubleshooting FlowchartsFlame Safety Service Guide Flame Safety Service Guide General Maintenance MaintenanceYearly Filter Quantity ChartWeeks after startup Every 3 monthsJob Information Start-Up and Maintenance DocumentationMaintenance Record Factory Service Department

Modular Direct Fired Heaters specifications

Energy Tech Laboratories has established itself as a leader in the development of innovative modular direct fired heaters, designed to meet the evolving demands of industries that require efficient and effective heating solutions. These heaters are engineered to offer versatility, reliability, and enhanced performance, making them suitable for a broad range of applications.

One of the standout features of Energy Tech Laboratories' modular direct fired heaters is their modular design. This allows for easy scalability and customization, enabling users to adjust the heating capacity according to specific requirements. The modular aspect also facilitates straightforward installation and maintenance, reducing downtime and operational costs.

The heaters utilize advanced combustion technology that optimizes fuel consumption while minimizing emissions. This ensures not only a cost-effective operation but also compliance with environmental regulations. By combining high thermal efficiency with a low carbon footprint, these heaters contribute to sustainable energy practices.

In addition to their efficient combustion system, Energy Tech Laboratories incorporates state-of-the-art control technologies in their heaters. These systems allow for precise temperature regulation and can be integrated with existing Building Management Systems (BMS) for enhanced monitoring and control. Users can benefit from real-time data and analytics, which help in diagnosing potential issues and optimizing performance.

Durability is another characteristic that sets these heaters apart. Constructed with high-quality materials, they are designed to withstand harsh industrial conditions, ensuring a long service life. The robust design minimizes the likelihood of breakdowns, which is critical for industries that rely on continuous operation.

Moreover, Energy Tech Laboratories emphasizes safety in the design of their modular direct fired heaters. Equipped with multiple safety features such as flame detection, gas leak detection, and emergency shutdown systems, these heaters are built to operate within stringent safety standards.

The flexibility of these heaters makes them suitable for various sectors, including oil and gas, manufacturing, and construction. Their ability to provide direct heat quickly and efficiently makes them ideal for processes that require consistent temperature control.

In conclusion, Energy Tech Laboratories' modular direct fired heaters represent an advanced solution for today’s energy needs. With their modular design, advanced combustion technologies, and focus on safety and durability, these heaters stand out as a preferred choice for industries seeking reliable and efficient heating solutions. Their commitment to innovation and sustainability positions them as a front-runner in the energy technology sector.