Bryant 607C-A A Wet Coil Pressure Drop in. W.C, Filter Pressure Drop Table in. W.C

Page 22

607C-- -- A

Table 4 – Dry Coil Air Delivery CFM* - Horizontal and Downflow Discharge - Unit 607--A24-60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit

Motor Speed

Wire Color

 

 

 

 

External Static Pressure (in W.C)

 

 

 

 

 

0.1

0.2

0.3

0.4

 

0.5

0.6

 

0.7

0.8

0.9

 

 

 

 

 

 

 

Low

Blue

cfm

754

650

536

 

429

 

---

---

 

---

---

---

 

Med-Low

Pink

cfm

851

777

675

 

591

 

475

---

 

---

---

---

607----A24

Medium1

Red

cfm

 

 

774

 

 

 

 

 

 

 

 

 

941

851

 

684

 

576

479

 

---

---

---

 

Med-High

Orange

cfm

1009

917

840

 

759

 

667

577

 

447

---

---

 

High

Black

cfm

1241

1167

1111

 

1036

 

969

881

 

818

731

640

 

Low

Blue

cfm

741

638

547

 

415

 

---

---

 

---

---

---

607----A30

Med-Low

Pink

cfm

973

887

823

 

733

 

665

538

 

451

---

---

Medium

Red

cfm

1088

1023

954

 

881

 

800

723

 

658

563

461

 

Med-High1

Orange

cfm

1140

1064

996

915

 

840

758

 

687

564

480

 

High

Black

cfm

1202

1140

1082

 

1015

 

961

881

 

810

732

631

 

Low

Blue

cfm

1176

1121

1079

 

1019

 

974

920

 

877

826

754

 

Med-Low

Pink

cfm

1295

1234

1182

1126

 

1075

1016

 

955

898

857

607----A36

Medium1

Red

cfm

 

 

 

 

1194

 

1140

1095

 

 

 

 

1345

1282

1235

 

 

 

1027

974

921

 

Med-High

Orange

cfm

1505

1452

1413

 

1358

 

1323

1282

 

1234

1169

1130

 

High

Black

cfm

1705

1643

1607

 

1568

 

1518

1483

 

1448

1404

1360

 

Low

Blue

cfm

1295

1234

1182

 

1126

 

1075

1016

 

955

898

857

607----A42

Med-Low

Pink

cfm

1345

1282

1235

1194

 

1140

1095

 

1027

974

921

Medium

Red

cfm

1505

1452

1413

 

1358

 

1323

1282

 

1234

1169

1130

 

Med-High1

Orange

cfm

 

 

 

 

 

 

1362

1313

 

1278

1231

1188

 

1545

1492

1449

 

1411

 

 

 

High

Black

cfm

1705

1643

1607

 

1568

 

1518

1483

 

1448

1404

1360

 

Low

Blue

cfm

1430

1374

1327

 

1267

 

1223

1176

 

1127

1061

1016

 

Med-Low

Pink

cfm

1445

1389

1341

 

1281

 

1236

1189

 

1139

1072

1027

607----A48

Medium1

Red

cfm

 

 

 

 

1558

 

 

 

 

 

 

 

1678

1635

1602

 

 

1513

1474

 

1438

1404

1349

 

Med-High

Orange

cfm

2131

2088

2065

 

2013

 

1982

1941

 

1888

1860

1785

 

High

Black

cfm

2461

2409

2339

 

2286

 

2192

2140

 

2062

1968

1874

 

Low

Blue

cfm

1445

1389

1341

 

1281

 

1236

1189

 

1139

1072

1027

 

Med-Low

Pink

cfm

1678

1635

1602

 

1558

 

1513

1474

 

1438

1404

1349

607----A60

Medium1

Red

cfm

 

 

 

 

 

 

 

 

 

 

 

 

1962

1915

1880

 

1843

 

1794

1753

 

1711

1675

1628

 

Med-High

Orange

cfm

2131

2088

2065

 

2013

 

1982

1941

 

1888

1860

1785

 

High

Black

cfm

2461

2409

2339

 

2286

 

2192

2140

 

2062

1968

1874

*Air delivery values are without air filter and are for dry coil (See 607--- ---A Wet Coil Pressure Drop Table).

1 Factory ---shipped cooling/heat pump heating speed

NOTE: Deduct field---supplied air filter pressure drop and wet coil pressure drop to obtain external static pressure available for ducting. Shaded areas indicate speed/static combinations that are not permitted for dehumidification speed.

Table 5 – 607--A Wet Coil Pressure Drop (in. W.C.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT SIZE

 

 

 

 

 

 

STANDARD CFM (S.C.F.M)

 

 

 

 

 

 

 

500

600

700

800

900

1000

1100

1200

1300

1400

1500

1600

1700

1800

1900

2000

24

 

0.06

0.07

0.08

0.09

0.1

 

 

 

 

 

 

 

 

 

 

30

 

 

 

0.12

0.15

0.19

0.23

0.27

 

 

 

 

 

 

 

 

36

 

 

 

 

 

0.07

0.11

0.18

0.26

0.35

 

 

 

 

 

 

42

 

 

 

 

 

 

 

0.04

0.07

0.10

0.15

0.21

 

 

 

 

48

 

 

 

 

 

 

 

 

 

0.11

0.14

0.17

0.22

0.28

 

 

60

 

 

 

 

 

 

 

 

 

 

 

0.10

0.17

0.23

0.31

0.36

Table 6 – Wet Coil Air Delivery (CFM) - Downflow - High Speed with 1-in. (25 mm) Filter and Economizer

 

 

 

 

 

 

 

 

 

 

 

UNIT SIZE

 

 

 

EXTERNAL STATIC PRESSURE (in. W.C.)

 

 

 

 

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

36, 42

1612

1569

1527

1481

1451

1393

1351

1317

1278

1242

48

2298

2239

2180

2110

2044

1951

1862

1777

1697

1591

60

2298

2239

2180

2110

2044

1951

1862

1777

1697

1591

Table 7 – Filter Pressure Drop Table (in. W.C.)

FILTER SIZE

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

in. (mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

600

700

800

900

1000

1100

1200

1300

1400

1500

1600

1700

1800

1900

2000

2100

2200

2300

20X20X1

0.05

0.07

0.08

0.1

0.12

0.13

0.14

0.15

(508X508X25)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20X24X1

.09

.10

.11

.13

.14

.15

.16

(508X610x25)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24X30X1

0.04

0.05

0.06

0.07

0.07

0.08

0.09

0.10

(610X762x25)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24X36X1

0.06

0.07

0.07

0.08

0.09

0.09

0.10

0.11

0.12

0.13

0.14

0.14

(610X914X25)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 8 – Electric Heat Pressure Drop Table (in. W.C.)

Small Cabinet: 24-36 CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STATIC

 

 

 

 

 

 

CFM

 

 

 

 

 

 

500

600

700

800

900

1000

 

1100

1200

1300

1400

1500

1600

5kw

0.00

0.00

0.00

0.00

0.00

0.00

 

0.00

0.00

0.02

0.04

0.06

0.07

7.5 kw

0.00

0.00

0.00

0.00

0.00

0.00

 

0.02

0.03

0.05

0.07

0.08

0.09

10 kw

0.00

0.00

0.00

0.00

0.00

0.02

 

0.04

0.06

0.07

0.09

0.10

0.11

15 kw

0.00

0.00

0.00

0.02

0.04

0.06

 

0.08

0.10

0.12

0.14

0.16

0.18

20 kw

0.00

0.00

0.02

0.04

0.06

0.08

 

0.09

0.11

0.13

0.15

0.17

0.19

Electric Heat Pressure Drop Table (in. W.C.)

Large Cabinet 42-60 CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STATIC

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

1100

1200

1300

1400

1500

1600

1700

1800

1900

2000

2100

2200

2300

2400

2500

5kw

0.00

0.00

0.00

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.11

0.12

7.5 kw

0.00

0.00

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.13

10 kw

0.00

0.00

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.13

15 kw

0.00

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.13

0.14

0.15

20 kw

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.13

0.14

0.15

0.16

22

Image 22
Contents Table of Contents Safety ConsiderationsCheck Equipment Receiving and InstallationIntroduction Provide Unit Support607--A24-30 Unit Dimensions 607--A36-60 Unit Dimensions SMALL/COMMON Curb Rigging/Lifting of Unit See Fig Rig and Place UnitInspection Unit Falling HazardSelect and Install Ductwork Personal Injury and Electrical Operation HazardHigh-Voltage Connections Install Electrical ConnectionsProvide for Condensate Disposal Unit Component Damage HazardStandard Connections Accessory Electric Heaters InstallationSpecial Procedures for 208-V Operation Transformer ProtectionCondensate Trap Physical Data Unit 607--A Minimum Airflow for Reliable Electric Heater Operation CFMConnection Wiring Schematics 208/230-1-60 Cont. Ladder Wiring Schematics 208/230-1-60 607C a Cont. Ladder Wiring Schematics 208/230-3-60 Connection Wiring Diagram Cont. Ladder Wiring Diagram Check for Refrigerant Leaks Start-Up AdjustmentsSTART-UP Checking Cooling and Heating Control OperationTwo Cooling Fan Speeds Set-up Dehumidification feature used Checking and Adjusting Refrigerant ChargeIndoor Airflow and Airflow Adjustments Unit Operation HazardContinuous Fan Operation Single Speed Cooling With Higher Electric Heat SpeedColor Coding for Indoor Fan Motor Leads Quiet Shift Defrost ControlDefrost Indoor Blower and Motor MaintenanceAir Filter Personal Injury and Unit Damage Hazard607--A Wet Coil Pressure Drop in. W.C Filter Pressure Drop Table in. W.COutdoor Coil, Indoor Coil, and Condensate Drain Pan Cooling Charging Table-SubcoolingRefrigerant Circuit Electrical Controls and WiringOutdoor Fan Indoor AirflowHigh-Pressure Switch Pressure SwitchesLoss of Charge Switch Copeland Scroll Compressor Puron RefrigerantSTART-UP Checklist TroubleshootingSystem Information Puronr R-410A Quick Reference Guide Troubleshooting Chart Symptom Cause RemedyPreliminary Information Model no TemperaturesRemove and Store in Job Files III. START-UP Electrical Supply Voltage Compressor AmpsInstallation Vertical Economizer Factory Installed Option GeneralAccessories Small ChassisEconomizer Hood Top Panel Removal Filter Part NumberHood Divider Removed Economizer Hood Assembly Large Chassis Horizontal Return Duct Cover Panel and Hood Divider RemovalLeft Hood Side Hood Assembly Supply AIR Temperature SAT SENSOR-The supply ConfigurationEconomizer Standard Sensors 11.7C 12.8C 14.4C 17.2C 20C 22.8C 25.6C Economizer Controller 607C-- -- a Economizer Wiring Diagram A10200 Cont. Ladder Wiring Diagram A10199 607C-- -- a 607C-- -- a CO2 Sensor Standard Settings Economizer Input/Output Logic CO2 Sensor Standard SettingsOperation Troubleshooting 607C--A 30 3 Phase with Economizer 607C--A 36-60 3 Phase with Economizer