Single phase units:
1.Run the
2.Connect ground lead to chassis ground connection.
3.Locate the black and yellow wires connected to the line side of the contactor.
4.Connect field L1 to black wire on connection 11 of the compressor contactor.
5.Connect field wire L2 to yellow wire on connection 23 of the compressor contactor.
Use no. 18 American Wire Gage (AWG)
Standard Connections
Locate the eight (nine on
HIGH VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)
TWO POWER | EQUIP GR |
LEADS |
CONTROL BOX
POWER
SUPPLY
operation of unit. A gray wire is standard on
If an accessory electric heater is installed, low voltage leads from heater must be connected to factory supplied control leads from Indoor Fan Board P4 connector. Factory wires are provided for electric heat staging W1 and W2 (W2 and W3 on IFB). If room thermostat has only one stage of supplemental heat, connect white and violet wires shown in Fig. 9 to second stage heat field wire.
607C-- -- A
WIRING LABEL
SPLICE BOX
WHT(W1) | W1 |
| |
VIO (W2) | W2 |
| |
YEL(Y) | Y |
| |
GRN(G) | G |
| |
RED(R) | R |
| |
BRN(C) | C |
| |
ORN(O) | O |
| |
BLU(DH) | DH |
| |
GRA(Y2) | |
| |
| Only |
THERMOSTAT (TYPICAL)
Some electric heaters have four control wires (plus common wire). Consult unit wiring diagram and electric heater wiring diagram for additional details.
Transformer Protection
The transformer is of the
Accessory Electric Heaters Installation
Electric heaters may be installed with the
instructions supplied with electric heater package. See unit rating
A09071
Fig. 9 - High- and Control-Voltage Connections
1.Run the
2.Connect ground lead to chassis ground connection.
3.Locate the black and yellow wires connected to the line side of the contactor.
4.Connect field L1 to black wire on connection 11 of the compressor contactor.
5.Connect field wire L3 to yellow wire on connection 13 of the compressor contactor.
6.Connect field wire L2 to blue wire from compressor.
Special Procedures for 208-V Operation
!WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system and install lockout tag. With disconnect switch open, move black wire from transformer (3/16 in.) terminal marked 230 to terminal marked 208. This retaps transformer to primary voltage of 208 vac.
Control Voltage Connections
NOTE: Do not use any type of
plate for
Sequence of Operation
a. CONTINUOUS FAN
(1.) Thermostat closes circuit R to G energizing the blower motor for continuous fan.
b. COOLING MODE
(1.) If indoor temperature is above temperature set point, thermostat closes circuits R to G, R to Y and
Rto
c.ELECTRIC HEATING MODE
(1.) Thermostat closes circuit R to W/W1, or W2 and R to G. There are no on or off delays.
d.HEAT PUMP HEATING MODE
(1.) Thermostat closes circuits R to G and R to Y. The compressor, indoor and outdoor fans are energized.
e.HEAT PUMP HEATING WITH AUXILIARY ELECTRIC HEAT
(1.) Thermostat closes circuits R to G, R to Y and R to W/W1 or W2. The compressor, indoor and outdoor fans are energized, as well as the electric heat relays.
f.DEFROST MODE
The defrost mode is automatically energized by the defrost board during heating mode. The defrost board energizes “O” (reversing valve) and “W2” (electric heat). It also
9