Bryant 607C-A installation instructions Puronr R-410A Quick Reference Guide

Page 27

PURONR (R-410A) QUICK REFERENCE GUIDE

SPuron refrigerant operates at 50-70 percent higher pressures than R-22. Be sure that servicing equipment and replacement

components are designed to operate with Puron

SPuron refrigerant cylinders are rose colored.

SRecovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.

SPuron systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when charging into suction line with compressor operating

SManifold sets should be minimum 700 psig high side and 180 psig low side with 550 psig low-side retard. S Use hoses with minimum 700 psig service pressure rating.

S Leak detectors should be designed to detect HFC refrigerant. S Puron, as with other HFCs, is only compatible with POE oils. S Vacuum pumps will not remove moisture from oil.

S Do not use liquid-line filter driers with rated working pressures less than 600 psig. S Do not leave Puron suction line filter driers in line longer than 72 hours.

S Do not install a suction-line filter drier in liquid line.

S POE oils absorb moisture rapidly. Do not expose oil to atmosphere. S POE oils may cause damage to certain plastics and roofing materials. S Wrap all filter driers and service valves with wet cloth when brazing. S A factory approved liquid-line filter drier is required on every unit.

S Do NOT use an R-22 TXV.

S Never open system to atmosphere while it is under a vacuum.

S When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter driers. Evacuate to 500 microns prior to recharging.

S Do not vent Puron into the atmosphere.

S Observe all warnings, cautions, and bold text.

S All indoor coils must be installed with a hard shutoff Puron TXV metering device.

607C-- -- A

27

Image 27
Contents Safety Considerations Table of ContentsProvide Unit Support Receiving and InstallationIntroduction Check Equipment607--A24-30 Unit Dimensions 607--A36-60 Unit Dimensions SMALL/COMMON Curb Unit Falling Hazard Rig and Place UnitInspection Rigging/Lifting of Unit See FigPersonal Injury and Electrical Operation Hazard Select and Install DuctworkUnit Component Damage Hazard Install Electrical ConnectionsProvide for Condensate Disposal High-Voltage ConnectionsTransformer Protection Accessory Electric Heaters InstallationSpecial Procedures for 208-V Operation Standard ConnectionsMinimum Airflow for Reliable Electric Heater Operation CFM Condensate Trap Physical Data Unit 607--AConnection Wiring Schematics 208/230-1-60 Cont. Ladder Wiring Schematics 208/230-1-60 607C a Cont. Ladder Wiring Schematics 208/230-3-60 Connection Wiring Diagram Cont. Ladder Wiring Diagram Checking Cooling and Heating Control Operation Start-Up AdjustmentsSTART-UP Check for Refrigerant LeaksUnit Operation Hazard Checking and Adjusting Refrigerant ChargeIndoor Airflow and Airflow Adjustments Two Cooling Fan Speeds Set-up Dehumidification feature usedSingle Speed Cooling With Higher Electric Heat Speed Continuous Fan OperationColor Coding for Indoor Fan Motor Leads Defrost Control Quiet ShiftDefrost Personal Injury and Unit Damage Hazard MaintenanceAir Filter Indoor Blower and MotorFilter Pressure Drop Table in. W.C 607--A Wet Coil Pressure Drop in. W.CCooling Charging Table-Subcooling Outdoor Coil, Indoor Coil, and Condensate Drain PanIndoor Airflow Electrical Controls and WiringOutdoor Fan Refrigerant CircuitCopeland Scroll Compressor Puron Refrigerant Pressure SwitchesLoss of Charge Switch High-Pressure SwitchTroubleshooting START-UP ChecklistSystem Information Puronr R-410A Quick Reference Guide Symptom Cause Remedy Troubleshooting ChartIII. START-UP Electrical Supply Voltage Compressor Amps TemperaturesRemove and Store in Job Files Preliminary Information Model noSmall Chassis Vertical Economizer Factory Installed Option GeneralAccessories InstallationFilter Part Number Economizer Hood Top Panel RemovalHood Divider Removed Economizer Hood Assembly Horizontal Return Duct Cover Panel and Hood Divider Removal Large ChassisLeft Hood Side Hood Assembly Configuration Supply AIR Temperature SAT SENSOR-The supplyEconomizer Standard Sensors 11.7C 12.8C 14.4C 17.2C 20C 22.8C 25.6C Economizer Controller 607C-- -- a Economizer Wiring Diagram A10200 Cont. Ladder Wiring Diagram A10199 607C-- -- a 607C-- -- a CO2 Sensor Standard Settings CO2 Sensor Standard Settings Economizer Input/Output LogicOperation Troubleshooting 607C--A 30 3 Phase with Economizer 607C--A 36-60 3 Phase with Economizer