Table 16 – CO2 Sensor Standard Settings

 

 

 

VENTILATION

 

CO2

OPTIONAL

RELAY

SETTING

EQUIPMENT

OUTPUT

RATE

ANALOG

CONTROL

RELAY

HYSTERESIS

(CFM/

OUTPUT

RANGE

SETPOINT

 

 

 

(PPM)

 

 

 

PERSON)

 

(PPM)

(PPM)

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

Proportional

Any

0---10V

0---2000

1000

50

 

4---20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

Interface w/Standard Building

Proportional

Any

2---10V

0---2000

1000

50

Control System

7---20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

Exponential

Any

0---10V

0---2000

1100

50

 

4---20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

Proportional

15

0---10V

0---1100

1100

50

 

4---20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

Economizer

Proportional

20

0---10V

0---900

900

50

4---20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

Exponential

15

0---10V

1---1100

1100

50

 

4---20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

Exponential

20

0---10V

0---900

900

50

 

4---20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

Health & Safety

Proportional

---

0---10V

0---9999

5000

500

4---20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

Parking/Air Intakes/Loading Docks

Proportional

---

0---10V

0---2000

700

50

4---20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 17 – CO2 Sensor Standard Settings Economizer Input/Output Logic

 

INPUTS

 

 

 

 

 

OUTPUTS

 

 

 

 

 

 

 

 

 

 

DEMAND

ENTHALPY

 

 

 

COMPRESSOR

N TERMINAL

CONTROL

 

 

 

 

 

 

 

 

 

 

Y1

Y2

STAGE

STAGE

OCCUPIED

UNOCCUPIED

VENTILATION

OUTDOOR

RETURN

 

 

 

 

(DCV)

 

 

 

 

1

2

DAMPER

 

 

 

 

 

 

 

 

 

 

High (Free Cooling

 

On

On

On

On

 

 

 

 

 

 

 

 

 

 

 

Low

On

Off

On

Off

Minimum position

Closed

 

LED off)

 

 

 

 

 

 

 

 

Below set (DCV

 

 

Off

Off

Off

Off

 

 

LED Off)

 

 

 

 

 

 

 

 

Low (Free Cooling

 

On

On

On

Off

Modulating** (between min.

Modulating** (between closed

 

High

On

Off

Off

Off

position and full ---open)

and full ---open)

 

LED on)

 

 

 

 

 

 

 

 

 

 

Off

Off

Off

Off

Minimum position

Closed

 

 

 

 

 

 

 

 

 

 

High (Free Cooling

 

On

On

On

On

Modulating{{ (between

Modulating{{ (between closed

 

 

 

 

 

 

 

Low

On

Off

On

Off

min. position and DCV

 

LED off)

and DCV maximum)

 

 

 

 

 

 

maximum)

Above set (DCV

 

 

Off

Off

Off

Off

 

 

 

 

 

LED On)

 

 

 

 

 

 

 

 

Low (Free Cooling

 

On

On

On

Off

 

 

 

 

 

 

 

 

 

 

 

High

On

Off

Off

Off

Modulating***

Modulating{{{

 

LED on)

 

 

 

 

 

 

 

 

 

 

 

Off

Off

Off

Off

 

 

 

 

 

 

 

 

 

 

 

* For single enthalpy control, the module compares outdoor enthalpy to the ABCD set point.

{Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), now power (Unoccupied). **Modulating is based on the supply--- air sensor signal.

{{Modulation is based on the DCV signal.

***Modulation is based on the greater of DCV and supply--- air sensor signals, between minimum position and either maximum position (DCV) or fully open (supply--- air signal).

{{{Modulating is based on the greater of DCV and supply--- air sensor signals, between closed and wither maximum position (DCV) or fully open (supply--- air signal).

607C-- -- A

OPERATION

Sequence of Operation—When free cooling is not available, the compressor will be controlled by the thermostat. When free cooling is available, the outdoor-air damper is modulated by the Economizer control to provide a 50_ to 55_F (10_ to 12.8_C) supply-air temperature into the zone. As the supply-air temperature fluctuates above 55_ (12.8_C) or below 50_F (10_C), the dampers will be modulated (open or close) to bring the supply-air temperature back within the set points. For Economizer operation, there must be a thermostat call for the fan (G). This will move the damper to its minimum position during the occupied mode.

NOTE: The DCV Max potentiometer must be closed (CCW) when not using CO2 sensor.

Above 50_F (10_C) supply-air temperature, the dampers will modulate from 100% open to the minimum open position. From 50_F to 45_F (10_ to 7.2_C) supply-air temperature, the dampers will maintain at the minimum open position. Below 45_F (7.2_C), the dampers will be completely shut. As the supply-air temperature rises, the dampers will come back open to the minimum open position once the supply-air temperature rises to 48_F (8.9_C). If

power exhaust is installed, as the outdoor-air damper opens and closes, the power exhaust fans will be energized and deenergized. If field-installed accessory CO2 sensors are connected to the Economizer control, a demand controlled ventilation strategy will begin to operate. As the CO2 level in the zone increases above the CO2 set point, the minimum position of the damper will be increased proportionally. As the CO2 level decreases because of the increase in fresh air, the outdoor-air damper will be proportionally closed. Damper position will follow the higher demand condition from DCV mode or free cooling mode. Damper movement from full closed to full open (or vice versa) will take between 1 1/2 and 2 1/2 minutes. If free cooling can be used as determined from the appropriate changeover command (dry bulb, enthalpy curve, or differential enthalpy), a call for cooling (Y1 closes at the thermostat) will cause the control to modulate the dampers open to maintain the supply air temperature set point at 50_ to 55_F (10_ to 12.8_C). As the supply air temperature drops below the set point range of 50_ to 55_F (10_ to 12.8_C), the control will modulate the outdoor-air dampers closed to maintain the proper supply-air temperature.

47

Image 47
Contents Safety Considerations Table of ContentsProvide Unit Support Receiving and InstallationIntroduction Check Equipment607--A24-30 Unit Dimensions 607--A36-60 Unit Dimensions SMALL/COMMON Curb Unit Falling Hazard Rig and Place UnitInspection Rigging/Lifting of Unit See FigPersonal Injury and Electrical Operation Hazard Select and Install DuctworkUnit Component Damage Hazard Install Electrical ConnectionsProvide for Condensate Disposal High-Voltage ConnectionsTransformer Protection Accessory Electric Heaters InstallationSpecial Procedures for 208-V Operation Standard ConnectionsMinimum Airflow for Reliable Electric Heater Operation CFM Condensate Trap Physical Data Unit 607--AConnection Wiring Schematics 208/230-1-60 Cont. Ladder Wiring Schematics 208/230-1-60 607C a Cont. Ladder Wiring Schematics 208/230-3-60 Connection Wiring Diagram Cont. Ladder Wiring Diagram Checking Cooling and Heating Control Operation Start-Up AdjustmentsSTART-UP Check for Refrigerant LeaksUnit Operation Hazard Checking and Adjusting Refrigerant ChargeIndoor Airflow and Airflow Adjustments Two Cooling Fan Speeds Set-up Dehumidification feature usedColor Coding for Indoor Fan Motor Leads Single Speed Cooling With Higher Electric Heat SpeedContinuous Fan Operation Defrost Defrost ControlQuiet Shift Personal Injury and Unit Damage Hazard MaintenanceAir Filter Indoor Blower and MotorFilter Pressure Drop Table in. W.C 607--A Wet Coil Pressure Drop in. W.CCooling Charging Table-Subcooling Outdoor Coil, Indoor Coil, and Condensate Drain PanIndoor Airflow Electrical Controls and WiringOutdoor Fan Refrigerant CircuitCopeland Scroll Compressor Puron Refrigerant Pressure SwitchesLoss of Charge Switch High-Pressure SwitchSystem Information TroubleshootingSTART-UP Checklist Puronr R-410A Quick Reference Guide Symptom Cause Remedy Troubleshooting ChartIII. START-UP Electrical Supply Voltage Compressor Amps TemperaturesRemove and Store in Job Files Preliminary Information Model noSmall Chassis Vertical Economizer Factory Installed Option GeneralAccessories InstallationFilter Part Number Economizer Hood Top Panel RemovalHood Divider Removed Economizer Hood Assembly Horizontal Return Duct Cover Panel and Hood Divider Removal Large ChassisLeft Hood Side Hood Assembly Economizer Standard Sensors ConfigurationSupply AIR Temperature SAT SENSOR-The supply 11.7C 12.8C 14.4C 17.2C 20C 22.8C 25.6C Economizer Controller 607C-- -- a Economizer Wiring Diagram A10200 Cont. Ladder Wiring Diagram A10199 607C-- -- a 607C-- -- a Operation CO2 Sensor Standard SettingsCO2 Sensor Standard Settings Economizer Input/Output Logic Troubleshooting 607C--A 30 3 Phase with Economizer 607C--A 36-60 3 Phase with Economizer