Bryant 607C-A installation instructions Condensate Trap Physical Data Unit 607--A

Page 10

RETURN

AIR

TOP COVER

INDOOR

THERMOSTAT

FROM

POWER

SOURCE

DISCONNECT

PER NEC*

607C-- -- A

 

 

 

 

 

 

POWER ENTRY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*NEC - NATIONAL ELECTRICAL CODE

 

 

 

 

 

 

 

 

 

CONTROL ENTRY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A09238

 

 

 

 

 

Fig. 10 - Typical Installation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRAP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTLET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1-in. (25 mm) min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-in. (51 mm) min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A09052

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 11 - Condensate Trap

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 1 – Physical Data - Unit 607--A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

607----A24

607----A30

 

607----A36

 

 

607----A42

 

607----A48

607----A60

 

Unit Size

2

2.5

 

 

3

 

 

3.5

 

4

5

 

Shipping Weight (lb)

354

346

 

 

426

 

 

 

472

 

460

506

 

(kg)

161

157

 

 

193

 

 

214

 

209

230

 

Compressor Quantity

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

Type

 

 

 

 

 

 

 

 

 

 

Scroll

 

 

 

Refrigerant

 

 

 

 

 

 

 

 

 

 

R-410A

 

 

 

Refrigerant Quantity (lb)

11.1

10.3

 

 

9.9

 

 

 

11.3

 

12.5

15.2

 

Quantity (kg)

5.0

4.7

 

 

4.5

 

 

5.1

 

5.7

6.9

 

Refrigerant Metering Device

 

 

 

 

 

 

 

 

Indoor TXV, Outdoor

Dual Accuraters

 

 

 

 

Orifice OD (in)

0.032 (2)

0.037 (2)

 

 

0.038 (2)

 

0.040 (2)

 

0.040 (2)

0.049 (2)

 

(mm)

0.81 (2)

0.94 (2)

 

 

0.97 (2)

 

 

1.02 (2)

 

1.02 (2)

1.24 (2)

 

Outdoor Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rows...Fins/in,

2...21

2...21

 

 

2...21

 

 

2...21

 

2...21

2...21

 

face area (sq. ft.)

13.6

13.6

 

 

13.6

 

 

17.5

 

17.5

23.3

 

Outdoor Fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal Airflow (cfm)

2500

2700

 

 

3100

 

 

3100

 

3100

3500

 

Diameter (in.)

24

24

 

 

26

 

 

26

 

26

26

 

Diameter (mm)

610

610

 

 

660

 

 

660

 

660

660

 

Motor hp (rpm)

1/10 (810)

1/5 (810)

 

 

1/5 (810)

 

1/5 (810)

 

1/5 (810)

1/4 (810)

 

Indoor Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rows...Fins/in,

3...17

3...17

 

 

3...17

 

 

3...17

 

3...17

3...17

 

face area (sq. ft.)

3.7

3.7

 

 

4.7

 

 

4.7

 

5.6

5.6

 

Indoor Blower

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal Airflow (cfm)

800

1000

 

 

1200

 

 

1400

 

1600

1750

 

Size (in.)

 

 

 

 

10 x 10

10 x 10

 

11 x 10

 

 

11 x 10

 

11 x 10

11 x 10

Size (mm)

 

 

 

 

254 x 254

254 x 254

 

279 x 254

 

 

279 x 254

 

279 x 254

279 x 254

Motor hp (rpm)

1/2

1/2

 

 

3/4

 

 

3/4

 

1

1

 

High Pressure Switch (psig)

 

 

 

 

 

 

 

650 +/- 15

 

 

 

 

 

Cutout

 

 

 

 

 

 

 

 

 

 

 

 

Reset (Auto)

 

 

 

 

 

 

 

420 +/- 25

 

 

 

 

 

Loss-of-Charge/Low Pressure Switch (psig)

 

 

 

 

 

 

 

20 +/- 5

 

 

 

 

 

Cutout

 

 

 

 

 

 

 

 

 

 

 

 

Reset (Auto)

 

 

 

 

 

 

 

45 +/- 10

 

 

 

 

 

Return Air Filters

 

 

 

 

20x20x1

20x24x1

 

 

24x30x1

24x36x1

disposable (in)

 

 

 

 

 

 

(mm)

 

 

 

 

508x508x25

508x610x25

 

610x762x25

610x914x25

*Required filter sizes shown are based on the larger of the AHRI (Air Conditioning, Heating and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft/minute for throwaway type or 450 ft/minute for high ---capacity type. Air filter pressure drop for non ---standard filters must not exceed 0.08 IN. W.C.

{If using accessory filter rack refer to the filter rack installation instructions for correct filter size and quantity. } For 460 volt units, add 14 lb (6.4 kg) to the weight.

Table 2 – Minimum Airflow for Reliable Electric Heater Operation (CFM)

SIZE

607- -

A24

607- -

A30

607- -

A36

607- -

A42

607- -

A48

607- -

A60

AIRFLOW (CFM)

800

1025

1250

1400

1710

1800

10

Image 10
Contents Table of Contents Safety ConsiderationsCheck Equipment Receiving and InstallationIntroduction Provide Unit Support607--A24-30 Unit Dimensions 607--A36-60 Unit Dimensions SMALL/COMMON Curb Rigging/Lifting of Unit See Fig Rig and Place UnitInspection Unit Falling HazardSelect and Install Ductwork Personal Injury and Electrical Operation HazardHigh-Voltage Connections Install Electrical ConnectionsProvide for Condensate Disposal Unit Component Damage HazardStandard Connections Accessory Electric Heaters InstallationSpecial Procedures for 208-V Operation Transformer ProtectionCondensate Trap Physical Data Unit 607--A Minimum Airflow for Reliable Electric Heater Operation CFMConnection Wiring Schematics 208/230-1-60 Cont. Ladder Wiring Schematics 208/230-1-60 607C a Cont. Ladder Wiring Schematics 208/230-3-60 Connection Wiring Diagram Cont. Ladder Wiring Diagram Check for Refrigerant Leaks Start-Up AdjustmentsSTART-UP Checking Cooling and Heating Control OperationTwo Cooling Fan Speeds Set-up Dehumidification feature used Checking and Adjusting Refrigerant ChargeIndoor Airflow and Airflow Adjustments Unit Operation HazardContinuous Fan Operation Single Speed Cooling With Higher Electric Heat SpeedColor Coding for Indoor Fan Motor Leads Quiet Shift Defrost ControlDefrost Indoor Blower and Motor MaintenanceAir Filter Personal Injury and Unit Damage Hazard607--A Wet Coil Pressure Drop in. W.C Filter Pressure Drop Table in. W.COutdoor Coil, Indoor Coil, and Condensate Drain Pan Cooling Charging Table-SubcoolingRefrigerant Circuit Electrical Controls and WiringOutdoor Fan Indoor AirflowHigh-Pressure Switch Pressure SwitchesLoss of Charge Switch Copeland Scroll Compressor Puron RefrigerantSTART-UP Checklist TroubleshootingSystem Information Puronr R-410A Quick Reference Guide Troubleshooting Chart Symptom Cause RemedyPreliminary Information Model no TemperaturesRemove and Store in Job Files III. START-UP Electrical Supply Voltage Compressor AmpsInstallation Vertical Economizer Factory Installed Option GeneralAccessories Small ChassisEconomizer Hood Top Panel Removal Filter Part NumberHood Divider Removed Economizer Hood Assembly Large Chassis Horizontal Return Duct Cover Panel and Hood Divider RemovalLeft Hood Side Hood Assembly Supply AIR Temperature SAT SENSOR-The supply ConfigurationEconomizer Standard Sensors 11.7C 12.8C 14.4C 17.2C 20C 22.8C 25.6C Economizer Controller 607C-- -- a Economizer Wiring Diagram A10200 Cont. Ladder Wiring Diagram A10199 607C-- -- a 607C-- -- a CO2 Sensor Standard Settings Economizer Input/Output Logic CO2 Sensor Standard SettingsOperation Troubleshooting 607C--A 30 3 Phase with Economizer 607C--A 36-60 3 Phase with Economizer