607C-- -- A
Table 9 – Troubleshooting Chart
SYMPTOM | CAUSE | REMEDY | |
|
|
| |
| Power failure | Call power company | |
| Fuse blown or circuit breaker tripped | Replace fuse or reset circuit breaker | |
| Defective contactor, transformer, or | Replace component | |
Compressor and condenser fan will not start. | |||
| |||
|
|
| |
| Insufficient line voltage | Determine cause and correct | |
| Incorrect or faulty wiring | Check wiring diagram and rewire correctly | |
| Thermostat setting too high | Lower thermostat setting below room tempera- | |
| ture | ||
|
| ||
|
|
| |
| Faulty wiring or loose connections in compressor cir- | Check wiring and repair or replace | |
| cuit | ||
|
| ||
|
|
| |
Compressor will not start but condenser fan | Compressor motor burned out, seized, or | Determine cause | |
internal overload open | Replace compressor | ||
runs | |||
|
| ||
Defective run/start capacitor, overload, start relay | Determine cause and replace | ||
| |||
| One leg of | Replace fuse or reset circuit breaker | |
| Determine cause | ||
|
| ||
|
|
| |
| Correct the direction of rotation by reversing the | ||
makes excessive noise, and there may be a | Scroll compressor is rotating in the wrong direction | ||
low pressure differential. |
| ||
|
| ||
|
|
| |
| Refrigerant overcharge or undercharge | Recover refrigerant, evacuate system, and re- | |
| charge to capacities shown on rating plate | ||
|
| ||
|
|
| |
| Defective compressor | Replace and determine cause | |
Compressor cycles (other than normally sat- | Insufficient line voltage | Determine cause and correct | |
Blocked condenser | Determine cause and correct | ||
isfying thermostat). | |||
Defective run/start capacitor, overload or start relay | Determine cause and replace | ||
| |||
| Defective thermostat | Replace thermostat | |
| Faulty | Replace | |
| Restriction in refrigerant system | Locate restriction and remove | |
| Dirty air filter | Replace filter | |
| Unit undersized for load | Decrease load or increase unit size | |
| Thermostat set too low | Reset thermostat | |
Compressor operates continuously | Low refrigerant charge | Locate leak, repair, and recharge | |
Mechanical damage in compressor | Replace compressor | ||
| |||
| Air in system | Recover refrigerant, evacuate system, and re- | |
| charge | ||
|
| ||
|
|
| |
| Condenser coil dirty or restricted | Clean coil or remove restriction | |
| Dirty air filter | Replace filter | |
| Dirty condenser coil | Clean coil | |
Excessive head pressure | Refrigerant overcharged | Recover excess refrigerant | |
Air in system | Recover refrigerant, evacuate system, and re- | ||
| |||
| charge | ||
|
| ||
|
|
| |
| Condenser air restricted or air | Determine cause and correct | |
| Low refrigerant charge | Check for leaks, repair, and recharge. | |
Head pressure too low | Compressor IPR leaking | Replace compressor | |
| Restriction in liquid tube | Remove restriction | |
| High heat load | Check for source and eliminate | |
Excessive suction pressure | Compressor IPR leaking | Replace compressor | |
| Refrigerant overcharged | Recover excess refrigerant | |
| Dirty air filter | Replace filter | |
| Low refrigerant charge | Check for leaks, repair and recharge | |
| Metering device or low side restricted | Remove source of restriction | |
Suction pressure too low | Insufficient evaporator airflow | Increase air quantity | |
Check | |||
|
| ||
|
|
| |
| Temperature too low in conditioned area | Reset thermostat | |
| Outdoor ambient below 55°F (12.7°C) | Install | |
| Filter drier restricted | Replace filter |
28