When demand ventilation control is not being used, the minimum position potentiometer should be used to set the occupied ventilation position. The maximum demand ventilation position should be turned fully clockwise. Adjust the minimum position potentiometer to allow the minimum amount of outdoor air, as required by local codes, to enter the building. Make minimum position adjustments with at least 10_F (12.2_C) temperature difference between the outdoor and return-air temperatures. To determine the minimum position setting, perform the following procedure:

1.Calculate the appropriate mixed air temperature using the following formula:

(To x OA/100) + (TR x RA/100) = TM TO = Outdoor-Air Temperature

OA = Percent of Outdoor Air TR = Return-Air Temperature RA = Percent of Return Air TM = Mixed-Air Temperature

As an example, if local codes require 10% outdoor air during occupied conditions, outdoor-air temperature is 60_F (15.6_C), and return-air temperature is 75_F (23.9_C). (60 x .10) + (75 x .90) = 73.5_F (23.1_C)

2.Disconnect the supply air sensor from terminals T and T1.

3.Ensure that the factory-installed jumper is in place across terminals P and P1. If remote damper positioning is being used, make sure that the terminals are wired according to Fig. 45 and that the minimum position potentiometer is turned fully clockwise.

4.Connect 24 vac across terminals TR and TR1.

5.Carefully adjust the minimum position potentiometer until the measured mixed-air temperature matches the calculated value.

6.Reconnect the supply air sensor to terminals T and T1.

Remote control of the Economizer damper is desirable when requiring additional temporary ventilation. If a field-supplied remote potentiometer (Honeywell part number S963B1128) is wired to the Economizer controller, the minimum position of the damper can be controlled from a remote location. To control the minimum damper position remotely, remove the factory installed jumper on the P and P1 terminals on the Economizer controller. Wire the field-supplied potentiometer to the P and P1 terminals on the Economizer controller. See Fig. 44 and Fig. 45.

40

Image 40
Contents Table of Contents Safety ConsiderationsReceiving and Installation IntroductionCheck Equipment Provide Unit Support607--A24-30 Unit Dimensions 607--A36-60 Unit Dimensions SMALL/COMMON Curb Rig and Place Unit InspectionRigging/Lifting of Unit See Fig Unit Falling HazardSelect and Install Ductwork Personal Injury and Electrical Operation HazardInstall Electrical Connections Provide for Condensate DisposalHigh-Voltage Connections Unit Component Damage HazardAccessory Electric Heaters Installation Special Procedures for 208-V OperationStandard Connections Transformer ProtectionCondensate Trap Physical Data Unit 607--A Minimum Airflow for Reliable Electric Heater Operation CFMConnection Wiring Schematics 208/230-1-60 Cont. Ladder Wiring Schematics 208/230-1-60 607C a Cont. Ladder Wiring Schematics 208/230-3-60 Connection Wiring Diagram Cont. Ladder Wiring Diagram Start-Up Adjustments START-UPCheck for Refrigerant Leaks Checking Cooling and Heating Control OperationChecking and Adjusting Refrigerant Charge Indoor Airflow and Airflow AdjustmentsTwo Cooling Fan Speeds Set-up Dehumidification feature used Unit Operation HazardContinuous Fan Operation Single Speed Cooling With Higher Electric Heat SpeedColor Coding for Indoor Fan Motor Leads Quiet Shift Defrost ControlDefrost Maintenance Air FilterIndoor Blower and Motor Personal Injury and Unit Damage Hazard607--A Wet Coil Pressure Drop in. W.C Filter Pressure Drop Table in. W.COutdoor Coil, Indoor Coil, and Condensate Drain Pan Cooling Charging Table-SubcoolingElectrical Controls and Wiring Outdoor FanRefrigerant Circuit Indoor AirflowPressure Switches Loss of Charge SwitchHigh-Pressure Switch Copeland Scroll Compressor Puron RefrigerantSTART-UP Checklist TroubleshootingSystem Information Puronr R-410A Quick Reference Guide Troubleshooting Chart Symptom Cause RemedyTemperatures Remove and Store in Job FilesPreliminary Information Model no III. START-UP Electrical Supply Voltage Compressor AmpsVertical Economizer Factory Installed Option General AccessoriesInstallation Small ChassisEconomizer Hood Top Panel Removal Filter Part NumberHood Divider Removed Economizer Hood Assembly Large Chassis Horizontal Return Duct Cover Panel and Hood Divider RemovalLeft Hood Side Hood Assembly Supply AIR Temperature SAT SENSOR-The supply ConfigurationEconomizer Standard Sensors 11.7C 12.8C 14.4C 17.2C 20C 22.8C 25.6C Economizer Controller 607C-- -- a Economizer Wiring Diagram A10200 Cont. Ladder Wiring Diagram A10199 607C-- -- a 607C-- -- a CO2 Sensor Standard Settings Economizer Input/Output Logic CO2 Sensor Standard SettingsOperation Troubleshooting 607C--A 30 3 Phase with Economizer 607C--A 36-60 3 Phase with Economizer