Bryant 607C-A installation instructions Economizer Hood Top Panel Removal, Filter Part Number

Page 31

 

Hood Top

OAT Sensor

Panel

A09689

Fig. 23 - Economizer Hood Top Panel Removal

OAT Sensor

A09690

Fig. 24 - Oat Sensor Installed

6.Replace horizontal return duct cover panel. Screw in place ensuring all seams are air and watertight.

7.Install the 2 angle filter brackets to the right and left hood side panels respectively with the #10 screws provided. See Fig. 26.

8.Assemble hood according to Fig. 27 screwing together with provided #10 sheet metal screws.

9.Install assembled hood over the economizer opening in the replacement return chamber panel. See Fig. 28. Screw in place through pre-punched holes. Make sure all seams are air and watertight.

NOTE: The two wires that connect to the outside air temperature sensor (OAT) should remain accessible.

10.Connect the outside air temperature sensor (OAT) to the economizer per wiring diagram.

11.Open the filter clips on the inside of the hood top. Insert the aluminum filter into the hood and close the clips to hold in place. See Fig. 29.

12.To replace 12 x 20 x1 (304.8mm x 508mm x 25.4mm) air filters, open the filter access door (horizontal return duct cover panel), remove old filters and install new disposable filters in filter rack. See Table 13 for filter part number.

Table 13 – Filter Part Number

DESCRIPTION

PART NUMBER

 

 

 

Indoor Coil Air Filter

12 x 20 x 1

KH01AA312

(304.8 x 508 x 25.4 mm)

 

 

 

 

 

NOTE: The economizer control settings and the filters are accessible through the filter access door.

13.Economizer controls are set to a standard factory setting. Nevertheless, you can adjust these settings through the filter access door. Review the settings in the Operation section:

(5.) The standard economizer controller has a factory setting of “C” for the outdoor air temperature changeover and 63_F (17_C) for the supply air (mixed air) temperature sensor. The outdoor air temperature changeover setting is adjusted on the sensor by setting the dip switches on the sensor. The ABCD potentiometer on the economizer control should be set to the “D” position.

(6.) The low ambient compressor lockout switch setting is fixed at 42_F (5.6_C).

(7.) The minimum position for the outdoor air damper can be configured at the controller. When not using a CO2 sensor, the DCV Max potentiometer must be completely closed (CCW) for the Minimum Posi- tion potentiometer to function correctly.

(8.) Settings for the optional outdoor enthalpy sensor, indoor enthalpy sensor, and CO2 sensor can also be configured at the controller.

14.Replace the filter access panel. Screw in place ensuring all seams are air and watertight.

15.Install all economizer accessories then power HVAC unit and test cycle economizer.

607C-- -- A

31

Image 31
Contents Safety Considerations Table of ContentsProvide Unit Support Receiving and InstallationIntroduction Check Equipment607--A24-30 Unit Dimensions 607--A36-60 Unit Dimensions SMALL/COMMON Curb Unit Falling Hazard Rig and Place UnitInspection Rigging/Lifting of Unit See FigPersonal Injury and Electrical Operation Hazard Select and Install DuctworkUnit Component Damage Hazard Install Electrical ConnectionsProvide for Condensate Disposal High-Voltage ConnectionsTransformer Protection Accessory Electric Heaters InstallationSpecial Procedures for 208-V Operation Standard ConnectionsMinimum Airflow for Reliable Electric Heater Operation CFM Condensate Trap Physical Data Unit 607--AConnection Wiring Schematics 208/230-1-60 Cont. Ladder Wiring Schematics 208/230-1-60 607C a Cont. Ladder Wiring Schematics 208/230-3-60 Connection Wiring Diagram Cont. Ladder Wiring Diagram Checking Cooling and Heating Control Operation Start-Up AdjustmentsSTART-UP Check for Refrigerant LeaksUnit Operation Hazard Checking and Adjusting Refrigerant ChargeIndoor Airflow and Airflow Adjustments Two Cooling Fan Speeds Set-up Dehumidification feature usedContinuous Fan Operation Single Speed Cooling With Higher Electric Heat SpeedColor Coding for Indoor Fan Motor Leads Quiet Shift Defrost ControlDefrost Personal Injury and Unit Damage Hazard MaintenanceAir Filter Indoor Blower and MotorFilter Pressure Drop Table in. W.C 607--A Wet Coil Pressure Drop in. W.CCooling Charging Table-Subcooling Outdoor Coil, Indoor Coil, and Condensate Drain PanIndoor Airflow Electrical Controls and WiringOutdoor Fan Refrigerant CircuitCopeland Scroll Compressor Puron Refrigerant Pressure SwitchesLoss of Charge Switch High-Pressure SwitchSTART-UP Checklist TroubleshootingSystem Information Puronr R-410A Quick Reference Guide Symptom Cause Remedy Troubleshooting ChartIII. START-UP Electrical Supply Voltage Compressor Amps TemperaturesRemove and Store in Job Files Preliminary Information Model noSmall Chassis Vertical Economizer Factory Installed Option GeneralAccessories InstallationFilter Part Number Economizer Hood Top Panel RemovalHood Divider Removed Economizer Hood Assembly Horizontal Return Duct Cover Panel and Hood Divider Removal Large ChassisLeft Hood Side Hood Assembly Supply AIR Temperature SAT SENSOR-The supply ConfigurationEconomizer Standard Sensors 11.7C 12.8C 14.4C 17.2C 20C 22.8C 25.6C Economizer Controller 607C-- -- a Economizer Wiring Diagram A10200 Cont. Ladder Wiring Diagram A10199 607C-- -- a 607C-- -- a CO2 Sensor Standard Settings Economizer Input/Output Logic CO2 Sensor Standard SettingsOperation Troubleshooting 607C--A 30 3 Phase with Economizer 607C--A 36-60 3 Phase with Economizer