Kenmore 153.33264 manual All Air from the Building, Louvers and Grilles, All Air from Outdoors

Page 18

Permanent

openings to the outside or

additional

rooms within

the building

FIGURE 13.

All Air from the Building

When additional air is to be provided to the confined area from additional room(s) within the building, the total volume of the room(s) must be of sufficient size to properly provide the necessary amount of fresh air to the water heater and other gas utilization equipment in the area. If you are unsure that the structure meets this requirement, contact your local gas utility company or other qualified agency for a safety inspection.

Each of the two openings shall have a minimum free area of 1 square inch per 1,000 BTUH of the total input rating of all gas utilization equipment in the confined area, but not less than 100 square inches (Figure 14).

Con,,ned'

Spaie

free area of the opening to which they connect. The minimum dimension of rectangular air ducts cannot be less than three inches.

The size of each of the two openings is determined by the method in which the air is to be provided. Refer to Table 4 to calculate the minimum free area for each opening. Figures 15, 16, 17 and 18 are typical examples of each method.

Louvers and Grilles

In calculating free area for ventilation and combustion air supply openings, consideration must be given to the blocking effect

of protection louvers, grilles, and screens. These devices can reduce airflow, which in turn may require larger openings to achieve the required minimum free area. Screens must not be smaller than 114" mesh. If the free area through a particular design of louver or grille is known, it should be used in calculating the specified free area of the opening. If the design and free area are not known, it can be assumed that most wood louvers wilt

allow 20 - 25% of free area while metal louvers and grilles will allow 60 - 75% of free area.

Louvers and grilles must be locked open or interconnected with the equipment so that they are opened automatically during equipment operation.

Keep louvers and grilles clean and free of debris or other obstructions.

TABLE 4

Minimum Free Area of Permanent Openings for Ventilation and Combustion Air Supply - All Air from Outdoors Only.

Based on total BTUH input rating for all utilizing equipment

within the confined space.

 

 

Minimum Free

Area

 

 

Opening

Source

Per Opening (sq. in.)

Reference

Drawing

*Direct to outdoors

1 sq. in, per 4000

BTUH

Figure

15

Vertical

Ducts

1 sq. in, per 4000

BTUH

Figure

16

Horizontal

Ducts

1 sq. in, per 2000

BTUH

Figure

17

Single Opening

1 sq. in, per 3000

BTUH

Figure

18

Example: A water heater with an input rating of 50,000 BTUH using horizontal ducts would require each opening to have a minimum free area of 25 square inches.

Minimum free area = 50,000 BTUH x 1 sq. in. / 2000 BTUH = 25 sq. in.

, These openings connect directly with the outdoors through a venti- lated attic, a ventilated crawl space, or through an outside walt.

Consult the local codes of your area for specific ventilation and combustion air requirements.

FIGURE 14.

All Air from Outdoors

Outdoor fresh air can be provided to a confined area either directly or by the use of vertical and horizontal ducts. The fresh air can be taken from the outdoors or from crawl or attic spaces that freely communicate with the outdoors. Attic or crawl spaces cannot be closed and must be properly ventilated to the outside.

Ductwork must be of the same cross-sectional area as the

18

Image 18
Contents =I=€di,lld 317997-000Read and follow water heater warnings and instructions Important DefinitionsFire Hazard Improper installation and use may result in property damageFire or Explosion Hazard Explosion HazardVent Connectors Chimney InstallationClearances Accessibility High Altitude Installation Get to know your Water HeaterElectricalConnections SolarInstallation WiringDiagram PoweredAnodeRodOperationSears Installation Service Master Protection AgreementsExcessive Weight Hazard Important Information About This Water Heater153.332620 Natural 40,000 42.6153.332640 189 Natural 40,000 42.6 376or4102 559 57.13 1451 Materials Needed Gas Supply Piping SwitchTransformer Pressure Relief ValveCombustion Air Supply and Ventilation Installation ChecklistWater Heater Location Vent Pipe SystemRemoving the Old Water Heater ManualgasCarbon Monoxide Poisoning Hazard Location RequirementsSite Location SensorHigh Altitude Installation Pmpey Damage HazardMinimum Clearance Locations Gas Piping Gas Pressure TestingGas Pressure Gas Requirements Explosion HazardGas Pipe Capacity Table Atuml Gas Pipe Capacity Table Cue FtJHrUnconfined Space Confined SpaceCarbon Monoxide Warning All Air from Outdoors All Air from the BuildingLouvers and Grilles Minimum FreeDraft Hood Installation Vent Pipe SystemAll Air from Outdoors Through Ventilated Attic Chimney Connection Vent ConnectorsVent Pipe Size Vertical Exhaust Gas VentPiping Installation Venting Gas Vent System With Type B Double Wall Vent PipeTemperature and Pressure Relief Valve Closed System/Thermal Expansion Pmpey Damage HazardTemperature Pressure Relief Valve Relief Valve and Pipe InsulationDischarge Line Solar Installation Electrical ConnectionsFailure to do so can result in death Explosion or fire Manual before changing temperatureOperating Instructions Replace view port if glass is missing Or damagedBurn Hazard Water Heater OperationChecking the Draft Do not touch vent Doing so can result in burnsEmergency Shut Down Water TemperatureBurner Flames RegulationPowered Anode Operation Powered Anode SystemHotter J Temperature and Pressure Relief Valve Explosion Harzard Routine Preventive MaintenanceDraining and Flushing Removing the Manifold/Burner Assembly Replacement PartsRemoving the Burner from the Manifold/ Burner Assembly Replacing the Flame Sense/Hot Surface igniter AssemblyCleaning the Combustion Chamber and Air Diverter Assembly Replacing the Manifold/Burner AssemblyRemoving and Replacing the Gas Control Valve/Thermostat Door Gasket Burner ISlot ViewportReplacing the Gas Valve Start Up Conditions Smoke Odor Safety Shut-off and Thermal SwitchCondensation AIR In Hot Water FaucetsLeakage Checkpoints Pressurized Combustion Chamber System Operational Checklist Possible CausesCorrective Action Power IGN Heating Clean SW, OPEN, and Clean Screen Flashing Open YES Pressurized Combustion Chamber Key Parts Description153.332620 153.332640 Page Managemylife
Related manuals
Manual 44 pages 10.06 Kb

153.33262, 153.33264 specifications

The Kenmore 153.33262 and 153.33264 are highly versatile and efficient portable air conditioners designed to provide optimal cooling solutions for indoor spaces. These models stand out in their class due to their advanced features, technologies, and user-friendly characteristics, making them suitable for a variety of environments, from small apartments to large rooms.

One of the primary features of both the Kenmore 153.33262 and 153.33264 is their high cooling capacity. With powerful BTUs, they can effectively cool spaces up to a specified square footage. This capability ensures that users can maintain a comfortable indoor climate even during the hottest summer months. Their energy efficiency is another notable aspect, allowing homeowners to enjoy cooler air without incurring exorbitant energy bills.

The two models are equipped with various modes of operation, including cooling, fan, and dehumidifying modes. This multifunctionality allows users to customize their comfort based on prevailing weather conditions. For instance, the dehumidifying mode effectively reduces excess moisture in the air, creating a more comfortable environment, particularly in humid regions.

Both air conditioners come with a user-friendly digital interface that features an easy-to-read LED display. The interface allows for straightforward adjustments to the temperature, fan speed, and operating modes. Furthermore, remote control functionality enhances convenience, enabling users to change settings from across the room.

In terms of technology, these models incorporate a self-evaporating system that minimizes the need for manual water drainage. This feature is particularly advantageous for users who prefer low-maintenance options. Additionally, both units feature a washable air filter, designed to capture dust and allergens, improving air quality and ensuring that the units operate efficiently.

Portability is another significant characteristic of the Kenmore 153.33262 and 153.33264. Built-in caster wheels and side handles allow for easy movement from room to room, making them ideal for temporary cooling needs. The easy installation process and included window exhaust kit mean users can set up the units quickly without requiring professional assistance.

In conclusion, the Kenmore 153.33262 and 153.33264 portable air conditioners offer a robust combination of high cooling performance, energy efficiency, and user-friendly features. Their advanced technologies and versatile functionalities make them an ideal choice for those seeking effective indoor air conditioning solutions.