Freeze Protection

Set the freeze sensing switch SW2-2 on the printed circuit board for applications using a closed loop antifreeze solution to “LOOP”. On applications using an open loop/ground water system (or closed loop no antifreeze), set this dip switch to “WELL”, the factory default setting. (Refer to the Dip Switch Field Selection table on page 24.)

Condensate Drain

On vertical units, the internal condensate drain assembly consists of a drain tube which is connected to the drain pan, a 3/4-inch PVC female adapter and a flexible connecting hose. The female adapter may exit either the front or the side of the cabinet. The adapter should be glued to the field-installed PVC condensate piping. On vertical upflow units, a condensate hose is inside all cabinets as a trapping loop; therefore, an external trap is not necessary.

On horizontal units, a PVC stub is provided for condensate drain piping connection. An external trap is required (see below). If a vent is necessary, an open stand pipe may be applied to a tee in the field-installed condensate piping.

Figure 5: Horizontal Drain Connection

3/4" PVC Coupling

Vent (if needed)

3/4" PVC 1/8" per foot

3/4” PVC tube stub

1.5"

1.5"

 

 

Figure 6: Unit Pitch for Drain

1/2'' Pitch

Drain

8

Image 8
Contents Envision Residential Installation Manual Model Nomenclature VoltageTable of Contents General Installation Information Safety ConsiderationsInstalling Vertical Units Moving and StorageInstalling Horizontal Units Horizontal Unit MountingDuct System Water PipingWater Quality Freeze Protection Condensate DrainClosed Loop Ground Source Systems Multiple Units on One Flow CenterOpen Loop Ground Water Systems Solenoid ValveDesuperheater Connections Water Tank PreparationPlumbing Installation Desuperheater StartupUnit Power Connection Accessory RelayElectrical Connections GeneralAuxiliary Heat Ratings Pump WiringElectronic Thermostat Unit Electrical Data Single speed with ECM motorPerforming this operation Setting Fan Speed PSCFan Performance Data PSC Setting Fan Speed ECM Fan Performance Data ECMVertical Dimensional Data Top Air DischargeHorizontal Dimensional Data TOP ViewBottomflow Left ReturnPhysical Data Single Speed Single SpeedPhysical Data Dual Capacity Dual CapacityWiring Schematics Envision Single Speed Wiring Schematic 208-230/60/1Envision Single Speed Wiring Schematic 208-230/60/1 ECM 97P774-01 6/29/06 Envision Dual Capacity Wiring Schematic 208-230/60/1- ECM Unit Power 208-230/60/197P774-02 6/29/06 Microprocessor Control ECM2 Airflow Selection DIP Switches SW1 Heat, 3rd Stage Y1,Y2,W Dual Capacity UnitsEmergency Heat W only Cooling OperationCompressor Monitoring/Comfort Alert Comfort Alert Flash CodesComforTalk Fault FlashThermostat Displays DIP Switch Settings Description OFF PositionStartup Steps Before Powering Unit, Check The FollowingUnit Startup Operation Logic Data PSCUnit Operating Parameters Single Speed ModelsDual Capacity Models First Stage OperationPressure Drop GPMTroubleshooting LED Definitions and DiagnosticsStandard Microprocessor Controls Refrigerant SystemsPreventive Maintenance Replacement ProceduresManufactured by WFI 9000 Conservation Way Fort Wayne,