Envision Peripherals R-410A Closed Loop Ground Source Systems, Multiple Units on One Flow Center

Page 9

ENVISION RESIDENTIAL INSTALLATION MANUAL

Closed Loop Ground Source Systems

Note: For closed loop systems with antifreeze protection, set SW2-2 to the “loop” position (see table on page 28).

Once piping is completed between the unit, pumps and the ground loop (see figure below), final purging and charging of the loop is required. A flush cart (or a 1.5 HP pump minimum) is needed to achieve adequate flow velocity in the loop to purge air and dirt particles from the loop itself. Antifreeze solution is used in most areas to prevent freezing. Flush the system adequately to remove as much air as possible then pressurize the loop to a static pressure of 40-50 PSI (summer) or 50-75 PSI (winter). This is normally adequate for good system operation. Loop static pressure will fluctuate with the seasons. Pressures will be higher in the winter months than during the cooling season. This fluctuation is normal and should be considered when initially charging the system.

After pressurization, be sure to open the plug 1 turn in the end of the loop pump motor(s) (if applicable) to allow trapped air to be discharged and to ensure that the motor housing has been flooded. Ensure that the loop pumps provide adequate flow through the unit(s) by checking the pressure drop across the heat exchanger and comparing it to the unit capacity data in the specification catalog. 2.5 to 3 GPM of flow per ton of cooling capacity is recommended in earth loop applications.

Figure 7: Closed Loop Ground Source Application

Auxiliary Heat

GeoLink®

Supply

Polyethylene w/

 

Unit Supply

Armaflex®

Insulation

 

 

Flexible Duct

 

Collar

 

Auxiliary

 

Heater

 

Knockout

 

Unit Power

 

Desuperheater

 

Connections

Disconnects

(If Applicable)

Drain

Low

P/T

Voltage to

P/T Plugs

Thermostat

 

Vibration

Absorbing Pad

TO

LOOP

 

oLink

®

Ge

 

Flow

 

Cent

er

 

 

 

Insulated piping or hose kit

Note: Additional information can be found in Flow Center installation manual (IM1961) and Flush Cart manual (WFS302).

Multiple Units on

One Flow Center

When two units are connected to one loop pumping system, pump control is

Figure 8: Primary/Secondary Hook-up

Envision to Envision

Envision to Envision

Envision to

Microprocessor Units

Microprocessor Units

Electromechanical Units

automatically achieved by connecting the SL terminals on connector P2 in both units with 2-wire thermostat wire. These terminals are polarity dependant (see Figure 8). The loop pump(s) may be powered from either unit, whichever is more convenient. If either unit calls, the loop pump(s) will automati- cally start. The use of two units on one flow center is generally limited to a total of 20 GPM capacity.

Dual Capacity Envision Unit #1

Shut

C

C

SL1

SL1

Down

 

 

 

In

Out

With pump

 

 

 

 

wired to Unit 1

 

 

 

With pump

 

 

 

 

wired to

 

 

 

 

 

Unit 2

 

 

 

 

 

 

 

 

 

 

 

Shut

C

C

SL1

SL1

Down

In

Out

Envision Unit #2 Dual Capacity

Single Speed

Envision Unit #1

Shut

C

C

SL1

SL1

Down

 

 

In

Out

With pump wired to Unit 1

With pump wired to Unit 2

Shut

C

C

SL1

SL1

Down

In

Out

Envision Unit #2

Single Speed

Envision Unit #1

Shut

C

C

SL1

SL1

Down

 

 

 

 

In

Out

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C S

To Electromechanical Unit

9

Image 9
Contents Envision Residential Installation Manual Voltage Model NomenclatureTable of Contents Safety Considerations General Installation InformationInstalling Vertical Units Moving and StorageHorizontal Unit Mounting Installing Horizontal UnitsWater Piping Duct SystemWater Quality Condensate Drain Freeze ProtectionMultiple Units on One Flow Center Closed Loop Ground Source SystemsSolenoid Valve Open Loop Ground Water SystemsWater Tank Preparation Desuperheater ConnectionsDesuperheater Startup Plumbing InstallationAccessory Relay Unit Power ConnectionElectrical Connections GeneralPump Wiring Electronic ThermostatAuxiliary Heat Ratings Single speed with ECM motor Unit Electrical DataSetting Fan Speed PSC Fan Performance Data PSCPerforming this operation Fan Performance Data ECM Setting Fan Speed ECMTop Air Discharge Vertical Dimensional DataTOP View Horizontal Dimensional DataLeft Return BottomflowSingle Speed Physical Data Single SpeedDual Capacity Physical Data Dual CapacityEnvision Single Speed Wiring Schematic 208-230/60/1 Wiring SchematicsEnvision Single Speed Wiring Schematic 208-230/60/1 ECM 97P774-01 6/29/06 Unit Power 208-230/60/1 Envision Dual Capacity Wiring Schematic 208-230/60/1- ECM97P774-02 6/29/06 Microprocessor Control Heat, 3rd Stage Y1,Y2,W Dual Capacity Units ECM2 Airflow Selection DIP Switches SW1Emergency Heat W only Cooling OperationComfort Alert Flash Codes Compressor Monitoring/Comfort AlertFault Flash Thermostat DisplaysComforTalk Description OFF Position DIP Switch SettingsBefore Powering Unit, Check The Following Unit StartupStartup Steps PSC Operation Logic DataSingle Speed Models Unit Operating ParametersFirst Stage Operation Dual Capacity ModelsGPM Pressure DropLED Definitions and Diagnostics TroubleshootingStandard Microprocessor Controls Refrigerant SystemsReplacement Procedures Preventive MaintenanceManufactured by WFI 9000 Conservation Way Fort Wayne,