ENVISION RESIDENTIAL INSTALLATION MANUAL

Preventive Maintenance

Water Coil Maintenance

1.Keep all air out of the water. An open loop system should be checked to ensure that the well head is not allowing air to infiltrate the water line. Lines should always be airtight.

2.Keep the system under pressure at all times. It is recommended in open loop systems that the water control valve be placed in the discharge line to prevent loss of pressure during off cycles. Closed loop systems must have positive static pressure.

Note: On open loop systems, if the installation is in an area with a known high mineral content (125 PPM or greater) in the water, it is best to establish with the owner a periodic maintenance schedule so the coil can be checked regularly. Should periodic coil cleaning be necessary, use standard coil cleaning procedures which are compatible with either the cupronickel or copper water lines. Generally, the more water flowing through the unit the less chance for scaling.

Other Maintenance

Filters

Filters must be clean to obtain maximum performance. They should be inspected monthly under normal operating condi- tions and be replaced when necessary. Units should never be operated without a filter.

Condensate Drain

In areas where airborne bacteria produce a slime in the drain pan, it may be necessary to treat chemically to minimize the problem. The condensate drain can pick up lint and dirt, especially with dirty filters. Inspect twice a year to avoid the possibility of overflow.

Blower Motors

ECM blower motors are equipped with sealed ball bearings and require no periodic oiling.

PSC blower motors should only be lubricated if dry operation is suspected.

Desuperheater Coil

See Water Coil Maintenance section above.

Air Coil

The air coil must be cleaned to obtain maximum performance. Check once

a year under normal operating conditions and, if dirty, brush or vacuum (with a CAUTION: Fin edges are sharp. brush attachment) clean. Care must be taken not to damage the aluminum fins

while cleaning.

Replacement Procedures

Obtaining Parts

When ordering service or replacement parts, refer to the model number and serial number of the unit as stamped on the serial plate attached to the unit. If replacement parts are required, mention the date of installation of the unit and the date of failure, along with an explanation of the malfunctions and a description of the replacement parts required.

In-Warranty Material Return

Material may not be returned except by permission of authorized warranty personnel. Contact your local distributor for warranty return authorization and assistance.

39

Image 39
Contents Envision Residential Installation Manual Voltage Model NomenclatureTable of Contents Moving and Storage General Installation InformationSafety Considerations Installing Vertical UnitsHorizontal Unit Mounting Installing Horizontal UnitsWater Piping Duct SystemWater Quality Condensate Drain Freeze ProtectionMultiple Units on One Flow Center Closed Loop Ground Source SystemsSolenoid Valve Open Loop Ground Water SystemsWater Tank Preparation Desuperheater ConnectionsDesuperheater Startup Plumbing InstallationGeneral Unit Power ConnectionAccessory Relay Electrical ConnectionsPump Wiring Electronic ThermostatAuxiliary Heat Ratings Single speed with ECM motor Unit Electrical DataSetting Fan Speed PSC Fan Performance Data PSCPerforming this operation Fan Performance Data ECM Setting Fan Speed ECMTop Air Discharge Vertical Dimensional DataTOP View Horizontal Dimensional DataLeft Return BottomflowSingle Speed Physical Data Single SpeedDual Capacity Physical Data Dual CapacityEnvision Single Speed Wiring Schematic 208-230/60/1 Wiring SchematicsEnvision Single Speed Wiring Schematic 208-230/60/1 ECM 97P774-01 6/29/06 Unit Power 208-230/60/1 Envision Dual Capacity Wiring Schematic 208-230/60/1- ECM97P774-02 6/29/06 Microprocessor Control Cooling Operation ECM2 Airflow Selection DIP Switches SW1Heat, 3rd Stage Y1,Y2,W Dual Capacity Units Emergency Heat W onlyComfort Alert Flash Codes Compressor Monitoring/Comfort AlertFault Flash Thermostat DisplaysComforTalk Description OFF Position DIP Switch SettingsBefore Powering Unit, Check The Following Unit StartupStartup Steps PSC Operation Logic DataSingle Speed Models Unit Operating ParametersFirst Stage Operation Dual Capacity ModelsGPM Pressure DropRefrigerant Systems TroubleshootingLED Definitions and Diagnostics Standard Microprocessor ControlsReplacement Procedures Preventive MaintenanceManufactured by WFI 9000 Conservation Way Fort Wayne,