SPI9000 Inverter Unit FI9 – FI14 User Manual

September 2006

Table 5-6: Monitored Signals

Code

Signal Name

Unit

Description

 

 

 

 

 

 

 

 

V7.1

Output frequency

Hz

Frequency to the motor

 

 

 

 

V7.2

Frequency reference

Hz

 

 

 

 

 

V7.3

Motor speed

rpm

Calculated motor speed

 

 

 

 

V7.4

Motor current

A

Measured motor current

 

 

 

 

V7.5

Motor torque

%

Calculated torque based/nominal torque of the unit

 

 

 

 

V7.6

Motor power

%

Calculated actual power/nominal power of the unit

 

 

 

 

V7.7

Motor voltage

V

Calculated motor voltage

 

 

 

 

V7.8

DC-link voltage

V

Measured DC-link voltage

 

 

 

 

V7.9

Unit temperature

°C

Heatsink temperature

 

 

 

 

V7.10

Motor temperature

%

Calculated motor temperature

 

 

 

 

V7.11

Voltage input

V

AI1

 

 

 

 

V7.12

Current input

mA

AI2

 

 

 

 

V7.13

DIN1, DIN2, DIN3

Digital input statuses

 

 

 

 

V7.14

DIN4, DIN5,DIN6

Digital input statuses

 

 

 

 

V7.15

DO1, RO2, RO3

Digital and relay output statuses

 

 

 

 

V7.16

Analog output

mA

AO1

 

current

 

 

 

 

 

 

M1.17

Multimonitoring

 

Displays three selectable monitoring values. See

 

items

 

Page 5-23.

 

 

 

 

Note: Applications may embody more monitoring values.

Parameter Menu (M2)

Parameters are the way of conveying the commands of the user to the inverter. Parameter values can be edited by entering the Parameter Menu from the Main Menu when the location indication M2 is visible on the first line of the display. The value editing procedure is presented in Figure 5-6.

Pressing Menu Button Right once takes you to the Parameter Group Menu (G#). Locate the desired parameter group by using the Browser buttons and press Menu Button Right again to see the group and its parameters. Use the Browser buttons to find the parameter (P#) you want to edit. Pressing Menu Button right takes you to the edit mode. As a sign of this, the parameter value starts to blink. You can now change the value in two different ways:

Set the desired value with the Browser buttons and confirm the change with the ENTER button. Consequently, the blinking stops and the new value is visible in the value field.

Press Menu Button Right once more. Now you will be able to edit the value digit by digit. This may come in handy, when a relatively greater or smaller value than that on the display is desired. Confirm the change with the ENTER button.

The value will not change unless the ENTER button is pressed. Pressing Menu Button Left takes you back to the previous menu.

Several parameters are locked, i.e. cannot be edited, when the drive is in RUN status. If you try to change the value of such a parameter the text *Locked* will appear on the display. The inverter must be stopped to edit these parameters.

The parameter values can also be locked using the function in menu M6 (see Page 5-22).

5-8

For more information visit: www.EatonElectrical.com

MN04004002E

Image 60
Contents SPI9000 Inverter Unit FI9 FI14 Page Important Notice Please Read Contents SPI9000 Inverter Unit Block Diagram List of Figures25 HMI Acknowledge Timeout List of TablesSafety Definitions and SymbolsHazardous High Voltage September Vii Grounding and ground fault protection Motor and Equipment SafetyOverview I 0 1 6 a 0 4 a 1 NReceiving and Inspection FI9 FI14 Inverter Unit Catalog Numbering SystemMaintenance Technical DataStandard Features of SPI Inverter Units StorageSPI9000 Inverter Unit Block Diagram Power Ratings 380 500V AC, 50/60 Hz, Three-Phase Inverters RatingsSupply Voltage 465 800V DC, Motor Voltage 380 500V AC 525 690V AC, 50/60 Hz, Three-Phase Inverters Ratings Supply Voltage 640 1100V DC, Motor Voltage 525 690V ACControl Characteristics Technical InformationDescription Specification Supply Connection Motor ConnectionEMC at Default Settings SafetyDescription Specification Ambient Conditions Control ConnectionsDC Currents for 465 800V DC Supply Voltage DC Currents for 640 1100V DC Supply VoltageStructure Inom Output Motor COS IDC Input Dimensions Approximate Dimensions in Inches mm Inverters Voltage DiaMounting SPI9000 FI10 Inverter Dimensions SPI9000 FI12 Inverter Dimensions Fan Cooling Frames FI9 to FI14Installation Space Power Losses Approximate Dimensions in Inches mm Frame VoltageMounting Space Requirements Required Cooling AirPower Wiring FI9/FI10 Basic Wiring Diagram with ChargingFI9/FI10 Basic Wiring Diagram without Charging FI12 Basic Wiring Diagram with Charging FI12 Basic Wiring Diagram without Charging FI13 Basic Wiring Diagram with Charging FI13 Basic Wiring Diagram without Charging FI14 Basic Wiring Diagram with Charging FI14 Basic Wiring Diagram without Charging Power Connections DC Supply and Motor CablesCable Types Required to Meet Standards Fuses, 465 800V DC InvertersFuses, 640 1100V DC Inverters Fuses Used in 640 1100V DC InvertersInformation about fuses Inverter Supply and Motor Cables 380 500V AC Cable Sizes for 380 500V ACTerminal Sizes 380 500V AC Terminal Sizes for 380 500V ACInverter Supply and Motor Cables 525 690V AC Cable Sizes for 525 690V ACTerminal Sizes 525 690V AC Terminal Sizes for 525 690V ACInstallation Instructions Cable DistancesDistance Between Cables Shielded Inches m Cable in Feet m Frame Sizes Cable Installation and the UL Standards Cable and Motor Insulation ChecksTerminal Tightening Torques Tightening TorqueSeptember Control Wiring Control BoardControl Wiring Details Inverters Connected in ParallelOption Board A9 Wiring Diagram Control Cables Tightening Torques of Option Board TerminalsTerminal Screw Tightening Torque Lb-in Galvanic Isolation Barriers Galvanic Isolation BarriersControl I/O Terminal Signals on Option Board A9 Terminal Signal Technical InformationDigital Input Signal Inversions Control I/O Terminal Signals on Option Board A2Control I/O Terminal Signals on Option Board A3 Jumper Selections on Option Board A9 10 Jumper Blocks on Option Board A911 Jumper Selection for Option Board A9 September Indicators on the Keypad Display Menu InformationKeypad Operation Drive Status Indicators Drive Status IndicatorsControl Place Indicators Control Place IndicatorsKeypad Pushbuttons Status LEDs Green Green RedStatus LEDs Green Green Red Text LinesButton Descriptions Menu Navigation Keypad Display DataKeypad Navigation Chart Monitoring Menu M1 Monitoring MenuMonitored Signals Parameter Menu M2Parameter Value Change Procedure Keypad Control Menu M3Selection of Control Place Selection of Control Place Keypad ReferenceActive Faults Menu M4 Keypad DirectionStop Button Activated Fault Time Data Record Fault Type Symbol MeaningFault Time Recorded Data Fault History Menu M5Real Time Record Data Units Description10 Fault History Menu System Menu M6Code Function Min Max Unit Default Cust Selections 10 System Menu Functions10 System Menu Functions Selection of Language 11 Selection of Language Application SelectionCopy Parameters Parameter Sets S6.3.1Upload parameters to keypad To keypad, S6.3.2 Automatic Parameter Backup P6.3.4 Download parameters to drive From keypad, S6.3.3Parameter Comparison 15 Parameter ComparisonSafety Password S6.5.1Parameter Lock P6.5.2 Start-Up Wizard P6.5.3Default Page P6.6.1 Multimonitoring Items P6.5.4Default page in the operating menu P6.6.2 Timeout Time P6.6.3Contrast Adjustment P6.6.4 Backlight Time P6.6.5Hardware Settings Internal Brake Resistor Connection P6.7.1HMI Acknowledge Timeout P6.7.3 Fan Control P6.7.2Number of retries to receive HMI acknowledgement P6.7.4 System infoTotal Counters 11 Counter Pages12 Resettable Counters Trip CountersSoftware S6.8.3 13 Software Information PagesApplications S6.8.4 14 Applications Information PagesHardware S6.8.5 15 Hardware Information PagesExpander Boards S6.8.6 Expander Board Menu M7Code Parameter Min Max Default Cust Selections Further Keypad FunctionsSeptember Safety Precautions Start-UpSequence of Operation September September Appendix a Fault Codes Table A-1 Fault CodesFault Code Possible Cause Solution Eeprom Programmable Faults only Table A-1 Fault Codes September MN04004002E September Page Company Information

SPI9000 specifications

The Eaton Electrical SPI9000 is a cutting-edge power management system designed to enhance efficiency and reliability in electrical distribution. This state-of-the-art solution integrates advanced technologies to optimize performance, making it an ideal choice for various industrial and commercial applications.

One of the standout features of the SPI9000 is its scalability. Businesses can easily adapt the system to meet their unique power needs, whether for a single facility or multiple sites. This flexibility is crucial in today's fast-paced environment, where operational demands can shift rapidly. The system is engineered to grow alongside your business, providing robust power management as requirements evolve.

At the heart of the SPI9000 is its intelligent monitoring capability. The system utilizes real-time data analytics to monitor energy consumption, detect anomalies, and predict maintenance needs. This proactive approach not only helps in reducing downtime but also cultivates a culture of energy efficiency within organizations. By leveraging insights derived from data, companies can make informed decisions that lead to significant cost savings.

The SPI9000 incorporates advanced communications technology, allowing seamless integration with existing building management systems. This interoperability is vital for creating smart grids and enhancing overall control of electrical networks. Additionally, the system supports various communication protocols, including Modbus, BACnet, and Ethernet, ensuring compatibility with a wide range of devices and applications.

Safety is paramount in any electrical system, and the SPI9000 excels in this regard. It features enhanced protective measures, including overcurrent protection, short-circuit protection, and arc flash detection, ensuring the safety of both personnel and equipment. These safety features not only safeguard investments but also contribute to creating a safer working environment.

Energy efficiency is another cornerstone of the SPI9000 design. The system is equipped with advanced power quality monitoring features, which help identify and mitigate issues related to harmonics, voltage sags, and swells. By maintaining optimal power quality, the SPI9000 ensures that equipment operates efficiently, extending its lifespan while reducing energy costs.

In summary, the Eaton Electrical SPI9000 is a versatile and efficient power management solution that brings together scalability, intelligent monitoring, advanced communication capabilities, enhanced safety features, and energy efficiency. Thanks to its innovative technologies and characteristics, the SPI9000 serves as an indispensable tool for modern businesses seeking to streamline their electrical operations and enhance their energy management strategies.