Unit configuration menu: “Configuration”

9. Operating limits (cooling)

Low Amb Cooling

On

Low Amb Limit

-10.0°C

CW High Limit

On

CW High Limit

15.0°C

 

 

Low ambient temperature limitation:

On: (factory setting) Low ambiant limited

Off: Low ambient temperature not limited

Low ambient limit: -20 to 20°C: factory setting -10°C

Chilled water high limitation:

On: High water temperature limited (factory setting)

Off: High water temperature not limited

Chilled water high limit: 10 to 20 °C: Factory setting 15°C

10. Defrost demand setpoint

Low Amb Heat

-10.0°C

StP Min Temp

10.0°C

Defrost Max

12.0°C

StP Max Temp

22.0°C

 

 

Low ambient heating: -20 to 20°C, factory setting -10°C

Setpoint at minimum ambient: 1 to 30°C, (factory setting 10°C) Maximum ambient: -20 to 20°C: (factory setting 12°C)

Setpoint at maximum ambient: 1 to 30°C, (factory setting 22°C)

11. Defrost cycle termination

To access one of the parameters

displayed, press

 

and change

value using

or

. Confirm the

value by pressing

 

Term Stp

 

20.0 bar

Drying time

 

12 s

Max Defrost

 

7 min

Min cycle

 

25 min

Term StP: Defrost termination setpoint (10 to 30bar - factory setting: 20 bar)

Drying time: Drying time (5 to 30

seconds - factory setting: 12s)

Max Defrost: Maximum defrost time (5 to 30 minutes - factory setting:

7 min)

Min cycle: Minimum time between defrost cycle (15 to 60min - factory setting: 25 min)

Note: Dual circuits have two independent refrigerant circuits. Defrost cycle will only occur on the circuit that needs it. The other circuit will continue its normal operation if required.

12. Compressor alarm

To access one of the parameters

displayed, press Manual background and change

value using Manual background or Manual background . Confirm the value by pressing Manual background

Compressor alarm

00000 h

Default parameters?

N

Compressor alarm: Operating hours for a warning (0 to 999000 hours by 1000 hours)

Setting compressor alarm at 000000 h will disable the function.

Note: Total operating hours = compressor running hours + 3 x compressor starts

Default parameters?: Set the default parameters

Y: Reset all parameters

N: Keep all parameters

Note: When resetting, all parameters programmed on site will be definitively lost. Only factory default set parameters will be kept. Full configuration of the unit will have to be checked.