American Standard TRACER CH532 manual Unit configuration menu “Configuration”, 03.0C

Models: TRACER CH532

1 32
Download 32 pages 38.41 Kb
Page 19
Image 19
03.0°C

Unit configuration menu: “Configuration”

2. Compressors timers

To access one of the parameters

displayed, press

 

and change

value using

or

. Confirm the

value by pressing

 

ACC 1st Start

 

2 min

ACC On-On

 

5 min

Min On-On

 

060 s

Min Off-Off

 

015 s

ACC 1st Start: Short cycle compressor at first start (0 to 60 min - factory setting: 2min)

ACC On-On:Short cycle between 2 starts of the same compressor (2 to 10 min - factory: 5 min)

Min On-On:Minimum time to add compressor (5 to 240 s - factory setting: 60s)

Min Off-Off:Minimum time to remove compressor (1 to 120 s factory setting 15s)

3. HP Control

To access one of the parameters

displayed, press

 

and change

value using

or

. Confirm the

value pressing

 

 

Fan control

 

1Speed

Fan Ctrl Stp

 

15.0 b

Dead band Fan

 

06.0 b

Fan Control: Fan type:

1 speed: 1 Speed fan

2 speed: 2 Speed fan

Invert: Inverter

Fan Ctrl StP: Fan control setpoint

(10 to 30 bar - factory setting: 15 bar)

Dead band Fan: Fans regulation dead band (2 to 8 bar - factory setting: 5 bar)

4. Control dead bands

To access one of the parameters

displayed, press Manual background and change

value using Manual background or Manual background . Confirm the value by pressing Manual background

Dead band Cmp

03.0°C

Antifreeze02.0°C

Heater03.0°C

Dead band Cmp: Compressors regulation dead band around water temperature (0.4 to 8.0°C - factory setting: 3.0°C)

AntiFreeze: Cold water temperature limit (-15 to 10°C - factory setting: 2°C)

Heater: Evaporator heater setpoint according to ambient air temperature (0 to 10°C - factory setting: 3°C)

5. Winter Freeze Protection

CW High Limit

15°C

Pmp Cycle OFF

10 min

WinFreezeProtPmp

Yes

Ctrl Pump Required

 

 

 

Chilled water high limit: (15 to 25°C: factory setting 15°C)

Water pump cycle OFF: (5 to 15 min: factory setting 10min)

Winter Freeeze protection with pump:

No Heater or Ethylene

Glycol Required

Yes Ctrl Pump Required

CG-SV01B-E4

19

Page 19
Image 19
American Standard TRACER CH532 manual Unit configuration menu “Configuration”, 03.0C