American Standard TRACER CH532 manual Alarms, History events record, CG-SV01B-E4

Models: TRACER CH532

1 32
Download 32 pages 38.41 Kb
Page 24
Image 24
Table 5 - History events record

Alarms

Table 5 - History events record

No Message

Reset Type

Unit status

Description

 

No History

Auto

Unit On

No alarm was recorded

 

Air Sensor

Auto

Unit Off

Faulty sensor, out of range -30..+80°C

 

 

 

 

(short circuit or open circuit)

 

Water In Sensor

Auto

Unit On

Faulty sensor, out of range -30..+80°C

 

 

 

 

(short circuit or open circuit)

 

Water Out Sensor

Auto

Unit Off

Faulty sensor, out of range -30..+80°C

 

 

 

 

(short circuit or open circuit)

 

Lp Sensor Ckt1

Auto

Circuit 1 Off

Faulty sensor, out of range 0..10V, 0..1V,0..20mA or

4..20mA

 

 

 

following configuration

 

Hp Sensor Ckt1

Auto

Circuit 2 Off

Faulty sensor, out of range 0..10V, 0..1V,0..20mA or

4..20mA

 

 

 

following configuration

 

Lp Sensor Ckt2

Auto

Circuit 1 Off

Faulty sensor, out of range 0..10V, 0..1V,0..20mA or

4..20mA

 

 

 

following configuration

 

Hp Sensor Ckt2

Auto

Circuit 2 Off

Faulty sensor, out of range 0..10V, 0..1V,0..20mA or

4..20mA

 

 

 

following configuration

 

Fan Protection 1

Auto

Unit On

A fan on the circuit 1 is faulty

 

Fan Protection 2

Auto

Unit On

A fan on the circuit 2 is faulty

 

Lp Ckt1 fault

Auto or Manual

Circuit 1 Off

Lp circuit 2 is below the setpoint. Manual reset after 3 faults

 

 

 

within 1 hour

 

Lp Ckt2 fault

Auto or Manual

Circuit 2 Off

Lp circuit 1 is below the setpoint. Manual reset after 3 faults

 

 

 

within 1 hour

 

Low Water Temp

Manual

Unit Off

LWT < antifreeze or INT (antifreeze-EWT)<=10°Cxsecond

Comp. A1 Fault

Auto or Manual

CMP A1 Off

Manual reset if CMP A1 failure > 35 min or 6 failures within

 

 

 

3 hours 30 min

 

Comp. B1 Fault

Auto or Manual

CMP B1 Off

Manual reset if CMP B1 failure > 35 min or 6 failures within

 

 

 

3 hours 30 min

 

Comp. C1 Fault

Auto or Manual

CMP C1 Off

Manual reset if CMP C1 failure > 35 min or 6 failures within

 

 

 

3 hours 30 min

 

Comp. A2 Fault

Auto or Manual

CMP A2 Off

Manual reset if CMP A2 failure > 35 min or 6 failures within

 

 

 

3 hours 30 min

 

Comp. B2 Fault

Auto or Manual

CMP B2 Off

Manual reset if CMP B2 failure > 35 min or 6 failures within

 

 

 

3 hours 30 min

 

Comp. C2 Fault

Auto or Manual

CMP C2 Off

Manual reset if CMP C2 failure > 35 min or 6 failures within

 

 

 

3 hours 30 min

 

Hp Ckt1 Fault

Manual

Circuit 1 Off

High pressure switch Cut-Out circuit 1

 

Hp Ckt2 Fault

Manual

Circuit 2 Off

High pressure switch Cut-Out circuit 2

 

Ckt1 Fault

Manual

Circuit 1 Off

Simultaneous faults compressor A1 and (B1 or C1)

 

Ckt2 Fault

Manual

Circuit 2 Off

Simultaneous faults compressor A2 and (B2 or C2)

 

Unit Fault

Manual

Unit Off

Simultaneous faults on all the compressors

 

Ext Setpoint Signal

Auto

Unit Off

Faulty sensor, out of range 0..10V, 0..1V,0..20mA or 4..20mA

 

 

 

following configuration

 

Low Ambient

Auto

Unit Off

Air temperature below the setpoint while unit On

 

Water Pump 1

Manual

Unit On

Fault on water pump #1

 

Water Pump 2

Manual

Unit On

Fault on water pump #2

 

Water Flow

Auto

Unit Off

Loss of water flow for more than 4 sec when the system is On.

 

 

 

Pump restarts by a manual unit Off and On

 

Defrost Ckt1

Auto

Unit On

Defrost on circuit 1

 

Defrost Ckt2

Auto

Unit On

Defrost on circuit 2

 

24

CG-SV01B-E4

Page 24
Image 24
American Standard TRACER CH532 manual Alarms, History events record, CG-SV01B-E4